Unit installation

7.3.5 To provide drainage

Installer reference guide
80
▪ (1) Put the unit into position (using the sling to the left and the handle to the
right).
▪ (2) Remove the sling (by pulling 1 side of the sling).
▪ (3) Fix the unit.
1
a Air outlet
NOTICE
Properly align the unit. Make sure the backside of the unit does NOT protrude.
3 Remove the protective cardboard and instruction sheet.
a
a Protective cardboard
b Instruction sheet
Make sure that condensation water can be evacuated properly.
Install the unit on a base to make sure that there is proper drainage in order to
avoid ice accumulation.
Prepare a water drainage channel around the foundation to drain waste water
away from the unit.
Avoid drain water flowing over the footpath, so that it does NOT become slippery
in case of ambient freezing temperatures.
If you install the unit on a frame, install a waterproof plate within 150 mm of the
bottom side of the unit in order to prevent water from getting into the unit and
to avoid drain water dripping (see the following figure).
a
a
b
2
3
ERGA04~08E + EHBH/X04+08E
Daikin Altherma 3 R W
4P629085-1C – 2022.05