Installation Recommendations - Emerson Rosemount 2160 Quick Start Manual

Wireless vibrating fork level switch
Hide thumbs Also See for Rosemount 2160:
Table of Contents
June 2016
Mount the switch so that the battery side is accessible.
Clearance of 2
On the circuit side of the electronics housing, provide 0.75 in. (19 mm) of
clearance for units without an LCD display. Three inches of clearance is
required for cover removal if an LCD display is installed.
The housing can be rotated for optimal viewing of the optional LCD display
and to get the best antenna position (see
page
5).
Always ensure a proper seal by installing the electronics housing cover(s) so
that metal contacts metal. Use Rosemount O-rings.
Always ground the housing in accordance with national and local electrical
codes. The most effective grounding method for the housing is a direct
connection to earth ground with minimal impedance.

2.2 Installation recommendations

Avoid installing near liquid entering the tank at the fill point.
Avoid heavy splashing on the forks.
Avoid installing near heat sources.
Ensure the fork does not come into contact with a tank/pipe wall or fittings.
Allow a distance between product build-up and level switch fork
Figure 4. Avoid Product Build-up
OK
2.3 Housing rotation (optional)
1. Loosen the housing rotation set screw
2. First rotate the housing clockwise to the desired location. If the desired
location cannot be achieved due to the thread limit (up to 360°), rotate the
housing counter-clockwise to the desired location. Do not over twist.
3. Re-tighten the housing rotation set screw.
3
/
in. (60 mm) is required for cover removal.
8
"Housing rotation (optional)" on
(Figure 5 on page
6).