Parameter
Keypad and
Parameter
structure
display
x.00
7.25

Calibrate T5/6 analog input 1 full scale

Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Bit
SP
Coding
1
Open-loop, Closed-loop vector, Servo,
Default
Regen
Update rate
Background read
Setting this bit will cause the drive to re-calibrate the full scale level of analog input 1 provided the input voltage is below +1.5V or above +2.5V. This
parameter is cleared by the software automatically when the calibration is complete. If the input voltage is above +2.5V the input voltage itself is used
for calibration, and so after calibration this level will be full scale for the input. If the input voltage is below +1.5V the internal reference is used for
calibration, and so the full scale will be nominally 9.8V after calibration. The calibration level is automatically stored on power-down. It should be noted
that the Analog input 1 offset trim is included in the input voltage when the input voltage itself is used for calibration, but this trim is not included when
the internal reference is used for calibration.
7.26

T5/6 analog input 1 sample time

Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Bit
SP
Coding
Open-loop, Closed-loop vector, Servo,
Range
Regen
Open-loop, Closed-loop vector, Servo,
Default
Regen
Update rate
Background read
Analog input 1 is filtered using a window filter to remove quantization noise and adjust the resolution of this input. The length of the window can be
adjusted with this parameter. The shortest possible window is 250μs. It should be noted that if this input is not used as a speed reference (Pr 1.36,
Pr 1.37) or as a hard speed reference (Pr 3.22) the sample time affects the resolution. The nominal resolution is given by Pr 7.26 x 500 x 10, therefore
the default setting gives approximately 11 bit resolution.
7.28
T7 analog input 2 current loop loss
7.29

T8 analog input 3 current loop loss

Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Bit
SP
Coding
1
Update rate
Background write
If an analog input is used with 4-20mA or 20-4mA current loop modes the respective bit (Pr 7.28 - analog input 2 and Pr 7.29 -analog input 3) is set to
one if the current falls below 3mA. If the current is above 3mA with these modes or another mode is selected the respective bit is set to zero.
7.30

T5/6 analog input 1 offset

Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Bit
SP
Coding
Open-loop, Closed-loop vector, Servo,
Range
Regen
Open-loop, Closed-loop vector, Servo,
Default
Regen
Update rate
Background read
Unidrive SP Advanced User Guide
Issue Number: 10
Parameter
Advanced parameter
description format
descriptions
FI
DE
Txt
VM
DP ND RA
0
FI
DE
Txt VM DP
ND
1
0 to 8.0 ms
4.0
FI
DE
Txt
VM
DP
ND
1
FI
DE
Txt VM DP ND
2
±100.00 %
0.00
www.controltechniques.com
Serial comms
Macros
protocol
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
Electronic
Performance RFC mode
nameplate
PS
PS
1
PS
PS
Menu 7
159