Section 3: Prerequisites For Installation; Inventory; Environmental Specifications; Software Downloads - Honeywell SILENT KNIGHT 6700 Manual

Addressable fire alarm control panel
Table of Contents
This section of the Manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly,
especially if you are installing a 6700 panel for the first time.

3.1 Inventory

When the 6700 shipment is received, check that all the parts have been included in the shipment. The shipment consists of one of each of the
following:
main circuit board with the display
backbox with door
plastic bag containing two keys, screws, cables, and ten 4.7K ohm end-of-line resistors
manual

3.2 Environmental Specifications

It is important to protect the 6700 control panel from water. To prevent water damage, the following precautions should be FOLLOWED
when you install the units:
Intended for indoor use in dry locations only.
Do not mount the panel directly on exterior walls, especially masonry walls (condensation).
Do not mount the panel directly on exterior walls below grade (condensation).
Protect the panel from plumbing leaks.
Protect the panel from splash caused by Sprinkler System inspection ports.
Do not mount the panel in areas with humidity-generating equipment (such as dryers, production machinery).
When you select a location to mount the 6700 control panel, the unit should be mounted where it will NOT be exposed to temperatures out-
side the range of 32°F-120°F (0°C-49°C) or humidity outside the range of 10%-93% at 86°F (30°C) non-condensing.

3.3 Software Downloads

In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades
to the embedded software in our products. To ensure that you install and program the latest features, we strongly recommend that you down-
load the most current version of software for each product prior to commissioning any System. Contact Technical Support with any ques-
tions about software and the appropriate version for a specific application. The HFSS Honeywell Fire Software Suite is available at
www.silentknight.com.

3.4 Electrical Specifications

Table 3.1 lists the terminal block on the 6700 as well as a description of each individual terminal and their respective electrical rating. For the
location of the terminals, refer to Figure 4.3. See also Section 4 for installation information.
Terminal No.
Group
Terminal Block 3 TELCO 1
PHONE 1
TELCO 2
PHONE 2
Terminal Block 2 RELAY 1
RELAY 2
TROUBLE
SLC IN
SLC OUT
SLC PROG
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022

Section 3: Prerequisites for Installation

Label
Individual
RING
Phone Line 1 Telco Ring
TIP
Phone Line 1 Telco Tip
RING
Phone Line 1 Phone Ring
TIP
Phone Line 1 Phone Tip
RING
Phone Line 2 Telco Ring
TIP
Phone Line 2 Telco Tip
RING
Phone Line 2 Phone Ring
TIP
Phone Line 2 Phone Tip
NO
Normally open relay contact
COM
Common terminal
NC
Normally closed relay contact
NO
Normally open relay contact
COM
Common terminal
NC
Normally closed relay contact
NO
Normally open relay contact
COM
Common terminal
NC
Normally closed relay contact
Used for Class A installations
+
SLC terminals
+
Used for programming SLC Detectors
+
Table 3.1 Terminal Descriptions and Electrical Specifications
Description
Rating
Voltage
Current
27.4 VDC
2.5 A, resistive
27.4 VDC
2.5 A, resistive
27.4 VDC
2.5 A, resistive
32 VDC
100 mA
32 VDC
100 mA
32 VDC
100 mA
15