3.2.7 Suitable mounting position

To minimize signal interference observe the minimum distances in Table 3-14. Examples
of obstacles to avoid are protruding welds, internal installations, agitators, pipes and
nozzles extending into the container, heating coils, inlet streams, ladders, etc. Metallic
objects are a source of bigger interferences than non-metallic objects.
Turbulent applications may require the probe to be anchored to prevent it from contacting
or getting too close to container walls or obstacles.

Table 3-14: Minimum recommended distance to container wall and obstacles (mm)

Probe
Single wire
Single rod
Coax
Page 58

Figure 3-19: Mounting position

Minimum
distance to
obstacle
500mm (20")
100mm
500mm (20")
100mm
0mm (0")
0mm (0")
SLG 700 SmartLine Level Transmitter User's Manual
Minimum distance to
metallic container
wall
(4")
(4")
Minimum distance
to non-metallic
container wall
500mm (20")
500mm (20")
0mm (0")