GE DigitalFlow XGS868i Programming Manual page 39

Panametrics steam ultrasonic mass flow transmitter
Table of Contents
1.9.2e
RTD Inputs
Option cards with RTD inputs have a temperature range of –148 to 662°F (–100 to 350°C). While following the
programming instructions, refer to Figure 31 on page 80, and complete the following steps to set up the RTD inputs of
an option card installed in Slot 1.
Accessing the Input
1. In the Keypad Program, scroll to PROG and press [Enter].
2. In the PROG menu, scroll to GLOBL and press [Enter].
3. In the Global PROGRAM menu, scroll to I/O and press [Enter].
4. Scroll to OPTN and press [Enter].
5. Scroll to Slot 1 and press [Enter].
6. Scroll to the desired Input and press [Enter].
Note: Input letters (A, B, etc.) correspond to input wiring terminal numbers from top to bottom (e.g. Input A
corresponds to pins 1,2 and 3; Input B corresponds to pins 4, 5 and 6; etc.).
Setting Up the RTD Input
1. Enter a Label for the RTD input and press [Enter].
2. Scroll to the desired input type and press [Enter]. Do one of the following:
Off
If
was selected, go to Procedure Options below.
Temperature
If
was selected, proceed to the next step.
3. Enter a temperature value for the Low end of the analog input range and press [Enter].
4. Enter a temperature value for the High end of the analog input range and press [Enter].
Procedure Options
After completing the above steps, the XGS868i returns to the I/O window. Do one of the following:
To continue programming, refer to Appendix A, Menu Maps, to navigate to the desired menu.
To leave the Keypad Program, press [Escape] four times.
DigitalFlow™ XGS868i Programming Manual
Chapter 1. Programming Site Data
29