Command Builds

COMMAND
BUILD
MASTER
SECTOR
CHANNEL
Integral
sounder
TIME
BLOCK
I / O INTERFACE
INPUT LINE
SECTOR
That has just
come into fire
Sound
Sound
Silence
Reset
NONE
(CLEAR)
ZONE
DIFFERENT
TASK
MENU
FROM ANOTHER ZONE
"
Where possible use sectored action instead of
command build action.
¨
There can be up to 255 command builds per panel.
¨
a command build can only be set up with one trigger
(can be a range)
¨
a command build can be triggered:
for reversible action (automatic deaction on
removal of trigger)
or non-reversible action, (deactioned by another
command build for a non-fire trigger or reset for a
fire Trigger).
¨
the command build trigger for zone tasks reside under
the zone menu.
¨
command builds that are triggered through a sector fire
event will deaction on fire reset. This is independent of
whether the sector is configured to deaction on silence
alarms.
¨
command builds that are configured for turn Off
actions have no reverse action to turn On again,
another command build or manual action is required.
¨
command builds can be used under fire and non fire
conditions to carry out pre-configured actions built up
from the Control menu.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
ACTION (INPUT)
COMMAND BUILD FUNCTIONS
TRIGGER
TRIGGER
1 TO 255
TRIGGER
COMMAND
BUILD
TRIGGER
TRIGGER
'LABEL' OR NUMBER
ASSIGN
UP TO 40 CHARACTERS
ASSIGN
ASSIGN
TRIGGER
ACTION
TRIGGER
NOTE: Normally the
build reverse actions
is selected.
Vigilon (EN & BS) Compact (VA) panels
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
ACTION
ACTION
REV OR NOT-REV
ACTION
ACTION
REV OR NOT-REV
ACTION
ACTION
REV OR NOT-REV
ACTION
ACTION
REV OR NOT-REV
ACTION
ACTION
REV OR NOT-REV
ACTION
ACTION
REV OR NOT-REV
ACTION
ACTION
ACTION
ACTION
REV OR NOT-REV
ACTION
ACTION
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
¨
a command build can only be set up to perform one
action (can be a range), any split range would require a
second command build.
¨
each command build can be given a 40 character label
to be displayed and/or printed when triggered. If no
label is given then nothing will be displayed
¨
if a label is given, the local buzzer will operate for 1
minute when the command build is active.
¨
command builds are logged with an On/Off time, this
information can be viewed by selecting [info] ->
[Event]-> [Supervis]-> [Log] and if still On via
[Info]-> [Event]-> [Supervis]-> [Active], this is only
possible if a label has been given to the Command
Build
¨
when speed of operation is required the lowest number
command builds should be used as these are processed
first
¨
if a digital output line is to be actioned by a command
build, the I/O line should not be assigned to a sector as
it may deaction when the silence alarms is pressed
regardless of the command build still being active
¨
a fire condition takes priority over a command build
&
Take great care not to action a digital
output to an input line, as this will effectively disable
the input.
NOT-REVERSIBLE
REVERSIBLE
START MASTER ALARM
1ST
STOP MASTER ALARMS
NO ACTION
(CLEAR)
ENABLE
DISABLE
SECTOR
MASTER SECTOR
AUX RELAY
PRINTER
2ND
DIGITAL
TIME SLOT OVERRIDE
DELAY 0 TO 24 HOURS
DELAY BLOCK
PAUSE SOUNDERS
DELAY 0 TO 30 SEC
LOCAL BUILD
SOUNDER
INTEGRAL
SOUNDER IN OHS
SOUND
SILENCE
RESET
VERIFY
TONE/ MESSAGE
AUX MESSAGE
ALARM MESSAGE
123