GE AF-600 FP Design And Installation Manual page 126

Fan & pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents
Specifications
AF-600
Bussmann
[kW]/[HP]
Type RK1
0.75/1
KTS-R-5
1.5–2.2/2–3
KTS-R-10
3.7/5
KTS-R20
5.5/7.5
KTS-R-25
7.5/10
KTS-R-30
11–15/15–20
KTS-R-35
18.5/25
KTS-R-45
22/30
KTS-R-50
30/40
KTS-R-60
37/50
KTS-R-80
45/60
KTS-R-100
55/75
KTS-R-125
75/100
KTS-R-150
90/125
KTS-R-175
Table 12.18 525–600 V, 125 HP and below
AF-600
SIBA
[kW]/[HP]
Type RK1
0.75/1
5017906-005
1.5–2.2/2–3
5017906-010
3.7/5
5017906-020
5.5/7.5
5017906-025
7.5/10
5017906-030
11–15/15–20
5014006-040
18.5/25
5014006-050
22/30
5014006-050
30/40
5014006-063
37/50
5014006-080
45/60
5014006-100
55/75
2028220-125
75/100
2028220-150
90/125
2028220-200
Table 12.19 525–600 V, 125 HP and below
1) 170M fuses shown from Bussmann use the -/80 visual indicator. –TN/80 Type T, -/110 or TN/110 Type T indicator
fuses of the same size and amperage may be substituted.
AF-600 FP Design and Installation Guide
Recommended max. fuse
Bussmann
Bussmann
Type J
Type T
JKS-5
JJS-6
JKS-10
JJS-10
JKS-20
JJS-20
JKS-25
JJS-25
JKS-30
JJS-30
JKS-35
JJS-35
JKS-45
JJS-45
JKS-50
JJS-50
JKS-60
JJS-60
JKS-80
JJS-80
JKS-100
JJS-100
JKS-125
JJS-125
JKS-150
JJS-150
JKS-175
JJS-175
Recommended max. fuse
Littel fuse
Type RK1
KLS-R-005
KLS-R-010
KLS-R-020
KLS-R-025
KLS-R-030
KLS-R-035
KLS-R-045
KLS-R-050
KLS-R-060
KLS-R-075
KLS-R-100
KLS-R-125
KLS-R-150
KLS-R-175
DET-768A
Bussmann
Bussmann
Type CC
Type CC
FNQ-R-5
KTK-R-5
FNQ-R-10
KTK-R-10
FNQ-R-20
KTK-R-20
FNQ-R-25
KTK-R-25
FNQ-R-30
KTK-R-30
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Ferraz-
Shawmut
Type RK1
A6K-5-R
A6K-10-R
A6K-20-R
A6K-25-R
A6K-30-R
A6K-35-R
A6K-45-R
A6K-50-R
A6K-60-R
A6K-80-R
A6K-100-R
A6K-125-R
A6K-150-R
A6K-175-R
Bussmann
Type CC
LP-CC-5
LP-CC-10
LP-CC-20
LP-CC-25
LP-CC-30
-
-
-
-
-
-
-
-
-
Ferraz-
Shawmut
Type J
HSJ-6
HSJ-10
HSJ-20
HSJ-25
HSJ-30
HSJ-35
HSJ-45
HSJ-50
HSJ-60
12
HSJ-80
HSJ-100
HSJ-125
HSJ-150
HSJ-175
12-23
12
Table of Contents
loading

Table of Contents