Troubleshooting; Error Codes For Micro800 Plug-Ins - Allen-Bradley Micro800 2080-MEMBAK-RTC2 User Manual

Plug-in modules
Table of Contents

Troubleshooting

Error Codes for Micro800
Plug-ins
List of Error Codes for Micro800 Plug-ins
Error Code
Description
For the following four error codes, z refers to the slot number of the plug-in module. If z = 0, then the slot number cannot be identified
0xF0Az
The plug-in I/O module has encountered an error
during operation.
0xF0Bz
The plug-in I/O module configuration does not
match the actual I/O configuration detected.
0xF0Dz
A hardware error has occurred while power was
being applied to the plug-in module or the plug-in
module was removed.
0xF0Ez
The plug-in I/O module configuration does not
match the actual I/O configuration detected.
Rockwell Automation Publication 2080-UM004D-EN-E - March 2018
Error Codes
For troubleshooting your Micro800 controller system, see the User Manual for
your controller:
• Micro830, Micro850, and Micro870 Programmable Controllers User
Manual, publication 2080-UM002.
• Micro820 Programmable Controllers User Manual, publication
2080-UM005.
This section lists possible error codes for your plug-in modules, as well as
recommended actions for recovery.
If an error persists after performing the recommended action, contact your local
Rockwell Automation technical support representative. For contact information,
go to
http://support.rockwellautomation.com/MySupport.asp
Recommended Action
Perform one of the following:
• Check the condition and operation of the plug-in I/O module.
• Cycle power to the Micro800 controller.
Perform one of the following:
• Correct the plug-in I/O module configuration in the user program to match
that of the actual hardware configuration.
• Check the condition and operation of the plug-in I/O module.
• Cycle power to the Micro800 controller.
• Replace the plug-in I/O module.
Perform the following:
• Correct the plug-in I/O module configuration in the user program.
• Build and download the program using Connected Components Workbench.
• Put the Micro800 controller into Run mode.
Perform the following:
• Correct the plug-in I/O module configuration in the user program.
• Build and download the program using Connected Components Workbench.
• Put the Micro800 controller into Run mode.
C
Appendix
109