INSPIRE E10/E15
Fire Alarm Control panels
Operating Instructions
Table of Contents
loading

Summary of Contents for Honeywell NOTIFIER INSPIRE E10

  • Page 1 INSPIRE E10/E15 Fire Alarm Control panels Operating Instructions...
  • Page 2: Table Of Contents

    CONTENTS SCREEN and Day/Night and Zonal Indicator Settings Conventions System Information Abbreviations Log In and Out Introduction Display and controls Touch screen display Panel Buzzer LED indicators and PUSH Button Controls Touch Screen buttons, icons and symbols Normal SAFE Condition PIN entry to Controls Fire Condition What do I Need to do?
  • Page 3: Conventions

    INSPIRE E10/E15 Control Panels - Operating instructions CONVENTIONS ABBREVIATIONS Where appropriate, in this manual there are advisory Control and Indicating Equipment notes, warnings and cautions to remind you to consider Central Processing Unit safety at all times. Smaller size Notifier panel Larger size Notifier panel This symbol precedes a note that FARE...
  • Page 4: Introduction

    INTRODUCTION PANEL BUZZER The purpose of this manual is to explain how to use the INSPIRE E10/E15 Fire Alarm Control panel’s - Control and Indicating Equipment CIE (hereafter also referred to as the ‘panel’ or ‘control panel’). It documents how to use the built-in touch screen and push button This internal panel buzzer provides an audible alert to controls to access various functions and/or carry out...
  • Page 5: Led Indicators And Push Button Controls

    INSPIRE E10/E15 Control Panels - Operating instructions LED INDICATORS AND PUSH BUTTON CONTROLS There are 7 status LED indicators provided on the panel fascia and there are 3 push buttons for event conditions. Condition / Description FIRE Control Colour FIRE A fire condition has been detected.
  • Page 6: Touch Screen Buttons, Icons And Symbols

    TOUCH SCREEN BUTTONS, ICONS AND SYMBOLS Essential and Emergency Controls Description Pressing the ‘Reset Panel’ touch screen button or the panels ‘Reset Panel’ push button it will reset the panel Reset Panel to return it to normal condition after an event. Pressing the ‘Silence Alarms’...
  • Page 7 INSPIRE E10/E15 Control Panels - Operating instructions Event Symbols Description This indication shows there are a few active Fire events. In this example the number signifies there are 4 active Zone Fires. By selecting this icon you can view active Zones in fire.
  • Page 8 Fire Brigade Description status This 'FD Called' indication is given as a feedback that the Fire Brigade action was successfully deployed. The ‘Activated' indication is given when the Fire Brigade link is activated automatically. This 'Fault' indication is given when the Fire Brigade link or the Routing Equipment is faulty.
  • Page 9 INSPIRE E10/E15 Control Panels - Operating instructions Fault Routing equipment status Description This 'Activated' indication is given when Fault Routing equipment has activated. This 'Fault' indication is given when Fault Routing equipment or the transmission path is faulty. This 'Disabled' indication is given when Fault Routing equipment is disabled. This is a delayed status indication which appears with delayed operation of Fire Routing equipment.
  • Page 10 Selections Description Selecting this icon will open various settings or view options for selection. Selecting this button expands information normally hidden. Selecting this button compresses and hides the displayed information. Selecting this button provides more information on the subject. Selecting this button takes you to the previous screen. Selecting this button exits the menu.
  • Page 11: Normal Safe Condition

    INSPIRE E10/E15 Control Panels - Operating instructions NORMAL SAFE CONDITION Date & Time   Access Level   LED indication of panel / system status.  FIRE Physical Push buttons - Essential controls.  FAULT FAULT System Condition  SYSTEM FAULT DISABLED Toggle between Day Mode and Night Mode...
  • Page 12 Condition and Function Status If you navigate away from an Event page then the Condition and Function Status will remain. For example this may be the case if the menu icon is accessed to view historic events or enter the Enable/Disable controls. Condition / Description ...
  • Page 13 INSPIRE E10/E15 Control Panels - Operating instructions Day or Night Mode operation The Toggle function, if configured for your system, will allow a change between Day Mode and Night Mode. The Day Mode is made active on preselected days of the week over preselected time period. Outside the Day Mode the Night mode is automatially made active.
  • Page 14: Pin Entry To Controls

    PIN ENTRY TO CONTROLS Many of the touch screen control buttons and physical push buttons control require PIN code entry. Each on-site authorised user will have a PIN configured by the service organisation to access controls at the Control panel. This allows authorised users to control the fire alarm system during normal, fault, disablement, test and fire conditions.
  • Page 15: Fire Condition

    INSPIRE E10/E15 Control Panels - Operating instructions FIRE CONDITION When the devices responsible for the alarm is cleared for normal operation then select When one or more fire events occur, the screen turns red,  Reset Panel touch screen or press the the first zone in alarm and the time the zone went into the push button on the panel.
  • Page 16: Evacuate Button A Future Function

    Evacuate Button a future function. EVACUATE BUTTON a future function. including sounder devices are automatically activated.  Select Show All button to view details of all active This touch screen 'Evacuate' button Zone fire events. is not VdS approved. Normally hidden, Log Book Entry this button is configured during Enter information about this fire event(s) in the log...
  • Page 17 INSPIRE E10/E15 Control Panels - Operating instructions FIRE LIST VIEW   Select ‘Show All’ in the active Fire screen and then List view tab. The list shows further information of Zones  in fire. Each Zone can be expanded further by selecting the down arrow icon to show details of device that has detected the fire event.
  • Page 18: Fire Zone View

    Fire Zone View FIRE ZONE VIEW On selecting ‘Show All’ the page changes to List view. On this page there is a button for 'Zone View'. By selecting the 'Zone View' you will see all the active Zones that are in fire condition. To be advised.
  • Page 19: Enable / Disable Zones

    INSPIRE E10/E15 Control Panels - Operating instructions ENABLE / DISABLE ZONES How to Enable / Disable Zone(s) You can selectively disable or enable Zone(s) using the  Select the Menu icon and then select ‘Group by: Zones’ view. Also you can enable or disable ...
  • Page 20: Enable / Disable Devices On A Loop

    Enable / Disable Devices on a Loop How to Enable / Disable Device(s) ENABLE / DISABLE DEVICES ON A LOOP  Select the Menu icon and then You can selectively disable or enable Device(s) on a Loop and  select the ‘Menu’ tab disable or enable System Functions.
  • Page 21: Enable / Disable Devices By Detection Zone

    INSPIRE E10/E15 Control Panels - Operating instructions How to Enable / Disable Device(s) in a Zone ENABLE / DISABLE DEVICES BY  Select the Menu icon and then select the DETECTION ZONE  ‘Menu’ tab You can selectively disable and enable devices in ...
  • Page 22: Fault Warnings Condition

    Fault Warnings condition FAULT WARNINGS CONDITION What do I need to do? All active Fault Warnings events will appear on the display and can also Firstly silence the panel buzzer  be listed by selecting the active Fault summary icon .
  • Page 23: Disablement Condition

    INSPIRE E10/E15 Control Panels - Operating instructions DISABLEMENT CONDITION What do I need to do? All active Disablement events will appear on the display Where there are many active disablement events  with the panels Disablement LED lit. The Disablement listed, then use the Search facility and enter events can also be listed by selecting the active...
  • Page 24: Test System

    Test System TEST SYSTEM The detectors in the system can be tested on a zone by zone basis without affecting Outputs, like the Alarm Devices, Voice Alarms and Fire Brigade link.        TEST  ...
  • Page 25 INSPIRE E10/E15 Control Panels - Operating instructions How to put a detection Zone in test   Select the Menu icon and then select ‘Test System’   Select the ‘Test Type’ tab and then select ‘Test Mode - Detection Test’ ...
  • Page 26: Viewing The Event Logs

    Viewing the Event Logs VIEWING THE EVENT LOGS The system events of Fire, Fault, Disablement and Test are logged at the panel and can be recalled and viewed. The panel can hold 10,000 events and events can be recalled and filtered for viewing on the panel display. The filtering enables specific events to be listed for analysis.
  • Page 27 INSPIRE E10/E15 Control Panels - Operating instructions How to filter and view events   Select the Menu icon and then select the ‘Menu Tab’  Select the ‘Event History’ to view the Historic Event Log.  You can select the ‘List’ icon and select sort events by to either ‘Most recent first’...
  • Page 28: Time And Date Settings

    Time and date settings TIME AND DATE SETTINGS The time and date settings can be adjusted at a panel.            These are future options...
  • Page 29 INSPIRE E10/E15 Control Panels - Operating instructions Once an adjustment is made to the time and date at one panel in a network of panels, the other panels time and date settings get adjusted automatically to show same time and date at panels throughout a network.
  • Page 30: Display Settings

    Display settings How to set the display brightness DISPLAY SETTINGS  Select the Menu icon and then select the a future feature  ‘Menu Tab’ The panel display brightness can be adjusted to a  required level with the panel mains supply connected Select ‘Settings’...
  • Page 31: Language And Country Settings

    INSPIRE E10/E15 Control Panels - Operating instructions How to set the Language and Country LANGUAGE AND COUNTRY SETTINGS  Select the Menu icon and then select the This is an Access level 3 control.  ‘Menu tab’ The language setting allow selection of those languages enabled by the country code commissioned ...
  • Page 32: Screen And Day/Night And Zonal Indicator Settings

    SCREEN and Day/Night and Zonal Indicator Settings How to turn off/on the on screen zonal SCREEN AND DAY/NIGHT AND ZONAL indication? INDICATOR SETTINGS A future option which is not VdS approved. You can turn the Zonal indicators to On or Off. If switched ...
  • Page 33: System Information

    INSPIRE E10/E15 Control Panels - Operating instructions How to view system information? SYSTEM INFORMATION  Select the Menu icon and then This is a display of panel identification and the modules that are fitted  select the ‘Menu tab’ within the enclosure, the slot location of each module along with software version and serial number.
  • Page 34: Log In And Out

    Log In and Out How to Log-In as another level User? LOG IN AND OUT  Select the Menu icon and then select You can log in to access level 2 using a pin code 22. At  the ‘Menu tab’ any time you can log out and return to access level 1 by selecting ‘Logout’.
  • Page 35 INSPIRE E10/E15 Control Panels - Operating instructions...