About Programming
3.
F-53 Maximum Reference. Set maximum internal
adjustable frequency drive reference to 50 Hz.
(This sets the maximum adjustable frequency
drive speed at 60 Hz. Note that 50 Hz is a
regional variation.)
5
5
Figure 5.3
4.
AN-10 Terminal 53 Low Voltage. Set minimum
external voltage reference on Terminal 53 at 0 V.
(This sets the minimum input signal at 0 V.)
Figure 5.4
5-2
AF-600 FP Design and Installation Guide
5.
Figure 5.5
6.
Figure 5.6
DET-768A
AN-11 Terminal 53 High Voltage. Set maximum
external voltage reference on Terminal 53 at 10 V.
(This sets the maximum input signal at 10 V.)
AN-14 Terminal 53 Low Ref./Feedb. Value. Set
minimum speed reference on Terminal 53 at 20
Hz. (This tells the adjustable frequency drive that
the minimum voltage received on Terminal 53 (0
V) equals 20 Hz output.)