Technical Data - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents
1MRS757256 F
Table 58:
B1RBDR Non group settings (advanced)
Name
Values (Range)
Trigger level 1
Trig on 0
Trig on 1
Show indication 1
Hide
Show
IEC60870-5-103
Function type Ch 1
0 - 255
Information Num Ch
0 - 255
1
3.14.5
PML630/Compact Load-Shedding Solution
Technical Manual
Unit
-
-
-
-
Settings are the same for each channel. The channel numbers are
shown after the parameter name in LHMI and PCM600.

Technical data

Table 59:
DRRDRE technical data
Function
Pre-fault time
Post-fault time
Limit time
Maximum number of recordings
Time tagging resolution
Maximum number of analog inputs
Maximum number of binary inputs
Maximum number of phasors in the
Trip Value recorder per recording
Maximum number of indications in a
disturbance report
Maximum number of events in the
Event recording per recording
Maximum number of events in the
Event list
Maximum total recording time (3.4 s
recording time and maximum number
of channels, typical value)
Sampling rate
Recording bandwidth
Step
Default
-
Trig on 1
-
Hide
1
0
1
0
Range or value
(0.05–3.00) s
(0.1–10.0) s
(0.5–8.0) s
100, first in - first out
1 ms
20 + 20 (external + internally
derived)
64
30
64
150
1000, first in - first out
340 seconds (100 recordings) at
50 Hz, 280 seconds (80
recordings) at 60 Hz
1 kHz at 50 Hz
1.2 kHz at 60 Hz
(5-300) Hz
Section 3
Basic functions
Description
Trigger on positive
(1) or negative (0)
slope for binary input
1
Indication mask for
binary channel 1
Function type for
binary channel 1
(IEC60870-5-103)
Information number
for binary channel 1
(IEC60870-5-103)
Accuracy
-
-
-
-
See time synchronization
technical data
-
-
-
-
-
-
-
-
-
91