Setup (Initialization) Of Absolute Encoder; Transferring Absolute Data - Panasonic MINAS A5-series Operating Instructions Manual

Minas a5-series ac servo motor and driver
Table of Contents
7
Supplement
Absolute multi-turn data will be maintained by the absolute encoder battery.
When operating the machine for the first time after installing the battery to the absolute en-
coder, clear the encoder data (multi-turn data) to 0 at the origin by following the procedure
described below.
Clear the absolute encoder from the front panel (see P.2-79) or PANATERM. Turn off power
and then on again.
7
Supplement
Transfer the absolute data (absolute data of external scale) from the servo driver to the
host controller: turn on power and wait until the servo ready output (S-RDY) is turned on,
and then start transfer.
Setup of serial communication interface on host controller
• RS232
Baud rate
Data
Parity
Start bit
Stop bit
The baud rate is set according to Pr5.29 Baud rate setup of RS232 communication.
• RS485
Baud rate
Data
Parity
Start bit
Stop bit
The baud rate is set according to Pr5.30 Baud rate setup of RS485 communication.
Related page
• P.3-30 "Inputs and outputs on connector X4"
7-16
2. Absolute system
Setup (Initialization) of Absolute Encoder
2. Absolute system
Transferring absolute data
2400, 4800, 9600, 19200, 38400, 57600, 115200bps
8 bit
none
1 bit
1 bit
2400, 4800, 9600, 19200, 38400, 57600, 115200bps
8 bit
none
1 bit
1 bit
• P.4-49 "Details of parameter"