ABB Ekip Touch Operating Instructions Manual

Protection settings setup for touch trip units
O P E R AT I N G I N S T R U C T I O N S
Protection settings setup for
Ekip Touch Trip Units
loading

Summary of Contents for ABB Ekip Touch

  • Page 1 — O P E R AT I N G I N S T R U C T I O N S Protection settings setup for Ekip Touch Trip Units...
  • Page 3: Table Of Contents

    — Table of contents Index of terms & settings table Default protection settings 006– 040 Protection Setting Setup 006 – 025 XT5, XT7/XT7M and Emax 2 026 – 040 XT2 and XT4 041 – 052 Arc flash mitigation / RELT / 2I Protection setup 053 –...
  • Page 4 E K I P T O U C H T R I P U N I T S — Index of terms / Field setting sheet Traditional/Study ABB Ekip Touch Reference Reference Long Time Protection L Protection Overload (49) – Threshold I1 – t1 Short Time Protection S Protection Selective Short Circuit (51/50TD) –...
  • Page 5 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S —...
  • Page 6: Protection Setting Setup

    Ekip Programming*: ZEAEKPPGM (1SDA076154R1) *Powered via USB port on laptop/computer — Ekip TT Step 1. Insert the Ekip TT Plug End (B) into Ekip Touch Trip Unit Service Connector (G) a. Power LED e. Single-touch color touchscreen display b. Warning LED f.
  • Page 7 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 2.
  • Page 8 E K I P T O U C H T R I P U N I T S Step 5. Press the upper left icon - Protections Icon A DJ U S T I N G T H E L O N G T I M E P R O T E C T I O N S E T T I N G S —...
  • Page 9 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 7.
  • Page 10 E K I P T O U C H T R I P U N I T S A DJ U S T I N G T H E L O N G T I M E P I C K U P O R T H R E S D H O L D I 1 Step 9.
  • Page 11 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 11.
  • Page 12 E K I P T O U C H T R I P U N I T S A DJ U S T I N G T H E S H O R T T I M E P R O T E C T I O N S E T T I N G S The default setting for Short Time Protection is OFF or ENABLE = OFF —...
  • Page 13 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 15.
  • Page 14 E K I P T O U C H T R I P U N I T S Step 17. Press the Function per the coordination study A DJ U S T I N G T H E S H O R T T I M E P I C K U P O R T H R E S H O L D I 2 Step 18.
  • Page 15 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 19.
  • Page 16 E K I P T O U C H T R I P U N I T S Step 21. Change the Short Time Delay / Time t2 setting to the value in the coordination study. The setting range is from 0.05 to 0.8 Seconds (UL versions: t2 Max = 0.4s) Press the minus icon or the plus icon to change to the value in the coordination study (maintaining the press will advance the settings faster).
  • Page 17 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S A DJ U S T I N G T H E I N S TA N TA N E O U S P R O T E C T I O N S E T T I N G S —...
  • Page 18 E K I P T O U C H T R I P U N I T S Step 25. Change the Instantaneous Pickup / Threshold I3 setting to the value in the coordination study. The setting range is from 1.5 to 15.0 of the breaker’s nominal rating (rating plug value) Press the minus icon or the plus icon to change to the value in the coordination study (maintaining the press will advance the settings faster).
  • Page 19 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S A DJ U S T I N G T H E G R O U N D FA U LT P R O T E C T I O N S E T T I N G S The default setting for Ground Fault Protection is OFF or ENABLE = OFF —...
  • Page 20 E K I P T O U C H T R I P U N I T S Step 29. Press Enable On The Ground Fault - G Protection Function is now Enabled A DJ U S T I N G T H E G R O U N D FA U LT C U R V E O R F U N C T I O N Step 30.
  • Page 21 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 31.
  • Page 22 E K I P T O U C H T R I P U N I T S Step 33. Change the Ground Fault Pickup / Threshold I4 setting to the value in the coordination study. The setting range is from 0.1 to 1.0 of the breaker’s nominal rating (rating plug value) (UL Version: I4 Max = 1200A) Press the minus icon or the plus icon to change to the value in the coordination study (maintaining the press will advance the settings faster).
  • Page 23 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 35.
  • Page 24 E K I P T O U C H T R I P U N I T S A P P LY I N G/CO N F I R M I N G A DJ U S T M E N T S T O P R O T E C T I O N S E T T I N G S At the conclusion of inputting all the settings, these new settings MUST be confirmed to be saved.
  • Page 25 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 38.
  • Page 26: Xt2 And Xt4

    Ekip Programming*: ZEAEKPPGM (1SDA076154R1) *Powered via USB port on laptop/computer — Ekip TT Step 1. Insert the Ekip TT Plug End (B) into Ekip Touch Trip Unit Service Connector (7) a. Power LED f. iTest push-button b. Warning LED g. Service Connector c.
  • Page 27 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 2.
  • Page 28 E K I P T O U C H T R I P U N I T S A DJ U S T I N G T H E L O N G T I M E P R O T E C T I O N S E T T I N G S —...
  • Page 29 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S A DJ U S T I N G T H E L O N G T I M E P I C K U P O R T H R E S H O L D I 1 Step 8.
  • Page 30 E K I P T O U C H T R I P U N I T S Step 10. Change the Long Time Delay / Time T1 to the value in the coordination study using the Up or Down buttons (10a). 10a 10b The setting range is from 3 to 144 Seconds Press the Up or Down buttons (10a) to change to the value in the coordination study.
  • Page 31 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S A DJ U S T I N G T H E S H O R T T I M E P R O T E C T I O N S E T T I N G S —...
  • Page 32 E K I P T O U C H T R I P U N I T S This screen will be displayed A DJ U S T I N G T H E S H O R T T I M E C U R V E T Y P E O R F U N C T I O N Step 15.
  • Page 33 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S A DJ U S T I N G T H E S H O R T T I M E P I C K U P O R T H R E S H O L D I 2 Step 17.
  • Page 34 E K I P T O U C H T R I P U N I T S A DJ U S T I N G T H E S H O R T T I M E D E L AY O R T I M E T 2 Step 19.
  • Page 35 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S A DJ U S T I N G T H E I N S TA N TA N E O U S P R O T E C T I O N S E T T I N G S —...
  • Page 36 E K I P T O U C H T R I P U N I T S Step 24. Change the Instantaneous Pickup / Threshold I3 setting to the value in the coordination study using the Up and Down buttons (24a) and Press the Enter button (24b). 24a 24b The setting range is from 1.5 to 15.0 of the breaker’s nominal rating (rating plug/sensor value) Press Up or Down buttons (24a) to change to the value in the coordination study.
  • Page 37 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S A DJ U S T I N G T H E G R O U N D FA U LT P R O T E C T I O N S E T T I N G S —...
  • Page 38 E K I P T O U C H T R I P U N I T S A DJ U S T I N G T H E G R O U N D FA U LT C U R V E O R F U N C T I O N Step 29.
  • Page 39 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 32.
  • Page 40 E K I P T O U C H T R I P U N I T S This completes the settings of the Ground Fault / G Protection Function. A P P LY I N G/CO N F I R M I N G T H E A DJ U S T M E N T S T O P R O T E C T I O N S S E T T I N G S At the conclusion of inputting all the settings, these new settings MUST be confirmed to saved.
  • Page 41: Arc Flash Mitigation / Relt / 2I Protection Setup

    P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S —...
  • Page 42 E K I P T O U C H T R I P U N I T S Step 3. Press the upper center icon- Advanced Icon Step 4. Press the 2I Protection Second I Protection row...
  • Page 43 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 5.
  • Page 44 E K I P T O U C H T R I P U N I T S A DJ U S T I N G T H E S E CO N D I N S TA N TA N E O U S P I C K U P O R I 3 1 Step 7.
  • Page 45 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 9.
  • Page 46 E K I P T O U C H T R I P U N I T S Step 11. Then press Confirm This display is presented The Arc Flash / RELT / 2I Advanced Protection Parameter is now Updated.
  • Page 47 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 12.
  • Page 48 E K I P T O U C H T R I P U N I T S Step 14. Press the upper center icon- Advanced Icon Step 15. Press the down arrow key until you reach the last page.
  • Page 49 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 16.
  • Page 50 E K I P T O U C H T R I P U N I T S Step 18. Select Activation Step 19. Enter password Default Password: 00001. Zero appears in the first PIN box. Press Confirm to accept zero Repeat for the next three PIN boxes On the 5 PIN box change from zero to one (press the up triangle), then press Confirm...
  • Page 51 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 20.
  • Page 52 E K I P T O U C H T R I P U N I T S Step 22. Select Confirm Step 23. 2I Mode is now active...
  • Page 53: Appendix For Changing Language Back To English

    P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S —...
  • Page 54 E K I P T O U C H T R I P U N I T S Step 3. Press the Lenguaje Espanol row Step 4. Use the up/down arrows to scroll to “English”...
  • Page 55 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 5.
  • Page 56: How To Set Date And Time

    E K I P T O U C H T R I P U N I T S — How to set date and time XT5, XT7/XT7M and Emax 2 Step 1. Press the bottom left icon (six sub-icons) Step 2. Press the lower left icon – Settings Icon...
  • Page 57 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 3.
  • Page 58 E K I P T O U C H T R I P U N I T S Step 5. This display is presented (In order to change settings, a password is required) Default Password: 00001. Zero appears in the first PIN box Press Confirm to accept zero Repeat for the next three PIN boxes On the 5th PIN box change from zero to one (press the up triangle), then press Confirm...
  • Page 59 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 7.
  • Page 60: Xt2 And Xt4

    E K I P T O U C H T R I P U N I T S — How to set date and time XT2 and XT4 Step 1. Press ESC button (1a) or Enter Button (1b) Step 2. Press Up button (2a) to select Settings icon and Press Enter button (2b). Step 3.
  • Page 61 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S Step 4.
  • Page 62 E K I P T O U C H T R I P U N I T S Step 7. Press Down button (7a) to select Time and Press Enter (7b). Step 8. Press Up or Down buttons (8a) to adjust to the current Time and Press Enter (8b). Holding the Up or Down buttons (8a) will advance the settings faster.
  • Page 63 P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S...
  • Page 64 ABB Inc. does not accept any responsibility prevail. ABB Inc. does not accept any responsibility whatsoever for potential errors or possible lack of whatsoever for potential errors or possible lack of information in this document.