Installation Consideration
EN 61000-4-5 (IEC 61000-4-5): Surge transients:
Simulation of transients brought about, e.g., by
lightning that strikes near installations.
EN 61000-4-6 (IEC 61000-4-6): RF Common mode:
Simulation of the effect from radio-transmission
equipment joined by connection cables.
Voltage range: 200–240 V, 380–480 V
Basic standard
Acceptance criterion
Line
Motor
Brake
Load sharing
Control wires
Standard bus
7
7
Relay wires
Application and network
options
Keypad cable
External 24 V DC
Enclosure
AD: Air Discharge
CD: Contact Discharge
CM: Common mode
DM: Differential mode
1. Injection on cable shield.
Table 7.4 EMC Immunity Form
7.2.1 Immunity Requirements
The immunity requirements for adjustable frequency drives
depend on the environment where they are installed. The
requirements for the industrial environment are higher
than the requirements for the home and office
environment. All GE adjustable frequency drives comply
with the requirements for the industrial environment and
consequently comply also with the lower requirements for
home and office environment with a large safety margin.
In order to document immunity against electrical
interference from electrical phenomena, the following
immunity tests have been made on a system consisting of
an adjustable frequency drive (with options if relevant), a
shielded control cable and a control box with potenti-
ometer, motor cable and motor.
7-4
AF-600 FP Design and Installation Guide
Electrical
Surge
interference
IEC 61000-4-5
IEC 61000-4-4
B
B
2 kV/2 Ω DM
4 kV CM
4 kV/12 Ω CM
1)
4 kV CM
4 kV/2 Ω
1)
4 kV CM
4 kV/2 Ω
1)
4 kV CM
4 kV/2 Ω
1)
2 kV CM
2 kV/2 Ω
2 kV CM
1)
2 kV/2 Ω
1)
2 kV CM
2 kV/2 Ω
2 kV CM
1)
2 kV/2 Ω
1)
2 kV CM
2 kV/2 Ω
0.5 kV/2 Ω DM
2 kV CM
1 kV/12 Ω CM
See Table 7.4.
ESD
Radiated electromagnetic
IEC
61000-4-2
IEC 61000-4-3
B
8 kV AD
10 V/m
6 kV CD
The tests were performed in accordance with the following
basic standards:
EN 61000-4-2 (IEC 61000-4-2): Electrostatic
discharges (ESD): Simulation of electrostatic
discharges from human beings.
EN 61000-4-3 (IEC 61000-4-3): Incoming electro-
magnetic field radiation, amplitude modulated
simulation of the effects of radar and radio
communication equipment as well as mobile
communications equipment.
EN 61000-4-4 (IEC 61000-4-4): Electrical
interference: Simulation of interference brought
about by switching a contactor, relay or similar
devices.
DET-768A
RF common
field
mode voltage
IEC 61000-4-6
A
A
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
Table of Contents