7.1.2 Emission Requirements
According to the EMC product standard for adjustable
speed adjustable frequency drives EN/IEC61800-3:2004, the
EMC requirements depend on the intended use of the
Category
Definition
C1
adjustable frequency drives installed in the first environment (home and office)
with a supply voltage less than 1000 V.
C2
adjustable frequency drives installed in the first environment (home and office)
with a supply voltage of less than 1000 V, which are neither plug-in nor movable
and are intended to be installed and commissioned by a professional.
C3
adjustable frequency drives installed in the second environment (industrial) with a
supply voltage lower than 1000 V.
C4
Adjustable frequency drives installed in the second environment with a supply
voltage equal to or above 1000 V or rated current equal to or above 400 A or
intended for use in complex systems.
7
7
Table 7.1
When the generic emission standards are used the
adjustable frequency drives are required to comply with
the following limits:
Environment
First environment
(home and office)
Second environment
(industrial environment)
Table 7.2
7-2
AF-600 FP Design and Installation Guide
Generic standard
EN/IEC61000-6-3 Emission standard for residential, commercial and
light industrial environments.
EN/IEC61000-6-4 Emission standard for industrial environments.
adjustable frequency drive. Four categories are defined in
the EMC product standard. The definitions of the four
categories together with the requirements for line power
supply voltage-conducted emissions are given in the table
below:
according to the limits given in EN55011
DET-768A
Conducted emission requirement
according to the limits given in
EN55011
Class B
Class A Group 1
Class A Group 2
No limit line.
An EMC plan should be made.
Conducted emission requirement
Class B
Class A Group 1