Allen-Bradley PowerFlex 750 Series Installation Instructions Manual

Hide thumbs Also See for PowerFlex 750 Series:
Installation Instructions
Original Instructions
PowerFlex 750-Series EMC Plate and Cores - Frames 1...7
Catalog Numbers 20F and 20G
Frames 1...5 (200...240/400...480V AC)
Frames 3...5 (600V AC)
Frame 6 and Frame 7 (600/690V AC)
Topic
Summary of Changes
200...240/400...480V AC Input Drives – Frames 1...5
600/690V AC Input Drives – Frames 3...7
Summary of Changes
This publication contains new and updated information as indicated in the following table.
Topic
Added Frames 1...5 (200...240V AC)
Page
1
3
6
Page
Throughout
loading

Summary of Contents for Allen-Bradley PowerFlex 750 Series

  • Page 1 Installation Instructions Original Instructions PowerFlex 750-Series EMC Plate and Cores - Frames 1...7 Catalog Numbers 20F and 20G Frames 1...5 (200…240/400…480V AC) Frames 3…5 (600V AC) Frame 6 and Frame 7 (600/690V AC) Topic Page Summary of Changes 200…240/400…480V AC Input Drives – Frames 1…5 600/690V AC Input Drives –...
  • Page 2 PowerFlex 750-Series EMC Plate and Cores - Frames 1...7 x2 Frame 4 x1 Frame 5 20-750-EMC1-F1 20-750-EMC1-F2,F3 20-750-EMC3-F3 20-750-EMC3-F4, F5 20-750-EMC1-F4,F5 Frame 1 Frames 2 and Frame 3 Frame 3 Frames 4 and Frame 5 Frames 4 and Frame 5 200…240/400…480V AC 200…240/400…480V AC 600V AC...
  • Page 3 PowerFlex 750-Series EMC Plate and Cores - Frames 1...7 600/690V – see page 6 200…240/400…480V AC Input Drives – Frames 1…5 Step Frame Procedure 1.81 N•m (16.0 lb•in) x2 (Frame 1) Rockwell Automation Publication 750-IN006H-MU-P - June 2017...
  • Page 4 PowerFlex 750-Series EMC Plate and Cores - Frames 1...7 Step Frame Procedure 2…5 1.81 N•m (16.0 lb•in) x2 (Frame 2) x3 (Frame 3...5) continued Environments with vibration: support plate is recommended to Frame 2 shown provide core support. Drain wires must be pulled back and wrapped in a 360 degree pattern over the shield/braided surface.
  • Page 5 PowerFlex 750-Series EMC Plate and Cores - Frames 1...7 Step Frame Procedure Motor Cable (U, V, W) Shielded To PE Stud Input Power (R, S, T) Shielded or Unshielded To PE Stud 1 Loop (each wire) I/O Shield T20 or F - 6.4 (0.25 in.) 1.8 N•m (16 lb•in) 2…3 Frame 2 shown...
  • Page 6 PowerFlex 750-Series EMC Plate and Cores - Frames 1...7 600/690V AC Input Drives – Frames 3…7 Step Frame Procedure 3…5 1.8 N•m (16 lb•in) x2 (Frame 3) x3 (Frame 4...5) Environments with vibration: support plate is recommended to provide core support. Drain wires must be pulled back and wrapped in a 360 degree pattern over the shield/braided surface.
  • Page 7 PowerFlex 750-Series EMC Plate and Cores - Frames 1...7 Step Frame Procedure Motor Cable (U, V, W) Shielded Input Power (R, S, T) To PE Stud Shielded or Unshielded I/O Signal Shield To PE Stud IP20, NEMA/UL Type 0 Flange Mount M6 (10 mm) 5.6 N•m (50 lb•in) The motor cable ground wire connects to the motor PE stud in the drive, however it should...
  • Page 8 PowerFlex 750-Series EMC Plate and Cores - Frames 1...7 Step Frame Procedure IP54 The cable shield and drain wires must be terminated at the shield clamp on the conduit plate. The ground wire must be connected to the PE stud in the drive; however, it should not pass through the core.
  • Page 9 PowerFlex 750-Series EMC Plate and Cores - Frames 1...7 Step Frame Procedure For use on Frame 7 IP00 drives. After installation, the drive achieves an IP20 rating. IP00 The cable shield and drain wires must be terminated at the shield clamp on the conduit plate.
  • Page 10 PowerFlex 750-Series EMC Plate and Cores - Frames 1...7 Step Frame Procedure The cable shield and drain wires must be IP54 terminated at the shield clamp on the conduit plate. The ground wire must be connected to the PE stud in the drive; however, it should not pass through the core.
  • Page 11 PowerFlex 750-Series EMC Plate and Cores - Frames 1...7 Notes: Rockwell Automation Publication 750-IN006H-MU-P - June 2017...
  • Page 12: Rockwell Automation Support

    Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Allen-Bradley, PowerFlex, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400...