No.
Name/Value
12.27
AI2 min
-22.000 ... 22.000
mA or V
12.28
AI2 max
-22.000 ... 22.000
mA or V
12.29
AI2 scaled at AI2
min
-32768.000 ...
32767.000
12.30
AI2 scaled at AI2
max
-32768.000 ...
32767.000
13

13 Standard AO

13.11
AO1 actual value
0.000 ... 22.000 mA Value of AO1.
13.12
AO1 source
Zero
Motor speed used
Output frequency
Motor current
Description
Defines the minimum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal
from plant is wound to its minimum setting.
See also parameter
12.01 AI
Minimum value of AI2.
Defines the maximum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal
from plant is wound to its maximum setting.
See also parameter
12.01 AI
Maximum value of AI2.
Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter
(Changing the polarity settings of
effectively invert the analog input.)
AI
scaled
12.30
12.27
Real value corresponding to minimum AI2 value.
Defines the real value that corresponds to the maximum
analog input AI2 value defined by parameter
See the drawing at parameter
Real value corresponding to maximum AI2 value.
Configuration of standard analog outputs.
Displays the value of AO1 in mA.
This parameter is read-only.
Selects a signal to be connected to analog output AO1.
Alternatively, sets the output to excitation mode to feed a
constant current to a temperature sensor.
None.
01.01 Motor speed used
01.06 Output frequency
01.07 Motor current
(page 117).
tune.
tune.
12.27 AI2
12.29
and
12.30
(12.22)
12.28
12.29
12.28 AI2
12.29 AI2 scaled at AI2
(page 117).
(page 117).
Parameters 163
Def/FbEq16
0.000 mA or
V
1000 = 1 mA
or V
20.000 mA or
10.000 V
1000 = 1 mA
or V
0.000
min.
can
AI
(12.21)
in
1 = 1
100.000
max.
min.
1 = 1
-
1000 = 1 mA
Motor speed
used
0
1
3
4
Table of Contents