Daikin Altherma 3 GEO Series Installer's Reference Manual page 107

Hide thumbs Also See for Altherma 3 GEO Series:
Table of Contents
4/11
Field settings table
Breadcrumb
Field code
Setting name
5.7.2
[2-00]
Operation day
5.7.3
[2-02]
Start time
5.7.4
[2-03]
Tank setpoint
5.7.5
[2-04]
Duration
Tank
5.8
[6-0E]
Maximum
5.9
[6-00]
Hysteresis
5.A
[6-08]
Hysteresis
5.B
Setpoint mode
└─ WD curve
5.C
[0-0B]
Leaving water value for high ambient temp. for DHW WD curve.
5.C
[0-0C]
Leaving water value for low ambient temp. for DHW WD curve.
5.C
[0-0D]
High ambient temp. for DHW WD curve.
5.C
[0-0E]
Low ambient temp. for DHW WD curve.
Tank
5.D
[6-01]
Margin
User settings
└─ Quiet
7.4.1
Activation
└─ Electricity price
7.5.1
High
7.5.2
Medium
7.5.3
Low
User settings
7.6
Gas price
Installer settings
└─ Configuration wizard
└─ System
9.1.3.2
[E-03]
BUH type
9.1.3.3
[E-05]
Domestic hot water
[E-06]
[E-07]
9.1.3.4
[4-06]
Emergency
9.1.3.5
[7-02]
Number of zones
└─ Backup heater
9.1.4.1
[5-0D]
Voltage
9.1.4.5
[4-07]
Maximum BUH capacity
└─ Main zone
9.1.5.1
[2-0C]
Emitter type
9.1.5.2
[C-07]
Control
9.1.5.3
Setpoint mode
9.1.5.4
Schedule
9.1.5.5
WD curve type
9.1.6
[1-00]
Low ambient temp. for LWT main zone heating WD curve.
9.1.6
[1-01]
High ambient temp. for LWT main zone heating WD curve.
9.1.6
[1-02]
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
4P569818-1 - 2019.02
R/W
R/W
R/O
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/O
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
(#) Setting is not applicable for this unit.
Range, step
Default value
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
0~23 hour, step: 1 hour
3
60°C
60°C
40~60 min, step: 5 min
40 min
40~60°C, step: 1°C
60°C
2~20°C, step: 1°C
6°C
2~20°C, step: 1°C
10°C
0: Fixed
1: Weather dependent
35~[6-0E]°C, step: 1°C
55°C
45~[6-0E]°C, step: 1°C
60°C
10~25°C, step: 1°C
15°C
-40~5°C, step: 1°C
-10°C
0~10°C, step: 1°C
2°C
0: OFF
1: Quiet
2: More quiet
3: Most quiet
4: Automatic
0,00~990/kWh
1/kWh
0,00~990/kWh
1/kWh
0,00~990/kWh
1/kWh
0,00~990/kWh
0,00~290/MBtu
1,0/kWh
4: 9W
No DHW
Integrated
0: Manual
1: Automatic (normal SH/ DHW ON)
2: Auto red SH/ DHW ON
3: Auto red SH/ DHW OFF
4: Auto normal SH/ DHW OFF
0: Single zone
1: Dual zone
0: 230V, 1~
2: 400V, 3~
[5-0D]=2: 0~9 kW, step 1 kW
9 kW
[5-0D]≠2: 0~6 kW, step 1 kW
6 kW
0: Underfloor heating
1: Fancoil unit
2: Radiator
0: LWT control
1: Ext RT control
2: RT control
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
0: No
1: Yes
0: 2-points
1: Slope-Offset
-40~5°C, step: 1°C
-40°C
10~25°C, step: 1°C
15°C
[9-01]~[9-00], step: 1°C
[2-0C]=0
45°C
[2-0C]=1
55°C
[2-0C]=2
65°C
Installer setting at variance with
default value
Date
Value
(*1) *X*_(*2) *H*