Use table 1 in chapter "Technical data" to
calculate the maximum refrigerant charge
(m
) (kg) allowed for room A.
max
m
≥m
?
max
c
Yes
The unit can be installed in room A at the
specified installation height, and without
further room size or ventilation requirements.
Unit can be installed in room A if you provide 2 openings (one at the bottom, one at the top) between room A and B to ensure natural ventilation. The openings
must comply with the following conditions:
▪ Bottom opening (A
):
nv
▪ Must be a permanent opening that cannot be closed.
▪ Must be completely located between 0 and 300 mm from the floor.
▪ Must be ≥A
(minimum bottom opening area).
nv-min
▪ ≥50% of the required opening area A
▪ The bottom of the opening must be ≤100 mm from the floor.
▪ If the opening starts from the floor, the height of the opening must be ≥20 mm.
▪ Top opening:
▪ Must be a permanent opening that cannot be closed.
▪ Must be ≥50% of A
(minimum bottom opening area).
nv-min
▪ Must be ≥1.5 m from the floor.
ERGA04~08E + EHBH/X04+08E
Daikin Altherma 3 R W
4P629085-1C – 2022.05
INFORMATION
Multiple indoor units. If two or more indoor units are installed in a room, you must
consider the maximum refrigerant charge that can be released in the room when a
SINGLE leak occurs. Example: If two indoor units are installed in the room, each with
its own outdoor unit, then you have to consider the refrigerant charge of the largest
indoor-outdoor combination.
Input from installer:
▪ Area of adjacent room B (A
Use table 2 in chapter "Technical data" to
calculate the total minimum floor area
(A
) (m
min total
charge (m
c
(H).
No
Determine the refrigerant amount that exceeds
m
(dm) (kg). (dm=m
max
Use table 3 in chapter "Technical data" and
dm to calculate the minimum bottom opening
area for natural ventilation between room A
and room B (A
must be ≤200 mm from the floor.
nv-min
) (m
)
2
room B
) required for the total refrigerant
2
) at the selected installation height
No
A
≤A
+A
?
min total
room A
room B
Yes
–m
)
c
max
) (cm
).
2
nv-min
7
Unit installation
|
Contact your dealer.
A
Min. 50%
of A
A
nv
Installer reference guide
B
nv-min
(≥A
)
nv-min
71