Honeywell ESSER IQ8Control C Installation Instruction

Honeywell ESSER IQ8Control C Installation Instruction

Fire alarm
Hide thumbs Also See for ESSER IQ8Control C:
Table of Contents
Fire Alarm Control Panel IQ8Control C / M
Installation Instruction
G B
798951.10.GB0
04.2015 / AA
Table of Contents
loading

Summary of Contents for Honeywell ESSER IQ8Control C

  • Page 1 Fire Alarm Control Panel IQ8Control C / M Installation Instruction 798951.10.GB0 04.2015 / AA...
  • Page 2 This product must only be used for the applications outlined in the catalogue and the technical description and in combination with external components and systems which have been approved or recommended by Esser by Honeywell. Warning In order to ensure correct and safe operation of the product, all guidelines concerning its transport, storage, installation, and mounting must be observed.
  • Page 3: Table Of Contents

    Fire Alarm Control Panel IQ8Control C / M Table of contents General / Application ..............................5 Standards and guidelines ............................7 Approvals ................................7 Transport damage inspection ............................ 8 Configuration variants .............................. 10 Special configuration – Swiss option ....................... 11 FACP IQ8Control C ............................
  • Page 4 Fire Alarm Control Panel IQ8Control C / M System overview ..............................124 Function for fire alarm control panels ........................125 14.1 Use of the loop module in door control systems ................... 125 IQ8Wireless ................................126 Important battery information ..........................127 Top hat rail mounting kit (Part No.
  • Page 5: General / Application

    Fire Alarm Control Panel IQ8Control C / M General / Application This installation manual describes how to assemble the housing, install within a building and how to install a fire alarm system IQ8Control panel. The instructions form part of the fire alarm system (FAS) and should be kept in an accessible location in the immediate vicinity of the fire alarm control panel (FACP).
  • Page 6 Fire Alarm Control Panel IQ8Control C / M tools 8000 service and programming software The commissioning and configuration of the fire alarm system requires the use of the tools 8000 service and programming software. Depending on the software and system-specific customer data programming of your panel, its functions and display characteristics might differ from the ones described in this manual! The terminal connections and connections shown in this installation manual relate only to the specifications for the panel operating system software for the Federal Republic of Germany [D].
  • Page 7: Standards And Guidelines

    Fire Alarm Control Panel IQ8Control C / M Standards and guidelines The general technical rules must be observed when installing fire alarm systems. Any deviation from those rules is only admissible if the same degree of safety can be ensured with different means. Installations within the European Community are primarily subject to all EU regulations defining the current standards for security systems.
  • Page 8: Transport Damage Inspection

    Fire Alarm Control Panel IQ8Control C / M Transport damage inspection Please check all of the packaging and components for damage before commencing the assembly and installation work. Do not assemble or install visibly damaged modules and components! Fig. 1: Checking components for damage sustained during transport FB 798951.10.GB0 / 04.15...
  • Page 9 Fire Alarm Control Panel IQ8Control C / M 1. The cover contact and both connecting cables for the rechargeable batteries have already been attached to the Basic module. 2. Pull the ribbon cable of the operating module off the connectors of the Basic module. 3.
  • Page 10: Configuration Variants

    Fire Alarm Control Panel IQ8Control C / M Configuration variants The operating module front (7860xx) is available in various language versions. The language is defined with the 2-digits of the part number, e.g. 786002 = English lettering. IQ8Control C IQ8Control M Operating module ...
  • Page 11: Special Configuration - Swiss Option

    Fire Alarm Control Panel IQ8Control C / M Special configuration – Swiss option IQ8Control C IQ8Control M Operating module   786261   786262   786263 Fig. 3: Operating module – Swiss with integrated Fire department operating panel (FBA) For country-specific displays and labels as well as further information for refer to operating instructions FACP IQ8Control C/M (Part No.
  • Page 12: Facp Iq8Control C

    Fire Alarm Control Panel IQ8Control C / M FACP IQ8Control C The configuration of the FACP IQ8Control C includes:  1 Basic module  1 Power supply module  1 Field device module or 1 Extension module In the full configuration, two freely selectable micro modules can be employed.
  • Page 13 Fire Alarm Control Panel IQ8Control C / M Configuration of FACP IQ8Control C Example 1: MM 1 Basic module with a micro module and a Field device module (Part No.772479 without micro module slot) on slot 1 of the Basic module. Application: With this configuration, for example, a single control panel with an loop and max.
  • Page 14: Facp Iq8Control M

    Fire Alarm Control Panel IQ8Control C / M FACP IQ8Control M The configuration of the FACP IQ8Control C / M includes:  1 Basic module  1 Power supply module  1 Field device module or 1 Extension module 1 ...
  • Page 15 Fire Alarm Control Panel IQ8Control C / M Example: Configuration of FACP IQ8Control M Example 1: Basic module with a Field device module MM 1 (without micro module slot) on slot 1 and one MM 4 Extension module (with 3 micro module slots) on slot 2.
  • Page 16 Fire Alarm Control Panel IQ8Control C / M Example: Configuration of FACP IQ8Control M Example 3: Basic module with a Field device module (without micro module slot) on slot 1 and one Extension module (with 3 micro module MM 2 slots) on slot 2.
  • Page 17 Fire Alarm Control Panel IQ8Control C / M Three part housing with integrated printer The integrated printer and the operating module front are mounted in the upper housing. Due to the depth of the printer, the Basic module and all of the plug-in cards are integrated into a separate housing beneath. The emergency power supply with max.
  • Page 18 Fire Alarm Control Panel IQ8Control C / M Location of the components in a three part FACP housing IQ8Control M Fig. 11: Location of the components in a three part housing Mounting plate The mounting plate (Part No. 057633) allows installation of two esserbus ®...
  • Page 19: Definition Of The Primary Loop Number

    Fire Alarm Control Panel IQ8Control C / M Definition of the Primary loop number Individual assemblies of the FACP IQ8Control can be switched on/off with the internal primary loop number through the control panel keyboard or programmed with programming software . This internal primary loop number is composed of the control panel number, the slot and the assembly number.
  • Page 20 Fire Alarm Control Panel IQ8Control C / M Example: Primary Loop No. (Panel No. 01) Primary Loop No. Subassembly Position of modules Basic module Common Fault Relay (SaS-Relay) 0111 0112 Interface - RS485-1 or TTY 0113 Micro module slot Field device module 0121 Relay K2, K3 and K4 0122...
  • Page 21: Assembly And Installation Information

    Fire Alarm Control Panel IQ8Control C / M Assembly and installation information  The fire alarm control panel may only be installed in dry, clean, and adequately illuminated areas with restricted access. The ambient conditions must correspond to class 3k5 in accordance with DIN EN 60721-3-3:1995-09.
  • Page 22: Maintenance / Service

    Fire Alarm Control Panel IQ8Control C / M Maintenance / Service Maintenance is necessary for the proper operation of the fire alarm control panel as the function of the system parts can be affected by environmental conditions and ageing. Maintenance is regulated by national standards (e.g.
  • Page 23: Assembling The Wall Housing

    Fire Alarm Control Panel IQ8Control C / M Assembling the wall housing The housing is pre-assembled by factory delivery. For easy installation and correct assembly of the wall housing, carry out the following assembly steps in the order described: Fig. 14: Assembling the wall housing ...
  • Page 24: Fitting The Panel To The Mounting Surface

    Fire Alarm Control Panel IQ8Control C / M Fitting the panel to the mounting surface  Chose the place for mounting the panel as specified in the project documentation.  Observe the installation environment specifications.  Take note of the position of the cables and corresponding cable entry points ...
  • Page 25 Fire Alarm Control Panel IQ8Control C / M XX mm  Drill through the marks for the mounting holes to create four holes and insert suitable anchors.  The type of anchor best suited to this purposes depends on the mounting surface's material (cavity wall, concrete, wood etc.) and must be chosen accordingly.
  • Page 26 Fire Alarm Control Panel IQ8Control C / M The panel must be mounted on a flat surface using appropriate hardware (screws and dowels). Avoid mechanical stressing. It may only be commissioned after correct mounting on a wall or other mounting surface of sufficient strength to support the weight of the unit.
  • Page 27: Cable Glands

    Fire Alarm Control Panel IQ8Control C / M Cable glands  Lead the 230V main power cord through the wall and the cable entry provided in the rear of the unit (see Fig.). Fasten it using appropriate devices, e.g. plastic cable straps. Make sure that the mains and signal cables don’t interfere with the rear panel of the cabinet or the cabinet frame which is mounted on the rear panel.
  • Page 28: Connection Between The Housings

    Fire Alarm Control Panel IQ8Control C / M Connection between the housings The compact housing is connected to the extension housing using the connecting pieces provided. Example of housings fitted vertically on top of each other. Always use two connecting pieces  with cable entries.
  • Page 29: Operating Module / Housing Door

    Fire Alarm Control Panel IQ8Control C / M Operating module / Housing door The operating module/the housing door is installed by the manufacturer on the front housing part. If required for dismantling, loosen the 4 fixing screws  and remove the front part of the housing. Depending on the configuration, e.g.
  • Page 30: Housing Contact

    Fire Alarm Control Panel IQ8Control C / M Housing contact The housing contact provides the monitoring of the panels housing and may be used additionally for control function by means of service or maintenance work, e.g. to disconnect devices whilst the contact is open. Max.
  • Page 31: Electronic Devices

    Fire Alarm Control Panel IQ8Control C / M Electronic devices The FACP IQ8Control C / M has a modular design so that modules can be replaced/extended at any time. Only remove or insert modules when the FACP is voltage free. ...
  • Page 32 Fire Alarm Control Panel IQ8Control C / M Earth fault monitoring BR 1 1 2 3 Earth fault monitoring enabled (factory default = ON) 1 2 3 Earth fault monitoring disabled (not VdS appropriate) Information for powered loop systems In case of an earth fault with +U a ground fault message occurs and additionally the fault zone message "U...
  • Page 33 Fire Alarm Control Panel IQ8Control C / M 6.1.1 Specification Power supply module (Part No. 802426) Main voltage : 230 V AC (+10% / -15%) Rated current : 0,7 A Rated frequency : 50 Hz to 60 Hz Output voltage : 12 V DC Current for ext.
  • Page 34 Fire Alarm Control Panel IQ8Control C / M 6.1.2 Mains connection and earth connections The control panel may only be connected to the mains by a qualified electrician and in compliance with all relevant standards and regulations. The corresponding connection terminals are located on the basic module. Housing mantle T1.25A terminal...
  • Page 35 Fire Alarm Control Panel IQ8Control C / M 6.1.3 Protective and Functional earth The primary PE-connection (protective Wiring FACP IQ8Control C earth) of the mains supply must be connected to the appropriate terminal of Metal screws to the rear wall plate of the central unit's housing the FACP to ensure a proper operation of the system.
  • Page 36 Fire Alarm Control Panel IQ8Control C / M 6.1.4 Emergency power supply In case of loss of the mains voltage the control panel will be powered without a interruption by the connected battery. Depending on the capacity of the battery a backup time of up to 72 hours can be realised. After that time the external alarm devices must be still operable in an alarm condition.
  • Page 37 Fire Alarm Control Panel IQ8Control C / M 6.1.6 Checking the batteries Monitoring the batteries according to EN 54 In event of a failure of the rated voltage (230 V AC) and maximum load on the batteries, the supply of power must be guaranteed to ensure proper operation of the fire alarm control panel as well as the connected components and external devices.
  • Page 38 Fire Alarm Control Panel IQ8Control C / M Battery Monitor Module (Pat No. 788051.10) The battery monitor module is inserted between the 12 V battery to be monitored and the associated connection contact of the basic module of the FACP. Please see the documentation (Part No.
  • Page 39 Fire Alarm Control Panel IQ8Control C / M Wiring of two batteries max. 30 V DC / 1 A Battery 1 Akku 1 / T 4 A battery 1 Battery 2 max. 30 V DC / 1 A F2 battery 1 F3 battery 2 T2.5A T2.5A...
  • Page 40: Basic Module

    Fire Alarm Control Panel IQ8Control C / M Basic module The power supply module and a free selectable micro module may be installed on the appropriate Basic module connectors. >System connector 1< provides the connection of a Field device module or Extension module. The slot >System connector 2<...
  • Page 41 Fire Alarm Control Panel IQ8Control C / M Solder jumper to set whether the two batteries are connected and the monitoring for the free battery connection should be switched off. Open (default)  Connection of two batteries >Battery 1+2< closed ...
  • Page 42 Fire Alarm Control Panel IQ8Control C / M Connection of the AC mains voltage and emergency power supply For connecting the mains voltage (230 V AC) and emergency power supply, see Chapter 4.1. Mains 230V~ Fig. 32: Connection of the AC mains voltage and batteries Disconnect all power from the panel before carrying out any installation work! Observe before connecting the AC mains voltage (e.g.
  • Page 43: Software

    Fire Alarm Control Panel IQ8Control C / M Software System requirements: Firmware: from V3.01R000 Programming software tools 8000: from V1.15 6.3.1 Firmware Update The system software (Firmware) of the FACP IQ8Control may be updated directly at the panel via the integrated USB interface.
  • Page 44 Fire Alarm Control Panel IQ8Control C / M Open panel housing Set DIL switch S2 (1+2) on the Basic module in Pos. ON (LED V50 lits). Press reset button S1  FACP reset Wait until FACP is resetted and the display message „Servicemode“ appears. Connect USB cable (Part No.
  • Page 45 Fire Alarm Control Panel IQ8Control C / M 6.3.2 Customer data programming The Fieldbus- und panel interface PLus (Part No. 789862.10) or panel interface RS232 (Part No. 769828) incl. accessories is required to configure the panels Customer data. The software tools 8000 provides the configuration of the FACP IQ8Control functions and customizing the system to all requirements.
  • Page 46 Fire Alarm Control Panel IQ8Control C / M 6.3.5 Housing contact Housing open X7 X8 Depending on the panel housing used, up to four cover contacts can be connected to the connection terminals of the Basic module. A single contact per housing is integrated by factory settings. The opened housing contact is indicated by the illuminated LED Connection of one housing contact Connection of two housing contacts...
  • Page 47 Fire Alarm Control Panel IQ8Control C / M 6.3.6 Serial interface The serial interface on the Basic module may be configured as a TTY interface (20 mA) or as an RS485 interface. The required interface to connect external devices is selected by the Service software tools 8000. TTY interface These four terminals may be used for connecting an external V62 V63...
  • Page 48 Fire Alarm Control Panel IQ8Control C / M RS485 interface An external device, such as an LCD display panel, can be connected to the A/B terminals via the RS485 interface.  The RS485 BUS must be connected with an EOL resistor at both ends of the loop. ...
  • Page 49 Fire Alarm Control Panel IQ8Control C / M Common trouble relay (SaS) Contact change-over (EMI protected) Breaking capacity : 30 V DC / 1A Function Common trouble (SaS-relay FAULT) SaS-Relay If the control panel detects at least one trouble incident, relay activation will be interrupted and the relay will change its control status.
  • Page 50 Fire Alarm Control Panel IQ8Control C / M 6.3.7 Micro module slot Terminals (1-8) are provided at the micro module slot on the Basic module for connecting the freely selectable micro module. Assignment of the eight screw terminals will depend on the micro module type used. X27X28X29X30 1 2 3 4 5 6 7 8 micro module...
  • Page 51 Fire Alarm Control Panel IQ8Control C / M 6.3.8 Technical data Basic module Operating voltage : Internal via the power supply module, +5 V DC / + 12 V DC Quiescent current : approx 215 mA @ 12 V DC without operating module approx 230 mA @ 12 V DC incl.
  • Page 52: Field Device Module

    Fire Alarm Control Panel IQ8Control C / M Field device module The Field device module required in order to configure a stand-alone FACP in accordance to the appropriate standards and guidelines. The Field device module integrates all of the input and output modules that are necessary in addition to the modules on the Basic module to operate as a Fire Alarm Control Panel to DIN VDE 0833.
  • Page 53 Fire Alarm Control Panel IQ8Control C / M Field device module (Part No.772479) without micro module slot Field device module Fig. 43: Field device module (Part No.772479) Field device module (Part No.772477) with micro module slot Field device module Fig. 44: Field device module (Part No.772477) The Field device module (if available) must always be placed on the >System connector 1<...
  • Page 54 Fire Alarm Control Panel IQ8Control C / M Relay for connecting a master box. May also be used as a freely programmable relay. Relay K1 Selection of operating mode and emergency function by means of jumpers. (Monitoring range 50  to 1 k  ) Contact rating when used as a >non-monitored change-over contact<...
  • Page 55 Fire Alarm Control Panel IQ8Control C / M Connection terminals IN - top removable OUT - bottom removable Fig. 45: Connection terminals Connection terminals fire department operating panel Observe permitted torque (max. 0.4 Nm) of the terminals! Connection of the micro module Eight connecting terminals are provided for the micro module slot of the Field device module.
  • Page 56 Fire Alarm Control Panel IQ8Control C / M 6.4.1 Connecting fire department operating panel  Wiring differs from area to area and is governed by the requirements of the bottom - terminals regional fire department.  top - terminals A 12 V DC voltage is required for operation.
  • Page 57 Fire Alarm Control Panel IQ8Control C / M 6.4.2 Connecting master box (Relay K1) Relay K1 for the connection of a master box is part of the peripheral module. The control configuration of relay K1 can be set to  monitored and switching the positive potential ...
  • Page 58 Fire Alarm Control Panel IQ8Control C / M Operating mode 1  Relay K1 positive switching and monitored Fig. 49: Terminal of the master box relay K1 Relay K1 positive switching (+12 V DC / max. 1 A) and monitored intern Monitored end-of-line resistor R = 680 ...
  • Page 59 Fire Alarm Control Panel IQ8Control C / M Operating mode 1  Relay K1 – positive switching and monitored FACP IQ8Control C/M Master box Field device module (schematic circuit diagram) BACK MFAB acknowledge acknowledge ÜE - alarm ÜE + 680 + UB ext.
  • Page 60 Fire Alarm Control Panel IQ8Control C / M Operating mode 2  Relay K1 positive switching, not monitored Relay K1 Positive switching (+12 V DC / max. 1 A), intern not monitored Fig. 51: Terminal of the master box relay K1 Operating mode 3 ...
  • Page 61 Fire Alarm Control Panel IQ8Control C / M 6.4.3 Connecting Relays K2, K3, K4 Location of the relay K2,K3,K4 and the jumpers BR9 to 20 on the Field device module Jumpers are used for adjusting the three relays K2, K3 and K4 to a variety of requirements. The three relays may be coded independently of each other as >positive-switching<...
  • Page 62 Fire Alarm Control Panel IQ8Control C / M CPU failure mode function of relays K2, K3 and K4 Fig. 54: Location of the emergency mode jumpers BR3 to 5 on the Field device module Jumper X in position 1/2 No activation of the relay while the Fire Alarm Control Panel is in CPU failure mode (state on leaving factory).
  • Page 63 Fire Alarm Control Panel IQ8Control C / M 6.4.4 Technical data Field device module Operating voltage : Internal via the power supply module, +5 V DC / + 12V DC Quiescent current : approx. 15 mA @ 12 V DC Fuse F1 T1A –...
  • Page 64: Extension Module

    Fire Alarm Control Panel IQ8Control C / M Extension module Depending on the module type up to three slots for micro modules are integrated on the Extension module. Connections are available for each micro module. The pin assignment of the eight screw terminals depends on the employed type of micro module.
  • Page 65 Fire Alarm Control Panel IQ8Control C / M IQ8Control C The Field device module with a single micro module slot (Part No. 772478) must be placed on the >System connector 1< of the Basic module. This connector is normally used by the Field device module. Without the field device module a system configuration in accordance to the standards is not possible (refer to Chapter 4).
  • Page 66: Micro Module

    Fire Alarm Control Panel IQ8Control C / M Micro module The FACP IQ8Control C / M has a modular design, so that micro modules can be replaced/extended at any time. Only remove or insert micro modules when the FACP is voltage free. ...
  • Page 67 Fire Alarm Control Panel IQ8Control C / M Mode of loop operation The esserbus ® /esserbus ® PLus is a monitored two-wire loop fed from two sides and exhibiting loop topology. The use of zone isolators allows you to combine ring and spur loops as well as divide the loop into 127 detector zones with a total of 127 loop devices.
  • Page 68 Fire Alarm Control Panel IQ8Control C / M ® 7.1.1 esserbus loop module (Part No. 784382 / 784382.10 / 784382.D0) ® The loop module allows for esserbus connection and is configured with Programming software tools 8000 from V1.15. Fire alarm and extinguishing computer 8010 esserbus ®...
  • Page 69 Fire Alarm Control Panel IQ8Control C / M ® 7.1.2 esserbus -PLus loop module (Part No. 804382 / 804382.10 / 804382.D0) ® This module provides the "esserbus PLus" loop mode, e.g. for direct connection of audible loop devices. Note that the esserbus ®...
  • Page 70 Fire Alarm Control Panel IQ8Control C / M ® The esserbus PLus cable is directly connected to the terminals on loop module (Part No. 804382 / 804382.10 / 804382.D0) Example: ® esserbus PLus cable terminal  (Part No. 804382 / 804382.10 / 804382.D0) The cable screen must be connected to the...
  • Page 71 Fire Alarm Control Panel IQ8Control C / M 7.1.3 Maximum line lengths based on the total load factor of a loop FACP max. loop lenght Loop 1 Loop 2 Loop 3 Loop 4 Loop 5 Loop 6 up to 700 m 91 to 96 91 to 96 91 to 96...
  • Page 72 Fire Alarm Control Panel IQ8Control C / M 7.1.5 essernet ® module The essernet ® module permits networking up to 31 essernet ® devices, such as e.g. ESSER Fire Alarm Control Panel System and management systems. Additionally optional gateways are available to connect standard devices to the network.
  • Page 73 Fire Alarm Control Panel IQ8Control C / M ® 7.1.6 essernet micro module (Part No. 784840 / 784840.10 and 784841 / 784841.10) ® The essernet micro module must be placed on the micro module slot of the Basic module. There for it is required to set the corresponding jumpers on the Basic module to configure the terminals for the essernet ®...
  • Page 74 Fire Alarm Control Panel IQ8Control C / M Rotary address switch to select panel address factor x1 Rotary address switch to select panel address factor x10 64 pin connector for the micro module slot inside the FACP X4 / X5 jumpers for configuration of the terminals IN/OUT (terminal 1+2 and 3+4) copper cable fibre optic cable...
  • Page 75 Fire Alarm Control Panel IQ8Control C / M ® 7.1.7 Technical data essernet micro module essernet ® micro module 62.5 k essernet ® micro module 500 k (Part No. 784840 / 784840.10) (Part No. 784841 / 784841.10) Operating voltage : Internal via the power supply module, Internal via the power supply module, + 5 V DC +5 V DC...
  • Page 76 Fire Alarm Control Panel IQ8Control C / M Setting the essernet ® address The address of Network Micro Modules type 1 and 2 with hardware revision E and higher is set as a decimal number by means of two rotary switches. Use an appropriate screwdriver for setting switches S1 (x1) and S2 (x10).
  • Page 77 Fire Alarm Control Panel IQ8Control C / M 7.1.8 Features and installation informations  The outward and return lines of the essernet ® connection must always be routed separately from one another other; i.e. they must not be installed in one multipair cable or in one cable duct. Joint installation may affect the function or, if the cable/cable duct is destroyed, can cause complete failure of the connection if the outward and return cables become disconnected.
  • Page 78 Fire Alarm Control Panel IQ8Control C / M ® 7.1.10 FOC transmission line in the essernet ® Alternatively, the essernet can be set up with fibre optic cables. Optional fibre-optic converters are required for this. This FOC converter (Part No. 784763 / 784764 / 784765) converts electrical signals into optical signals for reliable data transmission under difficult transmission conditions in which, for example, copper cables cannot be used.
  • Page 79: Relay Module

    Fire Alarm Control Panel IQ8Control C / M Relay module 3-relay module / 3-relay common trouble module Micro module for activating external devices (not potential free), with monitoring capability. You may connect up to three external devices to this micro module. Relay assignment is programmed with the service PC and Programming software tools 8000 software.
  • Page 80 Fire Alarm Control Panel IQ8Control C / M Adjustment of the relays Relay Status Contacts switch S 1 Contact 10 k  monitored closed not monitored open 10 k  monitored closed not monitored open 10 k  monitored closed not monitored open No AC voltages may be applied to the relays built-into the Fire Alarm Control Panel.
  • Page 81 Fire Alarm Control Panel IQ8Control C / M Wiring an external device without loop monitoring Example with relay K2 (terminal 5 and 6), non-monitored mode external device alarm Fig. 68: Schematic wiring of an external device without loop monitoring L = inductive load relay = series diode BY251 (notice relays current max.
  • Page 82 Fire Alarm Control Panel IQ8Control C / M Connecting an external device with loop monitoring Monitored activation of external devices involves monitoring the loop for an end-of-line resistor of 10 k  . In the event of an incident, polarity changes between monitoring and activation voltage at the (relay) connection terminals.
  • Page 83 Fire Alarm Control Panel IQ8Control C / M Application examples (A) Three relays with a common external voltage (default setting). This application involves feeding an external voltage (e.g. +12V) to terminals 3 and 4 on the terminal card, this voltage then being switched via the relay to the external device for activation in the event of an incident occurring. 7 8 9 10 closed ext.
  • Page 84: 4- Relay Module

    Fire Alarm Control Panel IQ8Control C / M 4- Relay module This micro module accommodates four freely programmable, non-monitorable, potential-free relays for activating external devices and system components. Relay assignment is programmed with the service PC and programming software tools 8000. For each relay, you may enter a specific additional text comprising 25 characters per line for output on the display and protocol printer.
  • Page 85 Fire Alarm Control Panel IQ8Control C / M Terminal card assignment ext. device at relay K1 ext. device at relay K2 ext. device at relay K3 ext. device at relay K4 Fig. 74: Terminal card assignment Observe permitted torque (max. 0.4 Nm) of the terminals! Schematic circuit diagram (example using relay K1) Pow er supply external device...
  • Page 86 Fire Alarm Control Panel IQ8Control C / M 8.2.1 Technical Data Relay module 4-relay module (Part No. 787530) Operating voltage : Internal via the power supply module, + 5 V DC / +12 V DC Quiescent current : approx. 10 mA @ 12 V DC Fuse (F1, F2, F3, F4) : Multifuse 1 A (for Relay K1 to K4) Relay (K1, K2, K3, K4)
  • Page 87: Serial Interface Module

    Fire Alarm Control Panel IQ8Control C / M Serial interface module 8.3.1 RS 232 / TTY module This module provides either a serial RS 232 or TTY interface (20mA) for exchanging data with external devices connected. Assignment of the serial interface type is programmed with the service PC and software tools 8000. You may enter a specific additional text comprising 25 characters per line for output on the display and protocol printer.
  • Page 88 Fire Alarm Control Panel IQ8Control C / M external device Tx - Rx - transmitt not used not used transmitt Tx + Rx + not used Rx + receive Tx + not used Rx - Tx - receive Fig. 79: Assignment for terminal card TTY module If solder jumper BR3 is closed on the module, TTY interface may not be used.
  • Page 89: Master Box Activation Module

    Fire Alarm Control Panel IQ8Control C / M Master box activation module Micro module for activating a master box (MB) and alerting the relevant emergency services, such as the fire department. With the Fire Alarm Control Panel, a connection for a master box module is integrated in the Field device module.
  • Page 90 Fire Alarm Control Panel IQ8Control C / M DIL switch S2 The time for the duration of the activation of the MFAB can be selected using DIL switch S2. Selecting the activation time for the MFAB activation for approx. 6 seconds activation for approx.
  • Page 91 Fire Alarm Control Panel IQ8Control C / M Wiring of the terminal card + power supply not use MFAB MFAB reset (+12 V or +24 V / 300 mA) (schematic circuit diagram) monitoring power supply primary loop to MFAB (+MFAB) MFABrelay unlock fire department box (switched to GND max.
  • Page 92 Fire Alarm Control Panel IQ8Control C / M Inhibiting MFAB activation The master box or master box relay will not be activated if,  the cover contact is open. Factory setting of solder jumper on module: BR2 = open ; BR3 = closed. The customer data of the FACP must be programmed under menu point Functional designation of the MFAB control module to suppress the activation of the master box when the cover contact is open.
  • Page 93: Overview - Micro Module Terminals

    Fire Alarm Control Panel IQ8Control C / M Overview – micro module terminals Basic module IQ8 Control 1 2 3 4 5 6 7 8 micro module Fig. 82: Overview – micro module terminals 3 4 5 esserbus ® module (Part No.
  • Page 94 Fire Alarm Control Panel IQ8Control C / M RS232 / TTY module (Part No. 784842) 3 4 5 Serial interface, alternatively RS232- or TTY (20 mA) to connect external devices e.g. management systems, Printers, Remote indicator panels etc. not used TxD (transmitt) RxD (receive) not used...
  • Page 95 Fire Alarm Control Panel IQ8Control C / M 4 Relay module (Part No. 787536) Four dry relay contacts (not monitored) with programmable 3 4 5 operation mode normally open or normally close. Contact rating: max. 30 V DC / 1 A Quiescent current: approx.
  • Page 96: Installer Level - Commissioning / Maintenance

    Fire Alarm Control Panel IQ8Control C / M Installer level – Commissioning / Maintenance The Commissioning / Maintenance as well as Operations and Fire Alarm Control Panel functions which should only be performed by specialised installers or authorised persons are integrated under the menu options >Installer<...
  • Page 97 Fire Alarm Control Panel IQ8Control C / M The function menu of the installer level appears with four menu points: The function menu of the installer level with its four menu points appears after the successful entry of the code: Installer 1 Primary loop functions 2 Detector simulation...
  • Page 98: Primary Loop Function

    Fire Alarm Control Panel IQ8Control C / M 10.1 Primary loop function Primary loop function ® Under this menu point, the internal primary loops of this Fire Alarm Control Panel or other FACP in an essernet can be switched on or off and checked by a manual test function. Additionally, it is possible to replace single detectors in operative loops e.g.
  • Page 99: Testing (The Loop)

    Fire Alarm Control Panel IQ8Control C / M 10.2 Testing (the loop) 1 Switch on / reset Primary loop / transfer route 2 Switch off Primary loop : 121 3 Test 4 Replace detector Escape Function Fig. 86: Testing the loop ...
  • Page 100: Detector Replacement

    Fire Alarm Control Panel IQ8Control C / M 10.3 Detector replacement Replacement of fire and diagnostic detectors (4-zone module) Diagnostic fire detectors can be replaced without adjustment of the detector address on the base circuit board or overwriting data with the service PC. The menu options >Detector replacement< is inoperable for these detectors. Replacement of intelligent detectors Series 9200 (loop) ®...
  • Page 101 Fire Alarm Control Panel IQ8Control C / M Type/extent of the detector replacement without displayed Service-PC * trouble code The type and external switching of the exchanged detector are in conformance. For example, if a defective OHI-detector without a detector base output is replaced with a new OHI-detector without a detector base output.
  • Page 102: Simulation Of Detector States

    Fire Alarm Control Panel IQ8Control C / M 10.4 Simulation of detector states Under this menu point, the state of addressable detectors of the series 9200 and IQ8Quad (no esserbus ® transponder) can be simulated for test purposes. In all non-addressable detectors (Series 9000 / ES Detect), the detector zone state is simulated.
  • Page 103: Simulation Of Control States

    Fire Alarm Control Panel IQ8Control C / M 10.5 Simulation of control states Under this menu point, the state of any control, such as relays or open collectors, can be simulated for test purposes. The simulation of control states in an essernet ®...
  • Page 104: Query Of Additional And Info Texts Of Other Control Panels (Remote Text)

    Fire Alarm Control Panel IQ8Control C / M 10.6 Query of additional and info texts of other control panels (remote text) With this function, the programmed additional and info text for controls, detector zones or detectors of any Fire Alarm Control Panel in the essernet ®...
  • Page 105: Printer Function

    Fire Alarm Control Panel IQ8Control C / M 10.7 Printer function Under this menu point, the protocol printer connected to the Fire Alarm Control Panel (internal printer and/or external serial printer) can be switched on or off. In addition, the contents of the internal event memory of the control panel can be printed out on a local protocol printer.
  • Page 106 Fire Alarm Control Panel IQ8Control C / M Switching on the protocol printer Printer Switch off : 0110 Printer Switch on Print event mem Func.menu Repeat Select Fig. 95: Entering the number of the external (serial) printer  Enter the number of the printer which is to be switched on and press the >Select< function key. Enter the number of the desired function (2 = Switching on) or select the menu options >Switching on<...
  • Page 107: Display Of The Event Memory

    Fire Alarm Control Panel IQ8Control C / M 10.8 Display of the event memory At the installer level, the event memory of the Fire Alarm Control Panel can be shown on the display by pressing the >Event mem< key. The last 200 events, such as alarms, malfunctions, switch-offs and operating authorisations are stored in the event memory in chronological order.
  • Page 108: Diagnostic Display

    Fire Alarm Control Panel IQ8Control C / M Diagnostic display 11.1 Diagnostic display IQ8Control C/M The diagnostic display enables, e.g. a fast check of the power supply values of this FACP Panel IQ8Control C/M for service and maintenance work. In the panel display, a diagnostic field with individual measured values (analog measurement channels) which are automatically determined by the control panel is displayed.
  • Page 109: The Essernet ® Diagnostic Line

    Fire Alarm Control Panel IQ8Control C / M ® 11.2 The essernet diagnostic line ® The essernet connection of the various units in the network can be checked with this diagnostic line. The essernet ® diagnostic line (L:xxx) indicates which connections are functioning correctly (standard operation) and which have malfunctioned.
  • Page 110 Fire Alarm Control Panel IQ8Control C / M Example of essernet ® diagnostic line with four Fire Alarm Control Panels In the illustrated example, four Fire Alarm Control Panels are interconnected in the essernet ® Panel No. 1 Panel No. 4 Panel No.
  • Page 111: Checking The Essernet ® Devices And Connections

    Fire Alarm Control Panel IQ8Control C / M 11.3 Checking the essernet ® devices and connections An additional check of the essernet ® devices/connections can be carried out using the essernet ® micro modules (Part No. 784840.10 / 784841.10 - from index “E” onwards). Switching on the display on the fire alarm control panel: Test Test...
  • Page 112: Display Of The Analogue Values

    Fire Alarm Control Panel IQ8Control C / M 11.4 Display of the analogue values For service and maintenance work, the current analogue values for all micro modules and components of the device module can be displayed to check the FACP. The following tables show the individual micro modules, each with the valid range of analogue values.
  • Page 113 Fire Alarm Control Panel IQ8Control C / M * 3 relay module/3 relay module CF Normal value range FACP Analog channel Function IQ8Control Ana 1 Relay 1 93 ... 141 Ana 2 Relay 2 93 ... 141 Ana 3 Relay 3 93 ...
  • Page 114 Fire Alarm Control Panel IQ8Control C / M * Master box, internal (device module) Normal value range FACP Analog channel Function IQ8Control Ana 1 Monitoring input, master box (K1) 14 ... 185 Ana 2 Not occupied Ana 3 Not occupied Ana 4 Not occupied Ana 5...
  • Page 115: Meaning Of The Three Digit Error Codes / Test Mode

    Fire Alarm Control Panel IQ8Control C / M Meaning of the three digit error codes / test mode A three digit error code is displayed in the display in case of a failure of an intelligent fire detector. The meanings of these codes and measures for correcting the error condition are given in the following table.
  • Page 116 Fire Alarm Control Panel IQ8Control C / M Trouble Possible cause 1st. measure 2nd. measure Code No. Check the installed detector if the surrounding area is humid. Use protective Clean detector and check it with measures if necessary, e.g. programming software tools Detector is soiled or damp.
  • Page 117 Fire Alarm Control Panel IQ8Control C / M Trouble 2nd. measure Possible cause 1st. measure Code No. Fault occurs while loop is being switched on: switch off loop and switch back on again after 1-2 minutes. Fault occurs while switching the Take any necessary base output: Detector unable to correctly...
  • Page 118 Fire Alarm Control Panel IQ8Control C / M Trouble Possible cause 1st. measure 2nd. measure Code No. Communication between  esserbus transponder and Notify Customer Service. FACP  disturbed for 100 seconds. With 10 kOhm terminating With EOL-O end-of-line: ® Monitoring of the esserbus resistance: The set monitoring current does...
  • Page 119 Fire Alarm Control Panel IQ8Control C / M Trouble Possible Cause 1st. measure 2nd. measure Code No. If this change is not desired, If this change is not desired, There are more detectors on the connect service PC and run connect service PC and run a loop than programmed in the a wiring recognition.
  • Page 120 Fire Alarm Control Panel IQ8Control C / M Trouble Possible Cause 1st. measure 2nd. measure Code No. Detector circuitry has been Check whether this detector Otherwise install detector changed at detector location. location is to have an external you require and re-start Now detector has external circuit.
  • Page 121: Trouble Messages In The Display

    Fire Alarm Control Panel IQ8Control C / M 12.1 Trouble messages in the display Up to three works-programmed trouble messages with 8 characters each can be displayed in the second line of the display. If a clear text trouble message applying to an event is displayed, this trouble message is shown automatically in the display or can be activated with the function key >Param/AT<.
  • Page 122 Fire Alarm Control Panel IQ8Control C / M Trouble Possible cause 1st. measure 2nd. measure text An error has been detected Localise the source with when an loop was switched programming software tools start-up on; normal operation is 8000 switch on or reconfigure impossible.
  • Page 123 Fire Alarm Control Panel IQ8Control C / M Trouble Possible cause 1st. measure 2nd. measure text A dirty detector was found int. det. err Clean or replace detector. during an EDD zone test. A detector could not be reset reset Replace detector.
  • Page 124: System Overview

    Fire Alarm Control Panel IQ8Control C / M System overview The modular design with different micro modules and individual extension concepts allow the Fire Alarm Computer IQ8Control C and IQ8Control M to be easily adapted to special requirements. This provides the range from a stand-alone panel up to 31 Fire Alarm Control Panels Computer or other network subscribers such as ®...
  • Page 125: Function For Fire Alarm Control Panels

    Fire Alarm Control Panel IQ8Control C / M Function for fire alarm control panels The fire alarm control panel can be programmed to activate door control systems by installing an door control transponder. The esserbus ® door control transponder is operated as a bus device on the loop of the FACP. The corresponding detector zones for activating the door controls are programmed in the panel’s customer data.
  • Page 126: Iq8Wireless

    Fire Alarm Control Panel IQ8Control C / M IQ8Wireless The IQ8Wireless wireless components enable wireless connection of fire detectors and/or acoustic and optical alarm signalling units and can be used either as part of the FACP loop or as a stand-alone wireless control facility in fire alarm control systems with conventional detector zones.
  • Page 127: Important Battery Information

    Fire Alarm Control Panel IQ8Control C / M Important battery information Battery information relating to power consumption and batteries (Art. No. 805597) for use in IQ8Wireless RF components  Insert batteries into the RF devices shortly before initial operation (assigned to the RF transponders)! Unassigned RF devices consume approx.
  • Page 128: Top Hat Rail Mounting Kit (Part No. 788652)

    Fire Alarm Control Panel IQ8Control C / M Top hat rail mounting kit (Part No. 788652) In the FACP IQ8Control C / M can be installed a top hat rail mounting kit (optional). This mounting kit comprises of a mounting base, a standard 35 mm top hat rail (C-profile mounting), M5 x 30 bolts, M5 x 50 screws and insert nuts.
  • Page 129: Esserbus ® Transponder

    Fire Alarm Control Panel IQ8Control C / M esserbus ® transponder ® esserbus transponders are input/output modules for extending the control panel inputs/outputs. It is possible to install up to 32 esserbus ® transponders in separate detector zones (separated by zone isolators). Mixing the operation of fire detectors and esserbus ®...
  • Page 130: Extension Housing

    Fire Alarm Control Panel IQ8Control C / M Extension housing Four different extension housings and an additional Mounting plate are available for individual extension of the FACP IQ8Control C/M. Part No. Description 789300 Extension housing for batteries Housing complete with battery rear panel, space for two rechargeable batteries with an individual capacity of 12 V / 24 Ah.
  • Page 131: Extension Housing For Two Batteries (Part No. 789300 / -01)

    Fire Alarm Control Panel IQ8Control C / M The extension housing is assembled / mounted similar to the central housing. The individual assembly steps are described in the section "Assembling the central housing". The following must also be observed when assembling the extension housing: ...
  • Page 132: Power Supply For The Built-In Printer

    Fire Alarm Control Panel IQ8Control C / M Power supply for the built-in printer The internal power supply of the built-in printer is provided by the basic module terminals of the FACP. +UBext. +UBext. +UBext T2A +UBext T2A Printer Printer +UBext.
  • Page 133: Mounting / Replacing Of The Panel Front + Printer

    Fire Alarm Control Panel IQ8Control C / M Mounting / Replacing of the Panel front + Printer 21.1 Heat transfer Printer without paper take-up unit (Part No. 7868xx) Panel front for heat transfer Printer without paper take-up unit. Language identification, e.g. 00=German, 01=English etc. (refer to catalogue Fire Alarm systems) Damage to the system Fig.
  • Page 134 Fire Alarm Control Panel IQ8Control C / M Wiring FACP IQ8Control with Panel front (Part No. 7868xx) X23 Printer Basic module +UBext. +UBext T2A Printer switched +12 V ext. Ribbon cable Fig. 116: Wiring Printer Ribbon cable, length 50 cm (Part No. 750756) / Ribbon cable, length 120 cm (Part No. 750757) Observe permitted torque (max.
  • Page 135: Printer With Paper Take-Up Reel (Part No. 7863Xx)

    Fire Alarm Control Panel IQ8Control C / M 21.2 Printer with paper take-up reel (Part No. 7863xx) Panel front with heat transfer printer with paper take-up reel. Panel front for heat transfer printer with paper take-up reel (Part No. 7863xx) and printer kit for IQ8Control C / M (Part No. 784792) Language identification, e.g.
  • Page 136 Fire Alarm Control Panel IQ8Control C / M Wiring FACP IQ8Control Basic module IQ8 Control X23 Printer +UBext. +UBext T2A Printer switched +12 V ext. Ribbon cable Fig. 121: Wiring Printer with paper take-up reel Observe permitted torque (max. 0.4 Nm) of the terminals! Customer data programming with tools 8000 The printer must be programmed with the tools 8000 programming software from V1.15 or higher as a >Printer with take up reel for Serial 2<...
  • Page 137: Fire Protection Housing F30

    Fire Alarm Control Panel IQ8Control C / M Fire protection housing F30 The fire protection housing provides the installation of Fire Alarm Control Panels IQ8Control in accordance to the German MLAR and LAR requirements within corresponding ambient conditions. Cabling of fire protection equipment must remain in operation at least for 30 minutes to meet the Fire resistance rating standard F30 for: ...
  • Page 138 Novar GmbH a Honeywell Company Dieselstraße 2 41469 Neuss, Germany G 205129 Telefon: +49 2131 40615-600 Telefax: +49 2131 40615-606 Internet: www.esser-systems.com Technical changes reserved! E-Mail: [email protected] © 2015 Honeywell International Inc.

This manual is also suitable for:

Esser iq8control m

Table of Contents