Settings; Pulse Counter Pcggio; Function Block; Functionality - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents
1MRS757256 F
3.9.6
3.10
3.10.1
3.10.2
3.10.3
PML630/Compact Load-Shedding Solution
Technical Manual
Table 34:
MVEXP Output signals
Name
Type
HIGHHIGH
BOOLEAN
HIGH
BOOLEAN
NORMAL
BOOLEAN
LOW
BOOLEAN
LOWLOW
BOOLEAN

Settings

The function does not have any parameters available in LHMI or PCM600.

Pulse counter PCGGIO

Function block

PCGGIO
BLOCK
INVALID
READ_VAL
RESTART
BI_PULSE*
BLOCKED
RS_CNT
NEW_VAL
SCAL_VAL
GUID-A70F660E-B6C0-4F95-8CF5-E260CD2AFC17 V1 EN
Figure 36:
Function block

Functionality

Pulse counter (PCGGIO) function counts externally generated binary pulses, for
instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the BIO (binary input/output) module
and read by the PCGGIO function. A scaled service value is available over the station
bus.

Operation principle

The registration of pulses is done according to setting of CountCriteria parameter on
one of the 9 binary input channels located on the BIO module. Pulse counter values are
sent to the station HMI with predefined cyclicity without reset.
The reporting time period can be set in the range from 1 second to 60 minutes and is
synchronized with absolute system time. Interrogation of additional pulse counter
values can be done with a command (intermediate reading) for a single counter. All
active counters can also be read by IEC 61850.
Basic functions
Description
Measured value is above high-high limit
Measured value is between high and high-high limit
Measured value is between high and low limit
Measured value is between low and low-low limit
Measured value is below low-low limit
Section 3