Daikin Altherma 3 R W Installation Manual
Hide thumbs Also See for Altherma 3 R W:
Table of Contents
Installation manual
Daikin Altherma 3 R W
EHBH04E*6V
EHBH08E*6V
EHBH08E*9W
EHBX04E*6V
Installation manual
EHBX08E*6V
English
Daikin Altherma 3 R W
EHBX08E*9W
Table of Contents
loading

Summary of Contents for Daikin Altherma 3 R W

  • Page 1 Installation manual Daikin Altherma 3 R W EHBH04E*6V EHBH08E*6V EHBH08E*9W EHBX04E*6V Installation manual EHBX08E*6V English Daikin Altherma 3 R W EHBX08E*9W...
  • Page 2 3P633779-4...
  • Page 3: Table Of Contents

    Latest revisions of the supplied documentation may be available on 7.2.6 Configuration wizard: Additional zone......25 the regional Daikin website or via your dealer. 7.2.7 Detailed screen with weather-dependent curve..25 The original documentation is written in English. All other languages 7.2.8...
  • Page 4: Specific Installer Safety Instructions

    ▪ The full set of latest technical data is available on the Daikin closed. In case the minimum flow rate cannot be reached, Business Portal (authentication required).
  • Page 5 Next see the installer reference guide. commissioning instructions in this chapter, a general commissioning checklist is also available on the Daikin NOTICE Business Portal (authentication required). An overpressure bypass valve can be integrated in the The general commissioning checklist is complementary to system.
  • Page 6: About The Box

    Unit installation WARNING Make sure installation, servicing, maintenance and repair Preparing the installation site comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are WARNING executed only by authorised persons. The appliance shall be stored in a room without...
  • Page 7 ▪ Top opening: The area of the top opening must be larger than or equal to the bottom opening. The bottom of the top opening must be situated at least 1.5 m above the top of the bottom opening. ▪ Ventilation openings to the outside are NOT considered suitable ventilation openings (the user can block them when it is cold). EHBH/X04+08EA/EJ6V+9W Installation manual Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 8: Opening And Closing The Unit

    2 Reinstall the switch box cover and close the switch box. 3 Reinstall the front panel. NOTICE When closing the indoor unit cover, make sure that the tightening torque does NOT exceed 4.1 N•m. Installation manual EHBH/X04+08EA/EJ6V+9W Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 9: Mounting The Indoor Unit

    Ø6.4 mm (1/4") Gas piping Ø15.9 mm (5/8") ▪ Piping temper grade and thickness: Outer diameter Temper grade Thickness (t) (Ø) Ø 6.4 mm (1/4") Annealed (O) ≥0.8 mm 15.9 mm (5/8") Annealed (O) ≥1.0 mm EHBH/X04+08EA/EJ6V+9W Installation manual Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 10: Refrigerant Piping Insulation

    4 In case of connection with the optional domestic hot water tank, see the installation manual of the domestic hot water tank. See the recommended procedure as described in "8.2  Checklist commissioning" [ 4  32]. during Installation manual EHBH/X04+08EA/EJ6V+9W Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 11: To Fill The Water Circuit

    Only for the backup heater of the indoor unit ▪ [2.A] Thermostat type supply" [ 4  14]. "6.3.2 To connect the backup heater power For the additional zone: ▪ [3.A] Thermostat type ▪ [3.9] (read-only) Control EHBH/X04+08EA/EJ6V+9W Installation manual Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 12 Maximum length: 500 m adapter [2.9] Control ▪ Addendum book optional [1.6] Room sensor offset equipment Wires: 2×(0.75~1.25 mm²). Must be sheathed. Maximum length: 200 m See below ("LAN adapter – System requirements"). Installation manual EHBH/X04+08EA/EJ6V+9W Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 13: To Connect The Main Power Supply

    1 2 3 Interconnection cable (=main power supply) Normal kWh rate power supply Preferential power supply contact 3 Fix the cables with cable ties to the cable tie mountings. EHBH/X04+08EA/EJ6V+9W Installation manual Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 14: To Connect The Backup Heater Power Supply

    Electrical equipment complying with EN/IEC 61000-3-12 (European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16 A and ≤75 A per phase). Installation manual EHBH/X04+08EA/EJ6V+9W Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 15: To Connect The Shut-Off Valve

    X5M/6 and X5M/4; the negative polarity to X5M/5 and Maximum running current: 100 mA X5M/3. 230 V AC supplied by PCB unit" [ 4  8]): 1 Open the following (see "4.2.1 To open the indoor EHBH/X04+08EA/EJ6V+9W Installation manual Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 16: To Connect The Domestic Hot Water Pump

    2 Connect the domestic hot water pump cable to the appropriate Wires connected to the alarm terminals as shown in the illustration below. output Wire between X2M and A4P A4P Installation of EKRP1HBAA is required. Installation manual EHBH/X04+08EA/EJ6V+9W Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 17: To Connect The Space Cooling/Heating On/Off Output

    Wires connected to the alarm output Wire between X2M and A4P A4P Installation of EKRP1HBAA is required. X1 X2 EHBH/X04+08EA/EJ6V+9W Installation manual Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 18: To Connect The Power Consumption Digital Inputs

    3 Switch box appropriate terminals as shown in the illustration below. 2 Connect the safety thermostat (normally closed) cable to the appropriate terminals as shown in the illustration below. Installation manual EHBH/X04+08EA/EJ6V+9W Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 19: To Connect A Smart Grid

    [9.8.5] Smart grid operation mode [9.8.6] Allow electrical heaters [9.8.7] Enable room buffering [9.8.8] Limit setting kw The wiring of the Smart Grid in case of low voltage contacts is as follows: EHBH/X04+08EA/EJ6V+9W Installation manual Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 20 3 Connect the high voltage wiring as follows: X10M.1 1 2 3 4 X10M.2 X10M X10M.3 K1A K2A X10M.4 a, b Smart Grid high voltage contacts 2 Connect the low voltage wiring as follows: Installation manual EHBH/X04+08EA/EJ6V+9W Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 21: To Connect The Wlan Cartridge (Delivered As Accessory)

    The configuration influences the following: ▪ The calculations of the software ▪ What you can see on and do with the user interface You can configure the system via the user interface. EHBH/X04+08EA/EJ6V+9W Installation manual Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 22: Configuration Wizard

    • [E-06]: Is a domestic hot water tank installed in the system? • [E-07]: What kind of domestic hot water tank is installed? In case of EKHWP, we recommend to use the following settings: Installation manual EHBH/X04+08EA/EJ6V+9W Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 23 Number of zones on the illustrations. The system can supply leaving water to up to 2 water temperature zones. During configuration, the number of water zones must be set. EHBH/X04+08EA/EJ6V+9W Installation manual Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 24: Configuration Wizard: Backup Heater

    Human Comfort heater at nominal voltage. Nominal Interface (BRC1HHDA used as room value depends on backup heater thermostat). configuration. Installation manual EHBH/X04+08EA/EJ6V+9W Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 25: Configuration Wizard: Additional Zone

    The control type is displayed here, but cannot be adjusted. It is determined by the control type of the main zone. For more info about the functionality, see "7.2.5 Configuration wizard: Main zone" [ 4  24]. Weather-dependent curve when offset is selected: EHBH/X04+08EA/EJ6V+9W Installation manual Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 26: Configuration Wizard: Tank

    ▪ : Radiator Slope ▪ : Domestic hot water tank Offset 7.2.8 Configuration wizard: Tank This part only applies to systems with an optional domestic hot water tank installed. Installation manual EHBH/X04+08EA/EJ6V+9W Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 27: Weather-Dependent Curve

    ▪ during storage comfort, to prioritize the domestic hot water preparation. When the tank temperature rises above this value, domestic hot water preparation and space heating/cooling are executed sequentially. EHBH/X04+08EA/EJ6V+9W Installation manual Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 28: Slope-Offset Curve

    When slope is selected: set slope and go to offset. When offset is selected: set offset. Confirm changes and return to the submenu. 7.3.4 Using weather-dependent curves Configure weather-dependent curves as following: Installation manual EHBH/X04+08EA/EJ6V+9W Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 29: Settings Menu

    Only applicable in external room thermostat control. For more info Cold ↑ — zone" [ 4  29]. about the functionality, see "7.4.1 Main ↓ — Cold ↓ ↑ Cold Cold — ↑ EHBH/X04+08EA/EJ6V+9W Installation manual Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 30: Information

    ▪ 2: 2 contacts 7.4.3 Information Dealer information The installer can fill in his contact number here. Code Description [8.3] Number that users can call in case of problems. Installation manual EHBH/X04+08EA/EJ6V+9W Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 31: Menu Structure: Overview Installer Settings

    Solar kit settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. EHBH/X04+08EA/EJ6V+9W Installation manual Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 32: Commissioning

    Next Only for tanks with built-in booster heater: commissioning instructions in this chapter, a general commissioning checklist is also available on the Daikin Booster heater circuit breaker F2B (field supply) is Business Portal (authentication required). turned ON. The general commissioning checklist is complementary to There are NO refrigerant leaks.
  • Page 33: To Perform An Air Purge

    (domestic hot water mode). 1 Go to Stop UFH screed dryout. To monitor the temperatures: 2 Select OK to confirm. 1 In the menu, go to Sensors. 2 Select the temperature information. EHBH/X04+08EA/EJ6V+9W Installation manual Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 34: Hand-Over To The User

    ▪ Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. Installation manual EHBH/X04+08EA/EJ6V+9W Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 35: 10 Technical Data

    10 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). 10.1 Piping diagram: Indoor unit...
  • Page 36: Wiring Diagram: Indoor Unit

     Ext. thermistor  External thermistor R1H (A2P) * Humidity sensor  Heat pump convector  Heat pump convector R1T (A1P ) Outlet water heat exchanger thermistor R1T (A2P) * Ambient sensor On/OFF thermostat Installation manual EHBH/X04+08EA/EJ6V+9W Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 37 Only for wired On/OFF 3 wire type SPST 3 wire type SPST thermostat thermostat Booster heater power supply Booster heater power supply Only for wireless On/OFF Only for wireless On/OFF thermostat thermostat EHBH/X04+08EA/EJ6V+9W Installation manual Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 38 Power limitation A8P: X801M: 3-5 demand input 3 signal 2 core 2 core 2x0.75 Power limitation A13P: P1-P2 LAN adapter A8P: X801M: 4-5 communication demand input 4 signal 4D130334A Installation manual EHBH/X04+08EA/EJ6V+9W Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 39: Indoor Unit

    Table 3 – Minimum venting opening area for natural ventilation: indoor unit dm=m –m (kg) Minimum venting opening area (cm H=1150 mm H=1200 mm H=1300 mm H=1400 mm H=1500 mm H=1600 mm H=1700 mm H=1800 mm 1.80 1.60 1.40 1.20 1.00 0.80 0.60 0.40 0.20 EHBH/X04+08EA/EJ6V+9W Installation manual Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 40 If dm=1.55  kg, consider the value that corresponds to "dm=1.6 kg". Installation manual EHBH/X04+08EA/EJ6V+9W Daikin Altherma 3 R W 4P629081-1A – 2020.08...
  • Page 44 4P629081-1 A 0000000$ 4P629081-1A 2020.08 Verantwortung für Energie und Umwelt...