Daikin Altherma 3 R W Installation Manual

Daikin Altherma 3 R W Installation Manual

Hide thumbs Also See for Altherma 3 R W:
Table of Contents
Installation manual
Daikin Altherma 3 R W
https://daikintechnicaldatahub.eu
EHBH04EF6V
EHBH08EF6V
EHBH08EF9W
EHBX04EF6V
Installation manual
EHBX08EF6V
English
Daikin Altherma 3 R W
EHBX08EF9W
Table of Contents
loading

Summary of Contents for Daikin Altherma 3 R W

  • Page 1 Installation manual Daikin Altherma 3 R W https://daikintechnicaldatahub.eu EHBH04EF6V EHBH08EF6V EHBH08EF9W EHBX04EF6V Installation manual EHBX08EF6V English Daikin Altherma 3 R W EHBX08EF9W...
  • Page 2 3P633779-5A...
  • Page 3: Table Of Contents

    Configuration wizard: Main zone......... 27 and-manuals/product-information/ 7.2.6 Configuration wizard: Additional zone......28 7.2.7 Configuration wizard: Tank ......... 28 Weather-dependent curve............29 7.3.1 What is a weather-dependent curve? ......29 EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 4: Specific Installer Safety Instructions

    Daikin website (publicly accessible). WARNING ▪ The full set of latest technical data is available on the Daikin The appliance shall be stored so as to prevent mechanical Business Portal (authentication required). damage and in a well-ventilated room without continuously...
  • Page 5: About The Box

    When outdoor unit (ERGA06EAV3H or 30 m ERGA08EAV3H) is at highest location When outdoor unit (ERGA04EAV3 or 20 m ERGA04~08EAV3A) is at highest location When indoor unit is at highest location 20 m EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 6: Special Requirements For R32 Units

    WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation and are executed ONLY by authorised persons. NOTICE ▪ Pipework shall be protected from physical damage.
  • Page 7: Installation Patterns

    SINGLE leak occurs. Example: If two indoor units are installed in the room, each with its own outdoor unit, then you have to consider the refrigerant charge of the largest indoor-outdoor combination. EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 8 ▪ Must be a permanent opening that cannot be closed. nv-min ▪ Must be ≥50% of A (minimum bottom opening area). nv-min ▪ Must be ≥1.5 m from the floor. (≥A nv-min Installation manual EHBH/X04+08EF Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 9: Opening And Closing The Unit

    Example: If the refrigerant charge is 4.3 kg, use the row of 4.4 kg. Total refrigerant charge (kg) (dm²) 2 If you have to connect electrical wiring, remove the switch box nv-min cover. EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 10: To Close The Indoor Unit

    5 Optional: Remove the user interface panel. NOTICE If you remove the user interface panel, also disconnect the cables from the back of the user interface panel to prevent damage. Installation manual EHBH/X04+08EF Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 11: To Connect The Drain Hose To The Drain

    ▪ with a heat resistance of at least 120°C ▪ Insulation thickness Pipe outer diameter Insulation inner Insulation thickness (Ø diameter (Ø 6.4 mm (1/4") 8~10 mm 10 mm 15.9 mm (5/8") 16~20 mm 13 mm Ø Ø Ø Ø EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 12: Connecting Refrigerant Piping

    In case the minimum flow rate cannot be reached, a flow error 7H will be generated (no heating or operation). See the installer reference guide for more information. Installation manual EHBH/X04+08EF Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 13: Connecting Water Piping

    4  18]. on the domestic cold water inlet connection in accordance with the applicable legislation. Domestic hot water "6.3.5 To connect the domestic hot pump" [ 4  18]. pump water EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 14 Power supply for ▪ Installation manual of the DHW booster heater (from tank indoor unit to thermal ▪ Addendum book optional protector of booster equipment heater) Wires: (2+GND)×2.5 mm² [9.4] Booster heater Installation manual EHBH/X04+08EF Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 15: To Connect The Main Power Supply

    15 V DC, 10 mA. 6.3.1 To connect the main power supply [9.8] Benefit kWh power supply unit" [ 4  9]): 1 Open the following (see "4.2.1 To open the indoor Connect X11Y to X11YB. EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 16: To Connect The Backup Heater Power Supply

    3~ 230 V (6T1) 3+GND 3N~ 400 V 4+GND Q1DI [9.3] Backup heater Factory-mounted cable connected to the contactor of the backup heater, inside the switch box (K5M) Field wiring (see table below) Installation manual EHBH/X04+08EF Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 17: To Connect The Shut-Off Valve

    Safety contactor (in the switch box) Q1DI Earth leakage circuit breaker (field supply) Switch box Terminal (field supply) 3 Fix the cable with cable ties to the cable tie mountings. EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 18: To Connect The Electricity Meters

    DHW pump output. Maximum load: 2 A (inrush), 230 V AC, A4P Installation of EKRP1HBAA is 1 A (continuous) required. [9.2.2] DHW pump [9.2.3] DHW pump schedule unit" [ 4  9]): 1 Open the following (see "4.2.1 To open the indoor Installation manual EHBH/X04+08EF Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 19: To Connect The Space Cooling/Heating On/Off Output

    2 Connect the space cooling/heating ON/OFF output cable to the appropriate terminals as shown in the illustration below. Wires connected to the space cooling/heating ON/OFF output Wire between X2M and A4P A4P Installation of EKRP1HBAA is required. EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 20: To Connect The Power Consumption Digital Inputs

    2 Connect the safety thermostat (normally closed) cable to the appropriate terminals as shown in the illustration below. Note: The jumper wire (factory-mounted) must be removed from the respective terminals. Installation manual EHBH/X04+08EF Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 21: To Connect A Smart Grid

    Smart Grid relay kit (EKRELSG). The 2 incoming Smart Grid contacts can activate the following Smart Grid modes: Smart Grid contact Smart Grid operation mode Free running EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 22 3 Connect the high voltage wiring as follows: X10M K1A, K2A Relays X10M Terminal block Screws for X10M Screws for K1A and K2A Sticker to put on the high voltage wires Installation manual EHBH/X04+08EF Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 23: To Connect The Wlan Cartridge (Delivered As Accessory)

    "7.5 Menu structure: Overview installer settings" [ 4  32] 7.1.1 To access the most used commands To change the user permission level You can change the user permission level as follows: EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 24: Configuration Wizard

    [7.1] Language 2 Go to [9.I]: Installer settings > Overview field settings. 7.2.2 Configuration wizard: Time and date Code Description [7.2] Set the local time and date Installation manual EHBH/X04+08EF Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 25: Configuration Wizard: System

    INFORMATION In case of EKHWS*D* / EKHWSU*D*, we recommend to use the following settings: If [4‑03]=1 or 3, then Emergency = Manual is not applicable for the booster heater. EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 26: Configuration Wizard: Backup Heater

    ▪ 3: Relay 1 / Relay 2 Emergency Relay configured as the main zone, and ▪ the zone with the highest water temperature is configured as the additional zone. Installation manual EHBH/X04+08EF Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 27: Configuration Wizard: Main Zone

    Influence of the LWT setpoint mode [2.4] is as follows: ▪ In Fixed LWT setpoint mode, the scheduled actions consist of desired leaving water temperatures, either preset or custom. EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 28: Configuration Wizard: Additional Zone

    Code Description [5.4] [6-0C] Reheat setpoint: ▪ 30°C~min(50,[6‑0E])°C Installation manual EHBH/X04+08EF Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 29: Weather-Dependent Curve

    4  30]. "7.3.4 Using weather-dependent 7.3.2 2-points curve Define the weather-dependent curve with these two setpoints: ▪ Setpoint (X1, Y2) ▪ Setpoint (X2, Y1) Example Weather-dependent curve when offset is selected: EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 30: Using Weather-Dependent Curves

    To fine-tune the weather-dependent curve: 2-points curve [2.4] Main zone > Setpoint Weather dependent The following table describes how to fine-tune the weather- mode dependent curve of a zone or tank: Additional zone – Heating Installation manual EHBH/X04+08EF Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 31: Settings Menu

    ▪ 2: 2 contacts 7.4.3 Information Dealer information The installer can fill in his contact number here. Code Description [8.3] Number that users can call in case of problems. EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 32: Menu Structure: Overview Installer Settings

    Solar kit settings are shown but are NOT applicable for this Depending on the selected installer settings and unit type, unit. Settings shall NOT be used or changed. settings will be visible/invisible. Installation manual EHBH/X04+08EF Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 33: Commissioning

    Next commissioning instructions in this chapter, a general ▪ Between the local supply panel and the indoor unit commissioning checklist is also available on the Daikin ▪ Between the indoor unit and the valves (if applicable) Business Portal (authentication required).
  • Page 34: To Check The Minimum Flow Rate

    2 Go to [A.1]: Commissioning > Operation test ▪ C/H signal test run. ▪ DHW pump test 3 Select a test from the list. Example: Heating. ▪ Bizone direct pump test (bizone kit EKMIKPOA or EKMIKPHA) Installation manual EHBH/X04+08EF Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 35: To Perform An Underfloor Heating Screed Dryout

    ▪ Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 36: 10 Technical Data

    10 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). 10.1 Piping diagram: Indoor unit...
  • Page 37: Wiring Diagram: Indoor Unit

     On/OFF thermostat (wireless)  ON/OFF thermostat (wireless) S10S-S11S # Low voltage Smart Grid contact  Ext. thermistor  External thermistor SS1 (A4P) * Selector switch  Heat pump convector  Heat pump convector Power supply transformer EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 38 For HV smartgrid For high voltage Smart Grid For LV smartgrid For low voltage Smart Grid For safety thermostat For safety thermostat For smartgrid For Smart Grid Inrush Inrush current Installation manual EHBH/X04+08EF Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 39 Only for Human Comfort Interface 2 core A8P: X801M: 3-5 2×0.75 signal X5M: 11-12 A14P: P1-P2 user interface 2 core Power limitation demand input 4 communication A8P: X801M: 4-5 signal 4D130334C EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 40: Ventilation: Indoor Unit

    Table 3 – Minimum bottom opening area for natural ventilation: indoor unit dm=m –m (kg) Minimum bottom opening area (cm H=1150 mm H=1200 mm H=1300 mm H=1400 mm H=1500 mm H=1600 mm H=1700 mm H=1800 mm 1.80 1.60 1.40 1.20 1.00 0.80 0.60 0.40 0.20 Installation manual EHBH/X04+08EF Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 41 If dm=1.55  kg, consider the value that corresponds to "dm=1.6 kg". EHBH/X04+08EF Installation manual Daikin Altherma 3 R W 4P642727-1A – 2021.11...
  • Page 44 4P642727-1 A 0000000+ 4P642727-1A 2021.11 Verantwortung für Energie und Umwelt...