Chapter 3
Drive Port 0 Parameters
Drive (Port 0) Motor Control
File
No.
Display Name
Full Name
Description
25
Motor NP Volts
Motor Nameplate Volts
Rated volts shown on the motor nameplate.
26
Motor NP Amps
Motor Nameplate Amps
Rated full load amps shown on the motor nameplate.
27
Motor NP Hertz
Motor Nameplate Hertz
Rated frequency shown on the motor nameplate.
28
Motor NP RPM
Motor Nameplate Revolutions Per Minute
Rated RPM shown on the motor nameplate. Note: The value of this parameter must
reflect the slip speed of the motor. For example, for a 60 Hz, 4 pole motor, a value of
1800 is synchronous speed, and 1750 is slip speed.
29
Mtr NP Pwr Units
Motor Nameplate Power Units
Power units shown on the motor nameplate.
30
Motor NP Power
Motor Nameplate Power
Rated power shown on the motor nameplate.
31
Motor Poles
Motor Poles
Number of poles in the motor.
120 x [Motor NP Hertz]
Poles =
[Motor NP RPM]
50
Rockwell Automation Publication 750-PM001N-EN-P - February 2017
Values
Units:
V AC
Default:
Based on Drive Rating and Voltage Class
Min/Max:
0.10 x P25 [Motor NP Volts] / Based on Drive
Rating and Voltage Class
Units:
Amps
Default:
Based on Drive Rating
Min/Max:
0.01 x P21 [Rated Amps] / 14200.00
Units:
Hz
Default:
Based on Drive Rating
Min/Max:
2.00 / 650.00
Units:
RPM
Default:
Based on Drive Rating
Min/Max:
1.0 / 40000.0
Default:
Based on Drive Rating
Options:
0 – HP
1 – kW
Units:
HP (P29 = 0)
kW (P29 = 1)
Default:
Based on Drive Rating
Min/Max:
0.01 / 2000.00
Units:
Pole
Default:
4
Min/Max:
2 / 200
RW Real
RW Real
RW Real
RW Real
RW 32-bit
Integer
RW Real
RW 32-bit
Integer