ABB ACS880-x04 Firmware Manual page 279

Primary control program
Table of Contents
No.
Name/Value
31.33
Emergency ramp
supervision delay
0...32767 s
31.35
Main fan fault
function
Fault
Warning
No action
31.36
Aux fan fault
function
Fault
Warning
Description
If parameter
31.32 Emergency ramp supervision
this parameter defines the maximum time an emergency stop
(mode Off1 or Off3) is allowed to take. If the motor has not
stopped when the time elapses, the drive trips on
Emergency ramp
failed, sets bit 8 of
2, and coasts to a stop.
If
31.32
is set to a value other than 0%, this parameter defines
a delay between the receipt of the emergency stop command
and the activation of the supervision. It is recommended to
specify a short delay to allow the speed change rate to
stabilize.
Maximum ramp-down time, or supervision activation delay.
Selects how the drive reacts when a main cooling fan fault is
detected.
Note: With an inverter unit consisting of one or more frame
R8i inverter modules with speed-controlled fans, it may be
possible to continue operation even if one main fan of a
module stops. When fan failure is detected, the control
program will automatically
• set the other fan of the module to full speed
• set the fans of the other modules (if any) to full speed
• decrease the switching frequency to a minimum, and
• disable the supervision of temperature difference between
the modules.
If this parameter is set to Fault, the inverter unit will trip (but
still carry out the actions listed above). Otherwise, the inverter
will attempt to continue operation.
The drive trips on fault
5080
The drive generates an
No action taken.
(Only visible with a ZCU control unit)
Selects how the drive reacts when an auxiliary fan fault is
detected.
The drive trips on fault
5081 Auxiliary fan not
Note: The fault is suppressed for two minutes after power-up.
During this time, the drive only generates a warning,
Auxiliary fan not
running.
The drive generates a warning,
running.
06.17 Drive status word
Fan.
A581 Fan
warning.
running.
A582 Auxiliary fan not
Parameters 279