GE AF-600 FP Design And Installation Manual page 125

Fan & pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents
Specifications
AF-600 1-phase AF-600 3-phase
[kW]/[HP]
7.5/10
11/15
18.5/25
37/50
Table 12.16 380–480 V, 125 HP and below
AF-600 1-phase
[kW]/[HP]
7.5/10
11/15
2
12
18.5/25
37/50
Table 12.17 380–480 V, 125 HP and below
1) Ferraz-Shawmut A50QS fuses may substitute for A50P fuses.
12-22
AF-600 FP Design and Installation Guide
SIBA
[kW]/[HP]
Type RK1
0.75/1
5017906-006
1.5–2.2/2–3
5017906-010
3.7/5
5017906-020
5.5/7.5
5017906-025
7.5/10
5012406-032
11–15/15–20
5014006-040
18.5/25
5014006-050
22/30
5014006-063
30/40
2028220-100
37/50
2028220-125
45/60
2028220-125
55/75
2028220-160
75/100
2028220-200
90/125
2028220-250
AF-600 3-phase
Bussmann
[kW]/[HP]
Type JFHR2
0.75/1
FWH-6
1.5–2.2/2–3
FWH-10
3.7/5
FWH-20
5.5/7.5
FWH-25
7.5/10
FWH-30
11–15/15–20
FWH-40
18.5/25
FWH-50
22/30
FWH-60
30/40
FWH-80
37/50
FWH-100
45/60
FWH-125
55/75
FWH-150
75/100
FWH-200
90/125
FWH-250
Recommended max. fuse
Littel fuse
Type RK1
KLS-R-6
KLS-R-10
KLS-R-20
KLS-R-25
KLS-R-30
KLS-R-40
KLS-R-50
KLS-R-60
KLS-R-80
KLS-R-100
KLS-R-125
KLS-R-150
KLS-R-200
KLS-R-250
Recommended max. fuse
Ferraz-Shawmut
Type J
HSJ-6
HSJ-10
HSJ-20
HSJ-25
HSJ-30
HSJ-40
HSJ-50
HSJ-60
HSJ-80
HSJ-100
HSJ-125
HSJ-150
HSJ-200
HSJ-250
DET-768A
Ferraz-
Ferraz-
Shawmut
Shawmut
Type CC
Type RK1
ATM-R-6
A6K-10-6
ATM-R-10
A6K-10-R
ATM-R-20
A6K-20-R
ATM-R-25
A6K-25-R
ATM-R-30
A6K-30-R
-
A6K-40-R
-
A6K-50-R
-
A6K-60-R
-
A6K-80-R
-
A6K-100-R
-
A6K-125-R
-
A6K-150-R
-
A6K-200-R
-
A6K-250-R
Ferraz-Shawmut
Littel fuse
1)
Type JFHR2
Type JFHR2
-
-
-
-
-
-
-
-
-
-
-
-
A50-P-225
L50-S-225
A50-P-250
L50-S-250
-
-
-
-
-
-
-
-
-
-
-
-
Table of Contents
loading

Table of Contents