Symptom: The unit is NOT heating as expected ..93 INFORMATION 14.3.2 Symptom: The compressor does NOT start (space heating or domestic water heating)......94 Indicates useful tips or additional information. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
1.2.3 Refrigerant comply with applicable legislation (on top of the If applicable. See the installation manual or installer reference guide instructions described in the Daikin documentation). of your application for more information. CAUTION NOTICE Wear adequate personal protective equipment (protective Make sure refrigerant piping installation complies with gloves, safety glasses,…) when installing, maintaining or...
If applicable. See the installation manual or installer reference guide of your application for more information. WARNING The selection of the brine MUST be in accordance with the applicable legislation. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
WARNING Daikin website (publicly accessible). ▪ After finishing the electrical work, confirm that each ▪ The full set of latest technical data is available on the Daikin electrical component and terminal inside the electrical Business Portal (authentication required). components box is connected securely.
What to do in case of problems Disposal How to dispose of the system Technical data Specifications of the system Glossary Definition of terms Shut-off valve with integrated filter EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
▪ Combining the indoor unit with options Identification NOTICE When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
For installation instructions, see the installation manual of the room questions first: thermostat and addendum book for optional equipment. ▪ How many rooms are heated or cooled by the heat pump system? Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
▪ #: [2.9] the ambient temperature of the thermostat): Unit operation is ▪ #: [2.9] ▪ Code: [C-07] dedicated Human Comfort decided by the external ▪ Code: [C-07] Interface. thermostat. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 12
Benefits heat pump convector can only ▪ #: [2.A] ▪ Wireless. The Daikin external room thermostat is available in a send a thermo ON/OFF wireless version. ▪ Code: [C-05] condition. No separation between ▪ Efficiency. Although the external room thermostat only sends ON/ heating or cooling demand.
Benefits ▪ Easy. Same installation as for one room, but with thermostatic valves. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 14
▪ Comfort. You can set the desired room temperature, including schedules, for each room via the remote controller of the heat pump convectors. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
▪ Code: [7-02] temperature zone and the additional leaving water temperature zone in relation to the required capacity of both water temperature zones. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Main leaving water temperature zone One single room Dedicated Human Comfort Interface (BRC1HHDA used as room thermostat) Remote outdoor sensor Non-return valve (field supply) Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
NOT influenced or turned ON/OFF by direct ▪ Daikin is NOT responsible for incorrect or unsafe sunlight. situations in the auxiliary boiler system. ▪ Frequent changeover may cause corrosion of the ▪...
DHW pump and heater element (if needed) as shown above. Configuration The indoor unit can control DHW pump operation. For more information, see "10 Configuration" [ 4 55]. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
INFORMATION When measuring the electrical power consumption, make sure ALL power input of the system is covered by the electrical power meters. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
For details about connecting the power meters to the unit, see "8.2.4 To connect the electricity meters" [ 4 38]. Compressor (1N~) Power input Time Hydro (1N~) Digital input (power limitation level) Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Therefore, the electrical heater is limited and turned OFF first. The The power or current of the entire Daikin system is limited system limits power consumption in the following order: dynamically by digital inputs (maximum four steps). Each power Limits the backup heater.
▪ Set the power consumption control settings in [9.9] via the user interface (for description settings, "10 Configuration" [ 4 55]): ▪ Activate BBR16 ▪ Set the desired power limitation level Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed only by authorised persons. Opening and closing the unit 6.2.1...
2 Remove the insulation from the shut-off valves by cutting the cable ties. 5 Open the installer switch box as follows: 3 Remove the clips that lock the valves in place. 2× 4 Uncouple the piping. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 26
4 Drain remaining water and brine from the hydro module. Open the water and brine air purge valves at the top of the module to speed up the draining process. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
2 Connect the drain hose to the drain. See "6.3.4 To connect the Also read the precautions and requirements in the drain" [ 4 27]. drain hose to the "General safety precautions" chapter. 3 Slide the unit into position. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 28
▪ Fluid pressure – Domestic hot water tank. The maximum fluid pressure of the domestic hot water tank is 10 bar. Provide adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Schrader valve of the expansion vessel. To make sure that the unit operates properly: ▪ You must check the minimum water volume. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
3 Position the 3‑way valve correctly. 2 Mount the included safety valve on top of the vessel. 3 Install a shut-off valve (field supplied) below the vessel. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Insulating the water piping. inlet stop valves during periods of absence. NOTICE Install air purge valves at all local high points. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Keep the following in mind: 7.3.7 To insulate the water piping The piping in the complete water circuit MUST be insulated to prevent reduction of the heating capacity. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
C5: Power supply for the rest of the unit current sensors. (1N~) Wires: 3×2. Use part of the cable (40 m) delivered as accessory. [9.9.1]=3 (Power consumption control = Current sensor) [9.9.E] Current sensor offset Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 35
At that moment, the unit compressor will not operate. The wiring to the unit is different depending on whether the power supply is interrupted or not. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 36
(voltage supplied by PCB). The voltage-free contact shall ensure the minimum applicable load of 15 V DC, 10 mA. Connect the preferential kWh rate power supply contact (S1S) as 1× follows. 2× 1× Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
INFORMATION If the desired leaving water temperature is weather dependent, the full time outdoor temperature measurement is important. Remote outdoor sensor + cable (40 m) delivered as accessory EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
"6.2.2 To open the indoor 1 Top panel 2 User interface panel 3 Installer switch box cover 2 Connect the electricity meters cable to the appropriate terminals as shown in the illustration below. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
To connect the space cooling/heating ON/ Cable sleeve (field supply) OFF output Wires: (2+1)×0.75 mm² Maximum load: 3.5 A, 250 V AC — unit" [ 4 24]): 1 Open the following (see "6.2.2 To open the indoor EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
2 User interface panel 3 Front panel 4 Main switch box cover 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
2 Connect the safety thermostat (normally closed) cable to the appropriate terminals as shown in the illustration below. 2 Connect the power consumption digital inputs cable to the appropriate terminals as shown in the illustration below. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
(brine low pressure switch not installed). If not, this causes Restriction: Passive cooling is only possible for: an error. ▪ Heating only models Wires: 2×0.75 mm² ▪ Brine temperatures between 0 and 20°C Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
The indoor unit contains an integrated LAN adapter (model: hot water). BRP069A61), which allows for: ▪ LED flashing: ▪ App control of the Daikin Altherma heat pump system adapter performing a Smart Grid compatibility ▪ Integration of the heat pump system in a Smart Grid application check.
9 LAN adapter Smartphone with app control 9.1.1 System layout "9.2.4 Solar inverter/energy management system" [ 4 47]. Integrating the LAN adapter into a Daikin Altherma system allows for Circuit breaker the following applications: Solar inverter/energy management system Solar panels ▪ App control (only) "9.2.3 Electricity...
P/P1 N/P2 SG0 L SG1 L communication between Daikin Altherma system and smartphone. In case of Smart Grid application (only), the router is NOT a mandatory component, but only used for configuration purposes. In case of app control...
Three 2CMA100166R1000 B23 212-100 d Field-supplied Ethernet cable: ▪ Minimum category: Cat5e ▪ Maximum length: ▪ 50 m in case of Cat5e cables ▪ 100 m in case of Cat6 cables Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Connector X1A is for the connection of the LAN adapter to the digital 1 Top panel outputs of a solar inverter/energy management system, and allows 2 User interface panel for the integration of the Daikin Altherma system in a Smart Grid 3 Front panel application. 4 Main switch box cover X1A/N+L supply a 230 V AC detection voltage to the input contact of...
After correct installation and system 230 V AC – 20 mA. start-up, all system components (LAN adapter, router, and Online Controller app) should be able to find each other automatically by way of their IP address. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Retrieval via Instruction To update LAN adapter software The Daikin Online Controller app ▪ In the app, go to "Adapter information" > "IP address". Prerequisite: A router is (temporarily) part of the layout, you have a smartphone with the Online Controller app, and the app notified you ▪...
▪ Via the DIP switch (preferred method); Via the app ▪ Via the configuration web interface; Open the Online Controller app and perform a factory reset. ▪ Via the Online Controller app. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Use appropriate tooling to set the DIP switches to another Primary DNS position. Beware of electrostatic discharge. The LAN adapter allows for the connection of the Daikin Altherma Secondary DNS system to a solar inverter/energy management system, and enables it to run in various Smart Grid operation modes. In this way, all...
The solar inverter/energy management system controls the state of the digital inputs of the LAN adapter. Depending on the state of the inputs (open or closed), the Daikin Altherma system can run in the Static power limitation Static power limitation...
9.5.2 Operation modes In the "Recommended ON" operation mode, the power consumption of the Daikin Altherma system is limited either statically or "Normal operation/Free running" mode dynamically. In both cases, it is possible to include the power consumption of the electrical heaters in the calculation (default NOT In the "Normal operation"/"Free running"...
For a complete description of the status LEDs, check "9.1 About the adapter. adapter" [ 4 43]. INFORMATION If none of the corrective actions work, try performing a power reset of the total system. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
1 Set the user permission level to Installer. See "To — level" [ 4 55]. change the user permission 2 Go to [9.I]: Installer settings > Overview field settings. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Leaving water temperature setpoint Measured tank temperature k Malfunction b Current date and time A malfunction occurred. "14.4.1 To display the help text in case of a malfunction" [ 4 95] for more information. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Turn or press the left dial to Commissioning go to the submenu. Perform tests and maintenance. Change the active user profile. User profile Turn heating/cooling functionality and Operation domestic hot water preparation on or off. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
In this example, Monday is the first day you programmed. Thus, the last programmed action is valid up to the first action of next Monday. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
4 Confirm the changes. local circumstances such as climate and the insulation of the house, 5 Select Saturday. the curve can be adjusted by an installer or user. 6 Select Copy. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
: Domestic hot water Possible actions on this screen X1, X2 Examples of outdoor ambient temperature Go through the temperatures. Change the temperature. Go to the next temperature. Confirm changes and proceed. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
[3.6] Additional zone > Schedule Cooling WD curve In this menu item you can indicate if the room temperature is Tank [5.C] Tank > WD curve controlled with a schedule or not. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 63
NOT guaranteed. However, if room antifrost [2‑06] is activated, limited frost protection by the unit is possible: ▪ 0 No: Antifrost functionality is OFF. ▪ 1 Yes: Antifrost functionality is on. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
▪ 1: Yes Heating schedule You can set the main zone heating temperature schedule using the schedule screen. For more information about this screen, see Example" [ 4 59]. "10.3.7 Schedule screen: Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 65
▪ 1: Fancoil unit ▪ 2: Radiator The setting of the emitter type has an influence on the space heating setpoint range and the target delta T in heating as follows: EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 66
Human Comfort Interface (BRC1HHDA used as room thermostat). Code Description [2.9] [C‑07] ▪ 0: Leaving water ▪ 1: External room thermostat ▪ 2: Room thermostat Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 67
By setting the weather‑dependent curve to a higher the additional zone, if there is a cooling demand in the position, it cannot drop below the minimum setpoint. See additional zone. the illustration below. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
For more information about how to do this, "10.3.5 Setpoint screen" [ 4 58]. Schedule Indicates if the desired leaving water temperature is according to a zone" [ 4 64]. schedule. Also see "10.5.3 Main Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 69
1: Fancoil unit Maximum 65°C Variable (see [3.B.1]) 2: Radiator Maximum 65°C Variable (see [3.B.1]) Setpoint range For more information about this setting, also see "10.5.3 Main zone" [ 4 64]. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
▪ 10°C~35°C Heating/cooling The system can heat up and cool down a space. You have to tell the system which space operation mode to use. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 71
Not configuring the system in this way could cause damage to the heat emitters. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 72
The maximum values depend on the unit type: a Space heating/cooling control [9-0D]=0 [9-0D]=5 b Off a (kPa) a (kPa) c On d LWT temperature e Actual f Desired g Pump operation b (l/min) b (l/min) Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
0°C 0°C significant. In case of frequent domestic hot water operation, frequent and long space heating/cooling Absolute desired LWT interruptions will happen. Weather dependent desired LWT EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 74
See the operation manual for more details. Disinfection function is restarted in case the domestic hot water temperature drops 5°C below the disinfection target temperature within the duration time. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 75
)>maximum heat pump temperature–[6‑01] curve type [2.E] menu. See [ 4 64] for more "10.5.3 Main zone" –[6‑01]) information. HP MAX Code Description [5.E] ▪ 0: 2-points ▪ 1: Slope-Offset EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
24 hours. These settings can be changed 1 Go to [7.4.1]: User settings > Quiet > during initial configuration or via the menu structure [7.2]: Activation. User settings > Time/date. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
You can set the High, Medium and Low electricity [8.6] Operation modes Current operation mode prices according to your electricity supplier. Example: Defrost/oil return 3 Confirm the changes. mode [8.7] About Version information about the system EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
(see table below) and is then the Backup heater maximum capacity during emergency operation. Besides the type of backup heater, the voltage, configuration and capacity must be set on the user interface. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 79
[7-06] Activation of the HP forced off mode [8-01]+ [8-01]+ [8-04] [8-04] ▪ 0: disabled [8-02] [8-02] ▪ 1: enabled [8-01] [8-01] [5-03] [4-02] [F-01] 35°C Ambient (outdoor) temperature EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 80
[D‑00] Backup heater Compressor thermostat. Forced OFF Forced OFF Allowed Power consumption control Power consumption control [ 4 10] for detailed information about "5 Application guidelines" this functionality. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 81
If only 1 or no power meter is used, select 'None' to indicate the corresponding pulse input is NOT used. Code Description [9.9.3] [5-05] Limit: 0 A~50 A EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 82
[C-03]+[C-04] [C-03] calc Outdoor temperature Bivalent ON temperature (variable). Below this calc temperature, the auxiliary boiler will always be ON. T calc never go below [C‑03] or above [C‑03]+[C‑04]. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 83
Alarm output logic 2 Determine the value of [C‑03] using the graph: [C-09] Alarm No alarm No power supply to unit Closed output Open output Open output Open output Closed output EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
MUST be set to –12°C or lower. Result will be that the ▪ 1: On brine mixture may NOT freeze above that temperature. To prevent freezing of the unit, check the type and concentration of the brine carefully. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
User profile Operation Room Space heating/cooling Tank Setpoint screen Not applicable (**) Only accessible by installer INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Ext. amb. sensor offset Averaging time [9.C] Bivalent Bivalent Boiler efficiency Temperature Hysteresis Only applicable in Swedish language. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
If NOT, burning of the compressor might To perform an air purge on the brine circuit via brine be the result. pump test run or 10-day brine operation function. To perform a test run. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
"To perform an air [ 4 88]). In this case, use a brine purge with a brine filling station" filling station and the unit's own brine pump simultaneously. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
1 Set the user permission level to Installer. See "To — level" [ 4 55]. change the user permission 2 Go to [A.2]: Commissioning > Actuator test run. 3 Select a test from the list. Example: Pump. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
36 hours of power-on, manually disable room frost dryout. protection by setting [2‑06] to "0", and KEEP it disabled until the screed dryout has finished. Ignoring this notice will result in cracking of the screed. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
PCB. If the UFH screed dryout program was stopped due to a power failure and the power resumes, the program will automatically restart the last implemented step. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
▪ Flush the system and install an additional water filter (preferably of the filter, do NOT use excessive force when you reinsert a magnetic cyclone filter). INFORMATION It is recommended to perform this maintenance more than once a year. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Symptom: The unit is NOT heating as expected Possible causes Corrective action The temperature setting is NOT Check the temperature setting on correct the remote controller. Refer to the operation manual. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Actuators > Forced off contact. If Forced off contact is On, the unit is operating under the preferential kWh rate. Wait for the power to return (maximum 2 hours). Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Error codes: Overview between pressure relief valve and the cold water inlet. Error codes of the unit ▪ Replace the pressure relief valve. Error code Description 7H-01 Water flow problem EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 96
F6-00 U2-00 OU: Defect of power supply voltage OU: Abnormal high pressure, actuation of FA-00 U3-00 Underfloor heating screed dryout function not completed correctly H0-00 OU: Voltage/current sensor problem Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery. EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
16 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). 16.1 Piping diagram: Indoor unit...
Only for preferential kWh rate Backup heater control PCB power supply with separate power supply with separate Inverter PCB normal kWh rate power supply normal kWh rate power supply * Demand PCB EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 100
Safety thermostat contact: DC detection (voltage supplied 16 V DC detection (voltage by PCB) supplied by PCB) Shut-off valve Shut-off valve Switch box (7) Option PCBs (7) Option PCBs Alarm output Alarm output Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Page 101
Power limitation demand input 3 FIELD SUPPLY A8P: X801M: 3-5 signal 2 core Power limitation demand input 4 Router for LAN adapter A8P: X801M: 4-5 A15P: X4A signal ethernet 4D121919 EGSAH/X06+10DA9W(G) Installer reference guide Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
A (kPa) B (l/min) 3D122776 External static pressure (ESP) Brine flow rate NOTICE Selecting a flow outside the operating area can damage the unit or cause the unit to malfunction. Installer reference guide EGSAH/X06+10DA9W(G) Daikin Altherma 3 GEO 4P569820-1A – 2019.09...
Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with product according instructions accompanying documentation.
2/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value Room └─ Antifrost 1.4.1 [2-06] Activation 0: Disabled 1: Enabled 1.4.2 [2-05] Room antifrost temperature 4~16°C, step: 1°C 8°C └─...
Page 106
3/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value [0-00] Leaving water value for high ambient temp. for LWT add zone heating WD curve. [9-05]~min(45,[9-06])°C, step: 1°C [2-0C]=0 22°C [2-0C]=1...
Page 107
4/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value 5.7.2 [2-00] Operation day 0: Each day 1: Monday 2: Tuesday 3: Wednesday 4: Thursday 5: Friday 6: Saturday 7: Sunday 5.7.3 [2-02]...
Page 108
5/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value 9.1.6 [1-03] Leaving water value for high ambient temp. for LWT main zone heating WD curve. [9-01]~min(45, [9-00])°C , step: 1°C [2-0C]=0 22°C [2-0C]=1...
Page 109
6/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value 9.6.6 [8-01] Maximum running timer 5~95 min, step: 5 min 30 min 9.6.7 [8-04] Additional timer 0~95 min, step: 5 min 95 min Installer settings [4-04]...
Page 110
7/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value [0-00] Leaving water value for high ambient temp. for LWT add zone heating WD curve. [9-05]~min(45,[9-06])°C, step: 1°C [2-0C]=0 22°C [2-0C]=1...
Page 111
8/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value [2-0C] What emitter type is connected to the main LWT zone? 0: Underfloor heating 1: Fancoil unit 2: Radiator [2-0D] What emitter type is connected to the additional LWT zone? 0: Underfloor heating...
Page 112
9/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value [6-0C] What is the desired reheat temperature? 30~min(50, [6-0E])°C, step: 1°C 45°C [6-0D] What is the desired DHW production type? 0: Reheat only 1: Reheat + sched.
Page 113
10/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value [C-04] Bivalent hysteresis temperature. 2~10°C, step 1°C 3°C [C-05] What is the thermo request contact type for the main zone? 0: - 1: 1 contact 2: 2 contacts...