Table 153:
GTI Output signals
Name
Type
OUTPUT
BOOLEAN

Greater than or equal check for real signals GER

Function block
GUID-1D90C1E8-5B94-427A-A19D-69BABBCB34A7 V1 EN
Figure 89:
Function block
Functionality
The function compares the real inputs REAL_IN1 and REAL_IN2 and activates the
binary output OUTPUT, if REAL_IN1 is greater than or equal to REAL_IN2.
If REAL_IN1 ≥ REAL_IN2, OUTPUT = 1, else OUTPUT = 0.
Logic function blocks do not have the hysteresis feature. Oscillating
outputs should be avoided when comparing analog signals that have
very closely varying values.
Signals
Table 154:
GER Input signals
Name
Type
REAL_IN1
REAL
REAL_IN2
REAL
Table 155:
GER Output signals
Name
Type
OUTPUT
BOOLEAN

Greater than or equal check for integer signals GEI

Function block
GUID-4D68CEF6-6160-4D41-8F56-2C87D7B15FDD V1 EN
Figure 90:
Function block
Description
Binary output
Default
Description
0.0
Real input 1
0.0
Real input 2
Description
Binary output
Section 3
Basic functions
155