ABB SACE Tmax XT2 User Manual

ABB SACE Tmax XT2 User Manual

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents
DOC. No. 1SDH002031A1002
SACE Tmax XT2 – XT4
User manual for use and maintenance of Ekip Touch Trip units
for Tmax XT2 - XT4 low-voltage molded-case circuit breakers
ECN000092998
Rev. B
Power and productivity
for a better world
TM
Table of Contents
loading

Summary of Contents for ABB SACE Tmax XT2

  • Page 1 DOC. No. 1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 – XT4 User manual for use and maintenance of Ekip Touch Trip units for Tmax XT2 - XT4 low-voltage molded-case circuit breakers Power and productivity  for a better world...
  • Page 2: Table Of Contents

    Contents CONTENTS ............2 TEST ..............119 GLOSSARY ............3 33 - Test ..............119 INTRODUCTION ........... 4 ADDITIONAL FUNCTIONS ........121 Content ..............4 34 - Power Controller ..........121 Safety ..............5 35 - Load Shedding ..........122 EKIP TOUCH OVERVIEW ........
  • Page 3: Glossary

    Electronic unit connected to the CB, with the functions of measurement, control and protection Trip unit of the CB, following anomalous operating conditions; in the event of an alarm it triggers a TRIP Trip unit for CB SACE Tmax XT2-XT4, equipped with LCD display, available in four different Ekip Touch versions...
  • Page 4: Introduction

    All the remaining operations described in the manual must be carried out by experts in the electrical field. ABB will not be held responsible for damage to property or persons due to non- compliance with the instructions contained in this document.
  • Page 5: Safety

     These warnings and alarms do not include all modes of installation, use and maintenance recommended by ABB, or possible consequences and complications of each one, nor will ABB investigate all such modes.  Whoever is using maintenance procedures or devices, whether recommended by ABB or...
  • Page 6: Ekip Touch Overview

    Ekip Touch Overview 3 - General characteristics Families SACE Tmax XT2 - XT4 can be configured with two trip unit families:  Ekip Dip with dip-switch interface  Ekip Touch with LCD display Both families perform protection and measurement functions referring to system notifications and are available in different models and versions.
  • Page 7: Models And Versions

    Power Protections ROCOF Protections Adaptive Protections Class 1 Power & Energy Metering NOTES: package configurable if the Measuring package is present package available only when ordering the circuit breaker SACE Tmax XT2 – XT4 | 7 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 8 Voltage Protections Advanced Voltage Protections Frequency Protections Power Protections ROCOF Protections Adaptive Protections (NOTE) Class 1 Power & Energy Metering NOTE: package available only when ordering the circuit breaker SACE Tmax XT2 – XT4 | 8 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 9 Advanced Voltage Protections (NOTE) Power Protections ROCOF Protections NOTE: By default Ekip Hi-Touch has some protections from the complete package. The remaining protections in the package can be enabled upon request. SACE Tmax XT2 – XT4 | 9 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 10 By default Ekip M Touch has some protections from the complete package; the remaining protections in the package can be enabled upon request. package available only when ordering the circuit breaker SACE Tmax XT2 – XT4 | 10 1SDH002031A1002 ECN000092998...
  • Page 11: Accessories And Software

    Ekip Com Communication (various protocols) These modules can be connected to the Trip unit directly to the internal terminal board and only if is not equipped any external module. SACE Tmax XT2 – XT4 | 11 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 12 Ekip Touch functions and configurations in your system: documentation NOTE: some documents referred to in the following table refer to the SACE Emax 2 device, but can also be used with SACE Tmax XT2 - XT4 Name Code...
  • Page 13: Operating Characteristics

    IMPORTANT: if the Trip unit is connected directly the power supply must be galvanically isolated and must guarantee the insulation characteristics referred to in IEC 60950 (UL 1950) or their equivalent SACE Tmax XT2 – XT4 | 13 1SDH002031A1002 ECN000092998...
  • Page 14: Management Operations

    If not powered, connect the Ekip TT device to Ekip Touch and make sure Alarms that there are no alarms (details on page 18) Parameters Configure all unit parameters appropriately SACE Tmax XT2 – XT4 | 14 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 15 Touch input and make sure the status of Ekip touch is Input = ON. 8. Select the Release Output command on the Trip unit connected to the Ekip Touch input and make sure the status of Ekip Touch is Input = OFF. SACE Tmax XT2 – XT4 | 15 1SDH002031A1002 ECN000092998...
  • Page 16 2. Change the status of the AUP device and verify the Trip unit's correct reading removable version of the change in status using the Information-Circuit Breaker-CB Status menu of the CB SACE Tmax XT2 – XT4 | 16 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 17: Maintenance And Malfunction Identification

    Standard environments (measured dust level > 1 mg/m3) Maintenance One year or 2000 maneuvers or Six months or 1000 maneuvers or frequency after a short circuit after a short circuit SACE Tmax XT2 – XT4 | 17 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 18 (in alphabetical order): suggestions Signal Suggestions Numerical alarm Internal error. For this type of error contact ABB (e.g. 30002) Low battery Replace the battery (see kit sheet 1SDH001000R0509) CB status Incorrect CB status (example: current present but CB status open)
  • Page 19 NOTE: Check the error messages on the display before consulting the table; if the suggestions provided do not resolve the problem, contact ABB customer support, if possible providing the alert produced by the Ekip Connect software. Malfunction...
  • Page 20 No display of opening Auxiliary power supply is missing Proper operating condition data and/or battery is low SACE Tmax XT2 – XT4 | 20 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 21: Interface And Menu

    ESC button Left/Down button Enter button Power LED Warning LED Alarm LED Service connector Display The Ekip Touch's display is LCD, monochrome, and is active with the unit on. SACE Tmax XT2 – XT4 | 21 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 22 If lit and blinking at the same time, the Warning and Alarm LEDs signal the alarm caused by a hardware error inside the Trip unit. This type of alert requires the intervention of ABB. SACE Tmax XT2 – XT4 | 22...
  • Page 23 Programming, with the possibility of temporarily powering the unit, configuration of the parameters before startup, testing, extension of the configuration functions. IMPORTANT: use only cables supplied by ABB or with ABB accessories SACE Tmax XT2 – XT4 | 23 1SDH002031A1002 ECN000092998 Rev.
  • Page 24: Graphic

    Reactive power measurements page: real-time phase reactive power measurements  Total power measurements page: real-time total phase power measurements  Energy measurements page: total active, reactive, and apparent energy measurements SACE Tmax XT2 – XT4 | 24 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 25 Each message is followed by an icon that identifies the type of alarm: Icon Alarm Type Alarm Warning, error, or pre-alarm Information Timing for active protection The complete list of alarms is available on page 18. SACE Tmax XT2 – XT4 | 25 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 26: Menu

    (page 65), an intermediate menu is made available before the list of protections for the selection of the setting (Setting A / Setting B) available for LSIG versions SACE Tmax XT2 – XT4 | 26 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 27 Ekip Synchrocheck module CosØ available if required by the Trip unit model or if the Power Protections package has been enabled SETTING B available with the Adaptive Protection package SACE Tmax XT2 – XT4 | 27 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 28 Available if required by the Trip unit model or if the Measuring package has been enabled Available with the Ekip Synchrocheck module Available if required by the Trip unit model or if the Network Analyzer software package has been enabled SACE Tmax XT2 – XT4 | 28 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 29 The list of the specific submenu is only populated with the function enabled (= On) Available if required by the Trip unit model or if the relative software package has been enabled Available with Ekip M Touch SACE Tmax XT2 – XT4 | 29 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 30 Available if one or more modules are connected and detected by the unit Available if the function is installed and enabled on a Trip unit SACE Tmax XT2 – XT4 | 30 1SDH002031A1002 ECN000092998...
  • Page 31: Change Parameters And Commands

    Change to return to the menus and change the parameter Figure 17 Use the Right/Up and Left/Down buttons to move to the desired item, and confirm by pressing the Enter button. SACE Tmax XT2 – XT4 | 31 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 32 If the Trip unit detects an incorrect condition, the details are shown on the display and the command's execution is interrupted. WARNING! the cancellation of programming affects all the parameters changed during the session SACE Tmax XT2 – XT4 | 32 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 33: Password And Security

    There is no limit to the number of incorrect passwords that can be entered  If the password is lost, see the document 1SDH001501R0001 available on the ABB website, or contact ABB directly SACE Tmax XT2 – XT4 | 33 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 34: Protections

    Trip unit model and version and possible installation as an additional package: Package Page Standard Protections Voltage Protections Advanced Voltage Protections Frequency Protections Power Protections Adaptive Protections Motor Protections SACE Tmax XT2 – XT4 | 34 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 35: Standard Protections

    Distorted waveforms Abnormal temperatures Hardware Trip Internal connection errors Power thresholds Control thresholds exceeded NOTES: Not available with Ekip Touch in the LSI version Not available with Ekip M Touch SACE Tmax XT2 – XT4 | 35 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 36  The protection trip time is forced to 1 s if the calculations result in a lower theoretical value and/or if the current detected is higher than 12 In SACE Tmax XT2 – XT4 | 36 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 37 The I2 threshold must be greater than the I1 threshold (if the S protection is active)  With curve t = k/I the trip time is forced to t2 if the calculations result in a theoretical value that is lower than t2 itself SACE Tmax XT2 – XT4 | 37 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 38 The I5 threshold must be greater than the I1 threshold (if the S2 protection is active)  From the service connector (with Ekip Connect) or with system bus communication it is also possible to access the block functions and the selectivity type, see page70. SACE Tmax XT2 – XT4 | 38 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 39 I protection can be enabled with MCR protection disabled  From the service connector (with Ekip Connect) or with system bus communication it is also possible to access the block functions, see page 70 SACE Tmax XT2 – XT4 | 39 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 40 73 StartUp time 0.1 s The value is expressed in seconds, which are settable in a range: 0.1 s .. 30 s, with 0.01 s step SACE Tmax XT2 – XT4 | 40 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 41 Constraints, limitations, and additional functions  From the service connector (with Ekip Connect) or with system bus communication it is also possible to access the block functions and the selectivity type, see page70. SACE Tmax XT2 – XT4 | 41 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 42 Alerts With the 2I protection active, the message "2I active" appears in the diagnosis bar and on the Alarm List page, and the alarm LED is lit and fixed. SACE Tmax XT2 – XT4 | 42 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 43 0.5 s .. 60 s with 0.5 s step Ekip M Touch With Ekip M Touch IU protection is inhibited if the rms value of at least one of the phase currents is less than 0.25 In. SACE Tmax XT2 – XT4 | 43 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 44 The protection is triggered if the error states persist for more than one second  In the event of an alarm due to Trip coil disconnection, only the signal is managed SACE Tmax XT2 – XT4 | 44 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 45 Threshold: The value is expressed both as an absolute value (Ampere) and 3 In as a relative value (In), settable in a range: 0.1 In .. 10 In, with 0.01 step In Figure 19 SACE Tmax XT2 – XT4 | 45 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 46: Voltage Protections

    Constraints, limitations, and additional functions From the service connector (with Ekip Connect) or with system bus connection it is also possible to access the block functions, see page70. SACE Tmax XT2 – XT4 | 46 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 47 0.05 s .. 120 s, with 0.01 s step Constraints, limitations, and additional functions From the service connector (with Ekip Connect) or with system bus communication it is also possible to access the block functions, see page70. SACE Tmax XT2 – XT4 | 47 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 48 The protection can be activated in the Advanced – Alerts – Phase sequence menu (page 27) and the desired sequence set in the Settings - Phase sequence menu (page 29). SACE Tmax XT2 – XT4 | 48 1SDH002031A1002 ECN000092998...
  • Page 49 0.5 s .. 60 s, with 0.5 s step Constraints, limitations, and additional functions From the service connector (with Ekip Connect) or with system bus communication it is also possible to access the block functions, see page70. SACE Tmax XT2 – XT4 | 49 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 50: Advanced Voltage Protections

    1 In The value is expressed both as an absolute value (Ampere) and as a relative value (In), settable in a range: 0.6 In .. 10In with 0.1 In step SACE Tmax XT2 – XT4 | 50 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 51 0.05 s .. 30 s, with 0.01 s step Constraints, limitations, and additional functions From the service connector (with Ekip Connect) or with system bus communication it is also possible to access the block functions, see page70. SACE Tmax XT2 – XT4 | 51 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 52 ℎ2 − 2 The value is expressed both as an absolute value (Volt) and as a relative value (Un), settable in a range: 0.2 Un .. 1 Un with 0.01 Un step SACE Tmax XT2 – XT4 | 52 1SDH002031A1002 ECN000092998...
  • Page 53 0 s .. 0.2 s, with 0.02 s step Constraints, limitations, and additional functions From the service connector (with Ekip Connect) or with system bus communication it is also possible to access the block functions, see page70. SACE Tmax XT2 – XT4 | 53 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 54: Frequency Protections

    0.06 s .. 300 s, with 0.01 s step Constraints, limitations, and additional functions From the service connector (with Ekip Connect) or with system bus communication it is also possible to access the block functions, see page70. SACE Tmax XT2 – XT4 | 54 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 55 0.06 s .. 300 s, with 0.01 s step Constraints, limitations, and additional functions From the service connector (with Ekip Connect) or with system bus communication it is also possible to access the block functions, see page70. SACE Tmax XT2 – XT4 | 55 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 56 0.06 s .. 300 s, with 0.01 s step Constraints, limitations, and additional functions From the service connector (with Ekip Connect) or with system bus communication it is also possible to access the block functions, see page70. SACE Tmax XT2 – XT4 | 56 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 57: Power Protections

    0.05 s .. 120 s, with 0.01 s step Constraints, limitations, and additional functions From the service connector (with Ekip Connect) or with system bus communication it is also possible to access the block functions, see page70. SACE Tmax XT2 – XT4 | 57 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 58 This is the trip time in a backward direction. Time t7 Bw 0.2 s The value is expressed in seconds, settable in a range: 0.1 s .. 0.8 s, with 0.01 s step SACE Tmax XT2 – XT4 | 58 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 59 To avoid the possibility of an incorrect detection of the direction of the malfunction current in the event of a capacitive load, it is suggested that the regulation of this protection be referred to real malfunctions and not to overloads SACE Tmax XT2 – XT4 | 59 1SDH002031A1002 ECN000092998...
  • Page 60 0.5 s ..100 s, with 0.5 s step Constraints, limitations, and additional functions From the service connector (with Ekip Connect) or with system bus communication it is also possible to access the block functions, see page70. SACE Tmax XT2 – XT4 | 60 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 61 0.1 s .. 30 s, with 0.01 s step. Constraints, limitations, and additional functions From the service connector (with Ekip Connect) or with system bus communication it is also possible to access the block functions, see page70. SACE Tmax XT2 – XT4 | 61 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 62 Defines the slope of the straight line in relation to the threshold Q24. The value is expressed as an absolute value (angular coefficient of Threshold the straight line), settable in a range: -2 ..2 with 0.01 step SACE Tmax XT2 – XT4 | 62 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 63 Activates/deactivates protection and availability of protection threshold on Enable menu Defines the value that activates the protection; it is settable in a range: Threshold 0.5 .. 0.95 with 0.01 step SACE Tmax XT2 – XT4 | 63 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 64: Rocof Protections

    0.06 s .. 300 s, with 0.01 s step Constraints, limitations, and additional functions From the service connector (with Ekip Connect) or with system bus communication it is also possible to access the block functions, see page70. SACE Tmax XT2 – XT4 | 64 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 65: Adaptive Protections

    In the Advanced - Functions menu it is possible to program the event that causes the settings change (from default to secondary). See the chapter Programmable commands (page 75). SACE Tmax XT2 – XT4 | 65 1SDH002031A1002 ECN000092998...
  • Page 66: Motor Protections

    I1 (L protection), called Ir in the respective configuration menus. Example: Rated size = A, Threshold I1 = 0.8 In ( 32 A); Threshold Ij = 2.5 Ir ( 2.5 x 32 A = SACE Tmax XT2 – XT4 | 66 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 67 Constraints, limitations, and additional functions From the service connector (with Ekip Connect) or with system bus communication it is also possible to access the block functions, see page 70. SACE Tmax XT2 – XT4 | 67 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 68 Constraints, limitations, and additional functions From the service connector (with Ekip Connect) or with system bus connection it is also possible to access the block functions, see page 70. SACE Tmax XT2 – XT4 | 68 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 69 Enables/disables protection and availability on menu of the Enable parameters Activates/deactivates the open command: if disabled, the alarm Trip Enable and the lapsing of the protection time are managed only as information SACE Tmax XT2 – XT4 | 69 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 70: Additional Functions And Protections

     The device closest to the malfunction is triggered  The other devices are blocked for a programmable time NOTE: the connection is possible between ABB devices that have the zone selectivity function Characteristics Ekip Touch has five selectivity links:...
  • Page 71 The other devices are blocked for a programmable time NOTES:  The connection is possible between ABB devices that have the zone selectivity function  For correct use of the D selectivity function disable the zone selectivity of the S, S2 and G protections SACE Tmax XT2 –...
  • Page 72 NOTE: with zone selectivity activated, if the direction of the malfunction cannot be determined the unit intervenes taking into consideration the lowest programmed time between t7 Fw and t7 Bw, without activating any output (DFout or Dbout). SACE Tmax XT2 – XT4 | 72 1SDH002031A1002 ECN000092998...
  • Page 73 NOTE: startup does not reoccur while at least one current remains above the activation threshold level Below is a graphical representation with S protection: Figure 25 SACE Tmax XT2 – XT4 | 73 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 74 (e.g. generator + grid) for closing the interconnection switch. The descriptions of the module, the protection function and the performance are outlined in the chapter dedicated to the modules (page 161). SACE Tmax XT2 – XT4 | 74 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 75 0 s .. 100 s, with 0.1 s step IMPORTANT: the commands are sent if all the operating conditions expected by the units are found (connections, power supplies, alarms, etc.). SACE Tmax XT2 – XT4 | 75 1SDH002031A1002 ECN000092998...
  • Page 76: Logical Selectivity

    There are 2 additional states – C and D – but they are not configurable for Zone Selectivity. All 4 programmable states are used for the Programmable Logic function (see Ekip Link module, page 151). NOTE: the Programmable Logic function is independent from the Zone Selectivity function SACE Tmax XT2 – XT4 | 76 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 77 Bus and associated with Ekip Touch, while it is not necessary for the function to be enabled (the Selectivity Actor parameter does not have to be set to the value: True) SACE Tmax XT2 – XT4 | 77 1SDH002031A1002 ECN000092998...
  • Page 78: Performance Tables

    ± 7 % with If  6 In = t5 startup S2 StartUp The better of: ± 10 % or ± 40 ms ± 10 % with If > 6 In SACE Tmax XT2 – XT4 | 78 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 79 Protection Trip threshold Trip time t Trip time tolerance Protections [ANSI code] tolerance = t28 ROCOF [81R] ± 10 % The better of: ± 20 % or 200 ms SACE Tmax XT2 – XT4 | 79 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 80 ± 10 % ± 20 % (60 ms with t4 = instant) UF / UF2 / OF / OF2 ± 2 % ± 20 % Others ± 20 % SACE Tmax XT2 – XT4 | 80 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 81: Curves

    The curves do not take into account the effects of special parameters like thermal memory and startups. NOTES: to calculate the trip time it is recommended to always use the mathematical function in the protections summary table (page 78) L curve (t= k/I SACE Tmax XT2 – XT4 | 81 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 82 L curve (IEC 60255-151 SI) L curve (IEC 60255-151 VI) SACE Tmax XT2 – XT4 | 82 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 83 L curve (IEC 60255-151 EI) L curve (t= k/I SACE Tmax XT2 – XT4 | 83 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 84 L curve (Ekip M Touch) S curve (t= k/I SACE Tmax XT2 – XT4 | 84 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 85 S curve (t= k) Curve S2 I curve MCR curve 2I curve SACE Tmax XT2 – XT4 | 85 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 86 G curve (t= k/I G curve (t= k) SACE Tmax XT2 – XT4 | 86 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 87 IU curve UV curve UV2 curve SACE Tmax XT2 – XT4 | 87 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 88 OV curve OV2 curve VU curve SACE Tmax XT2 – XT4 | 88 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 89 S(V) curve S2(V) curve RV curve SACE Tmax XT2 – XT4 | 89 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 90 UF curve UF2 curve OF curve OF2 curve SACE Tmax XT2 – XT4 | 90 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 91 RP curve D curve SACE Tmax XT2 – XT4 | 91 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 92 OQ curve OP curve SACE Tmax XT2 – XT4 | 92 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 93 UP curve RQ curve SACE Tmax XT2 – XT4 | 93 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 94 ROCOF curve R JAM curve R STALL SACE Tmax XT2 – XT4 | 94 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 95 UC curve SACE Tmax XT2 – XT4 | 95 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 96: Measurements

    Measurement < Measurement > Display: "_ _ _" (not measurement min value max value available) for Phase currents ..> [64 In] Sensors disconnected ground fault currents SACE Tmax XT2 – XT4 | 96 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 97: Current

    Ne is available with CB 4P and 3P + N Power Ne, Ig Ig is available in the event of trips for G protection Temperature Currents L1, L2, L3, Ne The temperature cannot be seen on the display SACE Tmax XT2 – XT4 | 97 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 98 When the "Measurement interval" parameter is changed, the trip unit immediately saves a record Reset measurements The Measurement Reset command to clear all records is found in the Measurements - Logs - Measurements menu SACE Tmax XT2 – XT4 | 98 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 99 By activating communication with the Trip unit the following counters are also available:  Number of manual operations  Number of openings due to trips (TRIP)  Number of openings due to failed trips  Number of opening tests performed SACE Tmax XT2 – XT4 | 99 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 100: Measuring Measure

    -10 % .. f +10 % 0.1 % Total active, reactive and |Pmin .. Pmax| |0.3 .. 1.2 Sn| apparent power Active, reactive and |Pmin.. Pmax| |0.3 .. 1.2 Pn| apparent phase power SACE Tmax XT2 – XT4 | 100 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 101: Notes: (1) (2)

    NOTE: compared to current measurements, the graphical representation is compared to 1 Un (with a maximum value of 1.25 Un) for voltage records and compared to 1 Sn (with a maximum value of 1.25 Sn) for power records SACE Tmax XT2 – XT4 | 101 1SDH002031A1002 ECN000092998...
  • Page 102: Display

    Trip unit models, check the performance shown on page Reset measurements The Energy RESET command (page 28) is available in the Energy menu to reset the energy counters. SACE Tmax XT2 – XT4 | 102 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 103: Class 1 Power & Energy Metering

    (Active/Inactive) and the serial numbers of some accessories mounted on the CB specifically to respond to the characteristics of the package (assembly of electronic units and internal current sensors) SACE Tmax XT2 – XT4 | 103 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 104: Datalogger

    2 record delay and Restart/Stop commands Restart and Synchronized start and stop commands of the two data loggers, Stop Both valid and available with Datalogger Num. = 2 SACE Tmax XT2 – XT4 | 104 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 105 2. Data Viewer to open and view logs Both areas are available in Ekip Connect's Tools menu and described in the Help section of the application. SACE Tmax XT2 – XT4 | 105 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 106: Network Analyzer

    Menu with the control parameters for voltage sags Surges Menu with the control parameters for voltage surges Available by enabling the harmonic analysis of currents and/or Harmonics voltages, the menu allows configuring the harmonic control parameters SACE Tmax XT2 – XT4 | 106 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 107 Single Counter control threshold of the individual voltage harmonic th harmonics Counter control threshold THD Current. Threshold Voltage Single Counter control threshold of the individual current harmonic th harmonics SACE Tmax XT2 – XT4 | 107 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 108 L1, L2, L3, Ne Real-time value of the harmonic distortion of each current phase Real-time value of the harmonic distortion of each line-to-line THD Voltage U12, U23, U31 voltage SACE Tmax XT2 – XT4 | 108 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 109 Count of V Interruption referring to the current day Actual [day -2 ... day -7] Count of V Interruption detected in the last seven days of activity, number of I. calculated using the unit's internal clock SACE Tmax XT2 – XT4 | 109 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 110 Count of Sag.Short referring to the current day Actual [day -2 ... day -7] Count of Sag.Short detected in the last seven days of activity, number of S. calculated using the unit's internal clock SACE Tmax XT2 – XT4 | 110 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 111 Count of Swell. Long referred to the current day Count of Swell. Long detected in the last seven days of activity, Actual [day -2 ... day -7] number of S. calculated using the unit's internal clock SACE Tmax XT2 – XT4 | 111 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 112 Count of THD Voltages referring to the current day [min] Actual [day -2 ... day -7] Count of THD Voltages referred to the last seven days of activity, number of THD T. calculated using the unit's internal clock SACE Tmax XT2 – XT4 | 112 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 113: Settings

    NOTE: measurements are performed according to the grid frequency set. An incorrect parameter configuration can cause measurement and protection malfunctions Ekip Touch is supplied with the parameter set according to the configuration ordered. SACE Tmax XT2 – XT4 | 113 1SDH002031A1002 ECN000092998...
  • Page 114 IMPORTANT: the typical scenario for configuring Battery mode = On is: Ekip Touch + Ekip TT + communication with smartphone active. In all other cases, including System Update, Battery mode = --- SACE Tmax XT2 – XT4 | 114 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 115 Sets the contrast of the Ekip Touch LCD display. The parameter allows enabling/disabling an alarm related to unit maintenance, described on Maintenance page 99. Ekip Touch is supplied with the parameter set to: On. SACE Tmax XT2 – XT4 | 115 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 116 Autoreclosure Time The value is expressed in seconds, which can be set in a range: 1 s .. 1000 s, with 1 s steps SACE Tmax XT2 – XT4 | 116 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 117: Supplemental Settings

    User-programmable labels useful for facilitating the remote identification of units; User data NOTE: the TAG Name label and the communication address make up the identifier used by Ekip Connect for the connected devices SACE Tmax XT2 – XT4 | 117 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 118 (change recommended only for expert technical staff) Glitch The Glitch commands from 16 to 23 activate the respective glitch registers, useful for customizing any programmable functions or output contacts. SACE Tmax XT2 – XT4 | 118 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 119: Test

    Make sure the coils are connected to the power source  The commands check the Trip unit's operation. Any malfunctions of the coils are not detected by the test SACE Tmax XT2 – XT4 | 119 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 120 Provides the status of the selectivity input (On/Off) Force Output The selectivity output is activated Release Output The selectivity output is deactivated To check the selectivity contacts refer to the commissioning procedure (page 14). SACE Tmax XT2 – XT4 | 120 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 121: Additional Functions

    Information included Load Input Status Load status (from Load 1 to Load 15): open or closed Active load Load configuration (from Load 1 to Load 15): active or inactive SACE Tmax XT2 – XT4 | 121 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 122: Load Shedding

    10 s ..1800 s with 1 s steps NOTE: Load shedding is activated if the control conditions defined by the Frequency slope and FW Warning parameters are simultaneously present SACE Tmax XT2 – XT4 | 122 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 123 Information included Load Input Status Load status (from Load 1 to Load 15): open or closed Active load Load configuration (from Load 1 to Load 15): active or inactive SACE Tmax XT2 – XT4 | 123 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 124: Interface Protections Ips

    The value is expressed both in an absolute value (Volt) and a Threshold 0.8 Un relative value (Un), which can be set in a range: 0.1 Un .. 1.5 Un with 0.05 Un steps SACE Tmax XT2 – XT4 | 124 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 125 The control time that activates the signal. The value is expressed Time in seconds, which can be set in a range: 30 s 0.1 s .. 900 s, with 0.1 s steps SACE Tmax XT2 – XT4 | 125 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 126 The value is expressed both in an absolute value (Hertz) and a Threshold 1 Fn relative value (Fn), which can be set in a range: 0.9 Fn .. 1.1 Fn with 0.001 Fn steps SACE Tmax XT2 – XT4 | 126 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 127: External Accessories

    Outputs only function correctly if configured as: input state (of module itself) or non-communication with trip unit. For all other configurations, the module forces the Outputs as per Contact Type parameter (NO, NC). SACE Tmax XT2 – XT4 | 127 1SDH002031A1002 ECN000092998...
  • Page 128 System Interface The document 1SDH002031A1101, in .zip format, is available in the ABB library in order to ensure that the Ekip Com communication modules are used correctly; the file contains: Document Description Guidelines with details for commissioning the communication 1SDH002031A1101.pdf...
  • Page 129: Ekip Cartridge

    Access to all external connections are available on the respective modules, on the top side of Ekip Cartridge. Assembly To connect the module to Ekip Touch see the instruction sheets 1SDH002009A1503. SACE Tmax XT2 – XT4 | 129 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 130: Ekip Supply

    1SDM000068R0001 for terminal references. For external cabling, use AWG22-16 cables with a maximum external diameter of 1.4  the instruction sheets 1SDH001000R0511 to connect the module to Ekip Touch. SACE Tmax XT2 – XT4 | 130 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 131: Ekip Com Modbus Rtu

    Ekip Com Modbus RTU is supplied directly by the Ekip Supply module to which it is connected. Supply NOTE: in the absence of an auxiliary supply, the communication between Ekip Touch and module is interrupted SACE Tmax XT2 – XT4 | 131 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 132 3 and 4 Move dip switches 3 and 4 to ON position to connect Rpol IMPORTANT: move the dip-switches before connecting to Ekip Supply module and to the communication network SACE Tmax XT2 – XT4 | 132 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 133 From the service connector (via Ekip Connect) or with a system bus communication, additional information is available on the version and the status of the module: HW and Boot version, CRC information status (correctness of SW in the module). SACE Tmax XT2 – XT4 | 133 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 134: Ekip Com Profibus Dp

    Ekip Com Profibus DP is supplied directly by the Ekip Supply module, to which it is connected. NOTE: in the absence of an auxiliary supply, the communication between Ekip Touch and module is interrupted SACE Tmax XT2 – XT4 | 134 1SDH002031A1002 ECN000092998...
  • Page 135 3 and 4 Move dip switches 3 and 4 to ON position to connect Rpol IMPORTANT: move the dip-switches before connecting to Ekip Supply module and to the communication network SACE Tmax XT2 – XT4 | 135 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 136 From the service connector (via Ekip Connect) or with a system bus communication, additional Remote information information is available on the version and the status of the module: HW and Boot version, CRC status (correctness of SW in the module). SACE Tmax XT2 – XT4 | 136 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 137: Ekip Com Devicenet

    12 VDC. NOTE:  the PLC ABB with DeviceNet (CM575-DN) communication module already supplies the V+ V- supply  in the absence of the supplies from Ekip Supply and on the supply terminals of the bus, the communication between Ekip Touch and module is interrupted.
  • Page 138  the termination resistances must not be installed at the end of a drop line but only at the two ends of the main trunk line SACE Tmax XT2 – XT4 | 138 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 139 From the service connector (via Ekip Connect) or with a system bus communication, additional information information is available on the version and the status of the module: HW and Boot version, CRC status (correctness of SW in the module). SACE Tmax XT2 – XT4 | 139 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 140: Ekip Com Modbus Tcp

    ABB Ltd and its affiliates are not liable for damages and/or losses related to such security breaches,any unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 141   fixed light: correct connection Indicates status of the communication: Activity  off: activity on line absent   flashing: activity on line present (receiving and/or transmitting) SACE Tmax XT2 – XT4 | 141 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 142 IP addresses of the client devices connected to the module (in Server TCP Client 1, 2, 3 mode) Address assigned by ABB with OUI (Organizationally Unique Identifier) MAC Address equal to ac:d3:64 that identifies uniquely the manufacturer of an Ethernet device SACE Tmax XT2 –...
  • Page 143 Valid with IEEE 1588 Master = ON, communicates the presence IEEE 1558 status (Slave or PTP Master Active) or absence (PTP Master but Passive) of a higher level master SACE Tmax XT2 – XT4 | 143 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 144: Ekip Com Profinet

    ABB Ltd and its affiliates are not liable for damages and/or losses related to such security breaches,any unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 145   fixed light: correct connection Indicates status of the communication: Activity  off: activity on line absent   flashing: activity on line present (receiving and/or transmitting) SACE Tmax XT2 – XT4 | 145 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 146 About-Modules menu: Information Description SN and version Identification and SW version of the module Address assigned by ABB with OUI (Organizationally Unique Identifier) MAC Address equal to ac:d3:64 that identifies uniquely the manufacturer of an Ethernet device Remote From the service connector (via Ekip Connect) or with a system bus communication, additional...
  • Page 147: Ekip Com Ethernet/Ip

    ABB Ltd and its affiliates are not liable for damages and/or losses related to such security breaches,any unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 148   fixed light: correct connection Indicates status of the communication: Activity  off: activity on line absent   flashing: activity on line present (receiving and/or transmitting) SACE Tmax XT2 – XT4 | 148 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 149 IP address of the node to which the module is connected, in the Gateway address presence of several subnets Address assigned by ABB with OUI (Organizationally Unique Identifier) MAC Address equal to ac:d3:64 that identifies uniquely the manufacturer of an Ethernet device SACE Tmax XT2 –...
  • Page 150 Valid with IEEE 1588 Master = ON, communicates the IEEE 1558 status presence (Slave or PTP Master Active) or absence (PTP Master but Passive) of a higher level master SACE Tmax XT2 – XT4 | 150 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 151: Ekip Com Iec 61850

    ABB Ltd and its affiliates are not liable for damages and/or losses related to such security breaches,any unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 152   fixed light: correct connection Indicates status of the communication: Activity  off: activity on line absent   flashing: activity on line present (receiving and/or transmitting) SACE Tmax XT2 – XT4 | 152 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 153 IP address of the node to which the module is connected, in the presence address of several subnets Address assigned by ABB with OUI (Organizationally Unique Identifier) MAC Address equal to ac:d3:64 that identifies uniquely the manufacturer of an Ethernet...
  • Page 154 (28) and Request close switch (29) Falg word hex set a filter on the selectivity status NOTE: Enable IEEE 1558 and Enable SNTP client must not be enabled simultaneously SACE Tmax XT2 – XT4 | 154 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 155 Condition (true/false) of the programmable statuses and statuses (from E to R) information on selectivity arising from logics defined in the Remote inputs of zone configuration files loaded on module IEC 61850 selectivity SACE Tmax XT2 – XT4 | 155 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 156: Ekip Link

    Each Ekip Link can interface with at most 15 actors, with a maximum of 12 for the Zone Selectivity function. The following ports are used by the module: Port Service Notes In the event of fast information exchange between ABB 18/udp ABB Proprietor devices 319/udp IEEE 1588...
  • Page 157   fixed light: correct connection Indicates status of the communication:  Activity  off: activity on line absent  flashing: activity on line present (receiving and/or transmitting) SACE Tmax XT2 – XT4 | 157 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 158 IP address of the node to which the module is connected, in the presence of Gateway address several subnets Address assigned by ABB with OUI (Organizationally Unique Identifier) equal to MAC Address ac:d3:64 that identifies uniquely the manufacturer of an Ethernet device SACE Tmax XT2 –...
  • Page 159 (mixed) interactive mask for selecting selectivity do be sent also Repeat Configuration Mask to the upper levels (even if not active on the programmed 0x0000 device) SACE Tmax XT2 – XT4 | 159 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 160 B, C and D Remote programmable Word status value of the remote programmable Word A, B, C, D Zone logic selectivity Statuses of the logic selectivity (inputs and outputs) SACE Tmax XT2 – XT4 | 160 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 161: Ekip Com Hub

    ABB Ltd and its affiliates are not liable for damages and/or losses related to such security breaches,any unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 162 Enables the module's firmware to be updated. Two parameters are available: Remote firmware  update Enable, to configure the firmware download Automatic  Automatic, to automate updating the module SACE Tmax XT2 – XT4 | 162 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 163 IP address of the node to which the module is connected, in the Gateway address presence of several subnets Address assigned by ABB with OUI (Organizationally Unique Identifier) MAC Address equal to ac:d3:64 that identifies uniquely the manufacturer of an...
  • Page 164 Status Cloud side module and the server Application status indicators of progress of the operations general module indicators: SNTP status, flash, cable Status connection, FW availability, file errors, etc SACE Tmax XT2 – XT4 | 164 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 165: Ekip Signalling 2K

    Status detected by Ekip Status Electrical condition Configuration of contact Touch Active open Open Circuit open Active closed Active open Closed Short circuit active closed SACE Tmax XT2 – XT4 | 165 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 166 Modules Settings menu is activated. For each Ekip Signalling 2K module detected by Ekip Touch, a specific menu is available containing the submenus of all the available and configurable inputs and outputs. SACE Tmax XT2 – XT4 | 166 1SDH002031A1002 ECN000092998...
  • Page 167 SACE Tmax XT2 – XT4 | 167 1SDH002031A1002 ECN000092998...
  • Page 168 From the service connector (via Ekip Connect) or with a system bus communication, additional information information is available on the version and the status of the module: HW and Boot version, CRC status (correctness of SW in the module). SACE Tmax XT2 – XT4 | 168 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 169: Ekip Synchrocheck

    IMPORTANT: in order to be able to disable the frequency and phase controls, make sure that there is already the desired frequency and phase correspondence between external and internal contacts SACE Tmax XT2 – XT4 | 169 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 170 20 % permanent Electrical  insulation: 4 kV between inputs and outputs, 4 kV between screen and 4 kV outputs between screen and inputs.  frequency: 45-66 Hz SACE Tmax XT2 – XT4 | 170 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 171 O SC NOTE: The LED shows output status: depending on the rest configuration of the contact (normally open or closed), it can indicate synchronization OK or Not OK SACE Tmax XT2 – XT4 | 171 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 172 10% hysteresis is applied: once it is reached, the condition is lost if voltage falls below 90% of the set limit parameter not available with dead busbar and Auto Live-dead detect = Manual SACE Tmax XT2 – XT4 | 172 1SDH002031A1002 ECN000092998...
  • Page 173 Phase difference between voltages, expressed in degrees Phase  --- = measurement not available (e.g.: because of disabled synchronism or difference operation with dead busbar or frequencies outside measurement range) SACE Tmax XT2 – XT4 | 173 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 174 From the service connector (via Ekip Connect) or with a system bus communication, additional information information is available on the version and the status of the module: HW and Boot version, CRC status (correctness of SW in the module). SACE Tmax XT2 – XT4 | 174 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 175: Ekip Signalling 3T

    Ekip Supply module on the basis of the application and network. For applications in low voltage plants, ABB suggests using a dedicated external insulated PT1000 sensor. This can be ordered using the 1SDA085695R1 code and is provided with a nut and screw for use on a bar and is compatible with the dielectric strength and insulation levels specified in standard IEC 60947-2 (Ui= 1000 V, Uimp= 12 kV).
  • Page 176 NOTE: parameters and measurements are distributed on Ekip Connect pages and communication addresses that are sometimes not consequential; the following tables show the page references to Ekip Connect 2 SACE Tmax XT2 – XT4 | 176 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 177 0 % .. 30 % with 0.1 % step  (each step equivalent to 0.016 On the Warnings/Alarms page, the status of all the control thresholds can be checked. Statuses and alarms SACE Tmax XT2 – XT4 | 177 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 178: Ekip Ci

    8A @ 250 VAC / 5A @ 30 VDC Minimum breaking power 10 mA @ 5 VDC Insulation resistance between contact and Trip 1000 MΩ, 50 VDC unit NOTE: data related to a resistive load SACE Tmax XT2 – XT4 | 178 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 179 I 63 Off: input open  On: input closed Indicates the status of the command contact for the O61 contactor:  O 61 Off: contact closed  On: contact open SACE Tmax XT2 – XT4 | 179 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 180 Some additional information regarding the version and status of the module are available from information the service connector (via Ekip Connect) or the system bus communication: HW and Boot version, CRC status (correctness of the SW on the module). SACE Tmax XT2 – XT4 | 180 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 181: Internal Accessories

    Ekip Com Modbus RTU is supplied directly by the Ekip Touch module to which it is connected. NOTE: in the absence of an auxiliary supply, the communication between Ekip Touch and module is interrupted SACE Tmax XT2 – XT4 | 181 1SDH002031A1002 ECN000092998...
  • Page 182 From the service connector (via Ekip Connect) or with a system bus communication, additional information information is available on the version and the status of the module: HW and Boot version, CRC status (correctness of SW in the module). SACE Tmax XT2 – XT4 | 182 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 183: Ekip Com Modbus Tcp

    ABB Ltd and its affiliates are not liable for damages and/or losses related to such security breaches,any unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 184 Enables the subnet mask to be selected 0.0.0.0 Enables, in the presence of several subnets the IP Static Gateway address of the node to which the module is connected 0.0.0.0 address to be selected SACE Tmax XT2 – XT4 | 184 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 185 IP addresses of the client devices connected to the module (in Server TCP Client 1, 2, 3 mode) Address assigned by ABB with OUI (Organizationally Unique Identifier) MAC Address equal to ac:d3:64 that identifies uniquely the manufacturer of an Ethernet device SACE Tmax XT2 –...
  • Page 186: Ekip Com Profinet

    ABB Ltd and its affiliates are not liable for damages and/or losses related to such security breaches,any unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 187 About-Modules menu: Information Description SN and version Identification and SW version of the module Address assigned by ABB with OUI (Organizationally Unique Identifier) MAC Address equal to ac:d3:64 that identifies uniquely the manufacturer of an Ethernet device Remote From the service connector (via Ekip Connect) or with a system bus communication, additional...
  • Page 188: Ekip Com Ethernet/Ip

    ABB Ltd and its affiliates are not liable for damages and/or losses related to such security breaches,any unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 189 IP address of the node to which the module is connected, in the Gateway address presence of several subnets Address assigned by ABB with OUI (Organizationally Unique Identifier) MAC Address equal to ac:d3:64 that identifies uniquely the manufacturer of an Ethernet device SACE Tmax XT2 –...
  • Page 190 Valid with IEEE 1588 Master = ON, communicates the IEEE 1558 status presence (Slave or PTP Master Active) or absence (PTP Master but Passive) of a higher level master SACE Tmax XT2 – XT4 | 190 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 191: Ekip Com Iec 61850

    TFTP - Trivial File Transfer Protocol IMPORTANT: each XT2 / XT4 circuit breaker can accommodate only one module; configuration with external communication modules is not permitted if an internal module is present SACE Tmax XT2 – XT4 | 191 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 192 ABB Ltd and its affiliates are not liable for damages and/or losses related to such security breaches,any unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 193 IP address of the node to which the module is connected, in the presence address of several subnets Address assigned by ABB with OUI (Organizationally Unique Identifier) MAC Address equal to ac:d3:64 that identifies uniquely the manufacturer of an Ethernet...
  • Page 194 (28) and Request close switch (29) Falg word hex set a filter on the selectivity status NOTE: Enable IEEE 1558 and Enable SNTP client must not be enabled simultaneously SACE Tmax XT2 – XT4 | 194 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 195 Condition (true/false) of the programmable statuses and statuses (from E to R) information on selectivity arising from logics defined in the Remote inputs of zone configuration files loaded on module IEC 61850 selectivity SACE Tmax XT2 – XT4 | 195 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 196: Ekip Link

    The ports used by the module are: Port Service Remarks 18/UDP ABB proprietary For fast exchange of information between ABB devices 319/UDP IEEE 1588 Valid with IEEE 1588 protocol enabled 320/UDP DHCP client enabled as an alternative to Static Address = On...
  • Page 197 Enter the static IP address 0.0.0.0 Static Network Mask Enter the subnet mask 0.0.0.0 Static gateway With multiple subnets, enter the IP address of the node the 0.0.0.0 address module is connected to SACE Tmax XT2 – XT4 | 197 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 198 IP address of the node to which the module is connected when there are multiple Gateway address subnets Address assigned by ABB with OUI (Organizationally Unique Identifier) equal to MAC address ac:d3:64 that uniquely identifies the manufacturer of an Ethernet device...
  • Page 199 State (true/false) of the A, B, C and D remote programmable Remote programmable states states Remote programmable word status Value of the A, B, C, D remote programmable words Logical zone selectivity Logical selectivity states (inputs and outputs) SACE Tmax XT2 – XT4 | 199 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 200: Ekip Com Hub

    ABB and its affiliates are not responsible for damages and/or losses related to such security breaches, unauthorized access, interference, intrusion, loss and/or theft of data or information.
  • Page 201 IP address of the node to which the module is connected when there are Gateway address multiple subnets Address assigned by ABB with OUI (Organizationally Unique Identifier) MAC address equal to ac:d3:64 that uniquely identifies the manufacturer of an Ethernet device SACE Tmax XT2 –...
  • Page 202 Status of errors related to the TLS session established between the Status Cloud side module and the server Application status Progress indicators for operations General module indicators: status of SNTP, flash, cable connection, Status FW availability, file errors, etc SACE Tmax XT2 – XT4 | 202 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 203: Others Accessories

    The module can can be supplied at 110-240 VAC / DC or 24-48 VDC. More information Ekip Signalling available website http://www.abb.com/abblibrary/DownloadCenter/, document 1SDH001318R0002. IMPORTANT: make sure that you have read the safety requirements and requirements regarding prevention of unauthorized accesses. SACE Tmax XT2 – XT4 | 203 1SDH002031A1002 ECN000092998 Rev. B...
  • Page 204: Ekip Multimeter

    15 m must be used. The cable shield must be grounded on both sides of the connection. Documentation More information is available at http://www.abb.com/abblibrary/DownloadCenter/, in kit sheet 1SDH001000R0520. 62 - External neutral It is a current sensor for the neutral pole outside the circuit breaker for CB 3P to establish neutral protection by connecting to the Trip unit.
  • Page 205: Testing And Programming

    Bluetooth Low Energy (Bluetooth 4.1). Ekip Bluetooth Key is compatible with all the trip units installed on ABB low voltage circuit breakers of the Tmax XT and Emax 2 series. For more information, refer to the instruction manual 1SDH002023A1001 SACE Tmax XT2 –...
  • Page 206: Revisions

    Revisions Overhaul Description ECN000092998 Second version SACE Tmax XT2 – XT4 | 206 1SDH002031A1002 ECN000092998 Rev. B...