Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
Information in menu The following information will be available in the About - Modules menu if Ekip Touch has detected the
234 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
is available in the Settings menu (page 49).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings - Modules menu:
Parameter
Static IP address ON
Static address IP address
Static Network Mask
Static Gateway address
Enable SNTP client
SNTP Server Addr.
Configuration Session
Start Configuration
module correctly:
Information
Description
SN and version
Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the
time of connection to the network in the case of configuration with a
IP address
dynamic IP, or can be set via the menu in the event of a static IP
Subnet mask; identifies the method for recognizing the subnet to which
Network Mask
the modules belong and enables modules to be searched for within a
defined set of recipients.
IP address of the node to which the module is connected, in the presence
Gateway address
of several subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier)
MAC address
equal to ac:d3:64, which uniquely identifies the manufacturer of an
Ethernet device
Cfg file
Name of the configuration file uploaded to the modules
Cfg file error
Code of the error concerning the configuration file (0 = no error)
Description
Defines whether the module has the dynamic (Off) or
static (On) IP address.
Se = On all the associated parameters are enabled
Enables the static IP to be selected
Enables the subnet mask to be selected
When there are several subnets, enables the IP
address of the node to which the module is connected
to be selected
Allows the SNTP protocol for distribution of the clock
and synchronization signal to be enabled.
Allows the network server that supplies the SNTP to
be set.
Defines the write mode of the configuration file in the
module via the TFTP port; two options are available:
• Always ON: the TFTP port is always open and write
is always enabled
• Activation requested: the TFTP is opened by a
specific command, which enables write for a limited
time (or for a finite number of data packages)
Write enable command on TFTP port in Activation
mode requested
NOTE: without a DHCP server, the module automatically adopts a
random IP address within the 169.254.xxx.xxx range
ABB | SACE Emax 2
Default
OFF
0.0.0.0
0.0.0.0
0.0.0.0
OFF
0.0.0.0
Always
ON
---
External electronic accessories
8 - Ekip Com IEC 61850