Specifications
Control card, 10 V DC output
Terminal number
Output voltage
Max. load
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control characteristics
Resolution of output frequency at 0–1000 Hz
System response time (terminals 18, 19, 27, 29, 32, 33)
Speed control range (open-loop)
Speed accuracy (open-loop)
All control characteristics are based on a 4-pole asynchronous motor
Surroundings
Enclosure, frame size 4X and 5X
Enclosure, frame size 6X
Vibration test
Relative humidity
Aggressive environment (IEC 60068-2-43) H
Test method according to IEC 60068-2-43 H2S (10 days)
- with derating
- with full output power, typical EFF2 motors
- at full continuous drive output current
1)
For more information on derating see the AF-600 FP, section on Special Conditions.
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
Derating for high altitude, see section on special conditions in the Design Guide
EMC standards, Emission
EMC standards, Immunity
See section on special conditions in the Design Guide!
Control card performance
Scan interval
Control card, USB serial communication
USB standard
USB plug
CAUTION
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from ground protection. Use only isolated laptop/PC as connection to the
USB connector on the adjustable frequency drive or an isolated USB cable/drive.
AF-600 FP Design and Installation Guide
5%–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
S test
2
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
DET-768A
1:100 of synchronous speed
30-4,000 rpm: Maximum error of ±8 rpm
-13°–149°/158° F [-25°–+65°/70°C]
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2,
USB type B "device" plug
50
10.5 V ±0.5 V
25 mA
±0.003 Hz
≤ 2 ms
IP00, IP21, IP54
IP21, IP54
0.7 g
class kD
1)
max. 131° F [55°C]
1)
max. 122° F [50°C]
1)
max. 113° F [45°C]
32° F [0°C]
14° F [-10°C]
3,300 ft [1,000 m]
10,000 ft [3,000 m]
12
5 ms
1.1 (Full speed)
12-15
12
Table of Contents