S 3 Mark I - Honeywell Gent Viglion EN54 Generic Commissioning Instructions

For the fire alarm systems
Table of Contents
3
S
Mark I
An S
3
device can operate in Tone or Voice mode, dependent on type.
All S
3
in a system can share a common volume setting from a range between 16% to 100% sound output.
All S
3
in a system can share a common soft start facility, if set the sound output will increment the volume every 0.25s from a defined
start level to maximum output.
Setting selectable using the commissioning tool:
S
3
operating in tone mode allows selection from a range of low and high frequency tones that are outputted according to FAB/SAB
settings, see sounders configurations section.
S
3
set for Voice mode operation allows selection from a range of tones and messages that span over 10 seconds duration. The
tones and messages are those held in respective S
The Speech only S
Voice
provides voice message
with tone output.
The Sounder S provides
Sounder
sound output over a duration
as defined by the FAB/SAB
held at the control panel
Strobe
3
The Strobe S output is
defined by what signal
is being actioned on the S .
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
3
device.
Standard Tone
Tone 1
Tone 2
"
"
Tone 15
3
Message 1
Message 2
"
"
Message 7
Standard Tone
3
Tone 1
Tone 2
"
"
Tone 15
Standard Tone
Tone 1
Tone 2
"
"
Tone 7
3
Vigilon (EN & BS) Compact (VA) panels
10 seconds period
Attention tone
Std tone or Tone n
Tone + Message
Tone only
The sequence repeated until Sounder is silenced
FAB/SAB is output, see Sounders
configuration held at the control panel
If actioned:
Signal 1 will provide strobe output at 0.5Hz
Signals 2 or Signal 3 will provide strobe output at 1Hz.
Speech Message
Message
Tone