Name
Values (Range)
A low limit PhC
A low low Lim PhC
A minimum PhC
A maximum PhC
A Db type PhC
Table 253:
CMMXU Non group settings (advanced)
Name
Values (Range)
A Zer deadband PhA
A limit Hys PhA
A Zer deadband PhB
A limit Hys PhB
A Zer deadband PhC
A limit Hys PhC
6.1.5
PML630/Compact Load-Shedding Solution
Technical Manual
Unit
0.0 - 100000.0
A
0.0 - 100000.0
A
0.0 - 100000.0
A
0.0 - 100000.0
A
Cyclic
-
Dead band
Int deadband
Unit
0 - 100000
m%
0.000 - 100.000
%
0 - 100000
m%
0.000 - 100.000
%
0 - 100000
m%
0.000 - 100.000
%

Monitored data

Table 254:
CMMXU Monitored data
Name
I_INST_A
I_DB_A
I_ANGL_A
I_RANGE_A
I_INST_B
I_DB_B
I_ANGL_B
Table continues on next page
Step
Default
0.1
0.0
0.1
0.0
0.1
0.0
0.1
500.0
-
Cyclic
Step
Default
1
500
0.001
5.000
1
500
0.001
5.000
1
500
0.001
5.000
Type
Values (Range)
REAL
-
REAL
-
REAL
-
INTEGER
0=Normal
1=High
2=Low
3=High-High
4=Low-Low
REAL
-
REAL
-
REAL
-
Section 6
Measurement functions
Description
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Maximum value
Reporting type
Description
Zero point clamping in 0,001% of range
Hysteresis value in % of range and is
common for all limits
Zero point clamping in 0,001% of range
Hysteresis value in % of range and is
common for all limits
Zero point clamping in 0,001% of range
Hysteresis value in % of range and is
common for all limits
Unit
Description
A
Phase A amplitude,
magnitude of
instantaneous value
A
Phase A amplitude,
magnitude of reported
value
deg
Phase A angle,
instantaneous value
-
Phase A amplitude range
A
Phase B amplitude,
magnitude of
instantaneous value
A
Phase B amplitude,
magnitude of reported
value
deg
Phase B angle,
instantaneous value
199