Appendix D - Guidelines For Networked System Commands; Master Sectors - Honeywell Gent Viglion EN54 Generic Commissioning Instructions

For the fire alarm systems
Table of Contents
Generic Commissioning instructions
Appendix D - Guidelines for Networked system
commands
These functions apply to networked systems. See also guidelines for standalone system.
"
For information on Command build actions across a network, see Appendix C.
When commissioning a network of control panels, ensure the software version is same across all the panels. This is
also applicable when an existing network is to be installed with additional panels.

Master Sectors

MASTER SECTOR FUNCTIONS
PANEL 1
ASSIGN
SECTOR
that has
just gone
into fire
ASSIGN
SECTOR
that has
just gone
into fire
COMMAND
ACTION
BUILD
¨
There can be up to a maximum of 64 Master Sectors per panel
¨
a total of 255 master sectors per network system
¨
they are therefore a collection of:
Sectors
Delayblocks
Master Alarms
and Aux Relays from one or more Systems.
¨
they provide global alarm actions across a network of control panels
128
NETWORK
MASTER
SECTOR 1
255 PER
NETWORK
64 PER
PANEL
SIGNAL
1
SIGNAL
2
SIGNAL
3
ALL
SIGNALS
OFF
MASTER
SECTOR 2
SIGNAL
1
SIGNAL
2
SIGNAL
3
ALL
SIGNALS
OFF
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
PANEL 2
ASSIGN
SECTOR
ASSIGN
DELAY
BLOCK
ASSIGN
MASTER
ALARM
ASSIGN
AUX
RELAY
ASSIGN
COMMAND
BUILD
SECTOR
ASSIGN
COMMAND
BUILD
TRIGGER
Table of Contents
loading

This manual is also suitable for:

Gent viglion compact voice alarmGent viglion compactGent viglion bs

Table of Contents