ABB ACS880-x04 Firmware Manual page 510

Primary control program
Table of Contents
510 Fault tracing
Code
Warning
(hex)
A799
Ext I/O comm loss
Programmable warning:
31.55 Ext I/O comm loss
event
A79B
BC short circuit
A79C
BC IGBT excess
temperature
A7A1
Mechanical brake
closing failed
Programmable warning:
44.17 Brake fault function
Cause
The I/O extension module
types specified by parameters
do not match the detected
configuration.
00 0001 Communication with module
failed.
00 0002 Module not found.
00 0003 Configuration of module failed.
00 0004 Configuration of module failed.
Short circuit in brake chopper
IGBT
Brake chopper IGBT
temperature has exceeded
internal warning limit.
Status of mechanical brake
acknowledgement is not as
expected during brake close.
What to do
Check the auxiliary code (format
XXYY YYYY). "XX" specifies the number
of the I/O extension module (01:
parameter group
14 I/O extension
module
1, 02:
15 I/O extension module
03:
16 I/O extension module
"YY YYYY" indicates the problem (see
actions for each code below).
Check that the module is properly seated
in its slot.
Check that the module and the slot
connector is not damaged.
Try installing the module into another
slot.
Check the type and location settings of
the modules (parameters 14.01/14.02,
15.01/15.02
or 16.01/16.02).
Check that the module is properly seated
in its slot.
Check that the module and the slot
connector is not damaged.
Try installing the module into another
slot.
Replace brake chopper if external. Drives
with internal choppers will need to be
returned to ABB.
Ensure brake resistor is connected and
not damaged.
Let chopper cool down.
Check for excessive ambient
temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of
the cabinet.
Check resistor overload protection
function settings (parameters
43.06...43.10).
Check minimum allowed resistor value
for the chopper being used.
Check that braking cycle meets allowed
limits.
Check that drive supply AC voltage is not
excessive.
Check mechanical brake connection.
Check mechanical brake settings in
parameter group
44 Mechanical brake
control.
Check that acknowledgement signal
matches actual status of brake.
2,
3).
Table of Contents
loading