Daikin Altherma 3 GEO Series Installer's Reference Manual page 81

Hide thumbs Also See for Altherma 3 GEO Series:
Table of Contents
#
Code
[9.9.1]
[4-08]
Power consumption control:
▪ 0 No: Disabled.
▪ 1 Continuous: Enabled: You can set
one power limitation value (in A or
kW) to which the system power
consumption will be limited for all the
time.
▪ 2 Inputs: Enabled: You can set up
to four different power limitation
values (in A or kW) to which the
system power consumption will be
limited
digital input asks.
▪ 3 Current
can set a current limitation value (in
A) to which the household current
will be limited.
Continuous power consumption control and power
consumption control with digital inputs
The type of limit needs to be set in combination with the continuous
power consumption control and the power consumption control with
digital inputs.
#
Code
[9.9.2]
[4-09]
Type:
▪ 0 Amp: The limitation values are set
in A.
▪ 1 kW: The limitation values are set in
kW.
Limit when [9.9.1]=Continuous and [9.9.2]=Amp:
#
Code
Limit: Only applicable in case of full
[9.9.3]
[5-05]
time current limitation mode.
0 A~50 A
Limits when [9.9.1]=Inputs and [9.9.2]=Amp:
#
Code
[9.9.4]
[5-05]
Limit 1: 0 A~50 A
[9.9.5]
[5-06]
Limit 2: 0 A~50 A
[9.9.6]
[5-07]
Limit 3: 0 A~50 A
[9.9.7]
[5-08]
Limit 4: 0 A~50 A
Limit when [9.9.1]=Continuous and [9.9.2]=kW:
#
Code
[9.9.8]
[5-09]
Limit: Only applicable in case of full
time power limitation mode.
0 kW~20 kW
Limits when [9.9.1]=Inputs and [9.9.2]=kW:
#
Code
Limit 1: 0 kW~20 kW
[9.9.9]
[5-09]
Limit 2: 0 kW~20 kW
[9.9.A]
[5-0A]
Limit 3: 0 kW~20 kW
[9.9.B]
[5-0B]
[9.9.C]
[5-0C]
Limit 4: 0 kW~20 kW
Power consumption control via current sensors
Limit when [9.9.1]=Current sensor:
#
Code
[9.9.3]
[5-05]
Limit: 0 A~50 A
EGSAH/X06+10DA9W(G)
Daikin Altherma 3 GEO
4P569820-1A – 2019.09
Description
when
the
corresponding
sensor: Enabled: You
Description
Description
Description
Description
Description
Description
In case the current sensors are calibrated, you can specify an offset
for the output of the current sensors. This value will be added to the
current output value of the current sensor.
#
Code
[9.9.E]
[4-0E]
Current sensor offset: Offset on
the household current measured by the
current sensors.
–6 A~6 A, step 0.5 A
Priority heater
This setting defines the priority of the electrical heaters depending
on applicable limitation. As no booster heater is present, the backup
heater will always be prioritised.
#
Code
Priority heater
[9.9.D]
[4-01]
▪ 0 None : The backup heater is
prioritised.
▪ 1 Booster heater: After restart, the
setting will be reverted back to
0=None and the backup heater will
be prioritised.
▪ 2 Backup
heater is prioritised.
BBR16
See
"5.6.5  BBR16 power limitation" 
about this functionality.
INFORMATION
Restriction: BBR16 settings are only visible when the
language of the user interface is set to Swedish.
NOTICE
2 weeks to change. After you activated BBR16, you only
have 2 weeks to change its settings (BBR16 activation
and BBR16 power limit). After 2 weeks, the unit freezes
these settings.
Note: This is different from the permanent power limitation,
which is always changeable.
BBR16 activation
#
Code
BBR16 activation:
[9.9.F]
[7-07]
▪ 0: disabled
▪ 1: enabled
BBR16 power limit
#
Code
[9.9.G]
[N/A]
BBR16 power limit: This setting can
only be modified via the menu
structure.
▪ 0 kW~25 kW, step 0.1 kW
Energy metering
Energy metering
If energy metering is performed by the use of external power meters,
configure the settings as described below. Select the pulse
frequency output of each power meter in accordance with the power
meter specifications. It is possible to connect up to 2 power meters
with different pulse frequencies. If only 1 or no power meter is used,
select 'None' to indicate the corresponding pulse input is NOT used.
10 Configuration
Description
Description
heater: The backup
[ 4   22] for detailed information
Description
Description
Installer reference guide
81