ABB Ekip Touch Operating Instructions Manual page 35

Protection settings setup for touch trip units
P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S
A DJ U S T I N G T H E I N S TA N TA N E O U S P R O T E C T I O N S E T T I N G S
Factory Default Settings
Protection Function
Frame
Instantaneous Protection
XT2 & XT4
I Protection Short Circuit (50)
Range Adjustability
Protection Function
Instantaneous Protection
I Protection Short Circuit (50)
1
I3 threshold must be higher than I2 (if S Enabled = ON)
Step 22. Press Down button (22a) to select the I Protection and Press Enter (22b).
Step 23. Press Down button (23a) to select Threshold I3 and Press Enter (23b).
Function /
Enabled
Trip Enabled
Curve
ON
-
-
Frame
Threshold /Pickup Range
XT2 & XT4
1.5 x In to 15 x In; in 0.1 In steps
Threshold /
Time /
Pickup
Delay
I3 = 5.5 x In
-
1
22a 22b
23a 23b
35
Thermal
Pre-alarm
Memory
-
-
Time /Delay Range
-
loading

This manual is also suitable for:

Xt5Xt7Xt7mEmax 2Xt2Xt4