Product Version History; Pcm600 And Ied Connectivity Package Version - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents
Section 2
PML630 overview
2.2
2.3
22
method thereby dividing the network into sectors called power network areas. Each
PML630 is responsible for the load-shedding action in its respective area, based on the
power source capabilities and inter-power network area connectivity status. The
coordination of load-shedding actions between the PML630 IEDs is handled by
suitable parameterization. This arrangement of multiple PML630 IEDs in a peer-to-
peer method is called cPMS - LS configuration B.
The PML630 IEDs communicate with each other also using IEC 61850 GOOSE.
Likewise, cPMS - LS configuration B is also a feature in PML630. The Configuration
B is always built up over and above the Configuration A and hence the latter is a
prerequisite.
The maximum recommended number of PML630 IEDs in a peer-to-peer mode in
Configuration B is three.
The power network areas would be connected to each other through their grid 1 or grid
2 power source connection points.

Product version history

Product version
Product history
1.1
First release
1.1.1
Maintenance release
1.1.2
Maintenance release
1.2
1.2.1
Maintenance release

PCM600 and IED connectivity package version

Protection and Control IED Manager PCM600 Ver.2.5 or later
ABB IED Connectivity Package PML630 Ver.1.2.1
®
Support for Relion
620 series, RIO600 in the solution cluster
Fast load-shedding: external trigger enabling, extending network
capability with Configuration B
Slow load-shedding: coverage of all 6 generators for current-based
overload load-shedding, 2 grid transformers' currents can be directly
monitored for overcurrent using 8 CT TRM card; provision for direct
reduction of overload (in addition to power-balance calculations)
Manual load-shedding: defining load-shedding by power value from
LHMI/COM600, external trigger for all 4 subnetworks
Underfrequency load-shedding using 630 series' Multipurpose analog
protection MAPGAPC for underfrequency detection and activation
through fast and slow load-shedding functions
Manual load-shedding mode not affected when fast and slow load-
shedding modes are blocked
Provision for external inhibition of load feeders
Adaptation for double-busbar configuration
1MRS757256 F
PML630/Compact Load-Shedding Solution
Technical Manual