Background Music - Honeywell Gent Viglion EN54 Generic Commissioning Instructions

For the fire alarm systems
Table of Contents

Background Music

The background music system should be connected to the control panel as shown below. The setting the 0dBA pre-amplified output
if adjustable must not cause the pointer on the VU meter at the control panel to deflect above 0dBA, in the red range, see page 22.
Further adjustment of volume level of audio to the speaker circuits is made during the configuration stage, this is done using the
commissioning tool. Volume adjustment is also possible using a remote control, see the micro DAU section.
Amplified volume
control adjusts
the pre-amplified
output.
PA Microphone
The PA microphone should be connected to the control panel as shown below. When configuring the system it is possible to select
the voice alarms zones to which PA announcements apply. An attention tone such as a bing bong tone can be configuration to sound
each time the press to talk button on the microphone is pressed.
Spot announcement machine
Multi play CD
Twin cassette deck
Digital
AM/FM Tuner
Amplifier
R
L
Pre-amplified output
0dB maximum
Mono
Stereo
L
R
BGM
P15
Audio Control Card
Recommended cable Belden No 9842
Cable distance 100m maximum
15-way D-type connector
Vigilon Compact VA system
There are many types
of entertainment systems
that are commercially available.
This example show one
arrangement of how
an entertainment system may
be connected to the panel.
DO NOT connect the
Speaker outputs of
the Amplifier to the
Audio Control Card.
PANEL
Junction box
PA
PA MIC 1
B
A
24V
PA1
P14
Audio Control Card
0V
PTT1
PANEL