Setting Up Slot 0 and Slot 1 Input/Outputs
The Model XGS868i has two built-in analog outputs, which are assigned to
cards may be installed in
available option cards.
To set up option cards, refer to one of the following sections:
Analog Outputs - refer to section below.
Analog Inputs - see page 28
RTD Inputs - see page 29
Alarm Relays - see page 30
Totalizer Outputs - see page 32
Frequency Outputs - see page 34
1.9.2c
Analog Outputs
While following the programming instructions, refer to Figure 31 on page 80.
Accessing the Output
1. In the Keypad Program, scroll to PROG and press [Enter].
2. In the PROG menu, scroll to GLOBL and press [Enter].
3. In the Global PROGRAM menu, scroll to I/O and press [Enter].
4. Scroll to OPTN and press [Enter].
5. Scroll to Slot 0 or Slot 1, depending on which output you want to set up.
6. Scroll to the desired Output and press [Enter].
Note: Output letters (A, B, etc.) correspond to the output wiring terminal numbers from top to bottom. For example,
Output A corresponds to pins 1,2 and 3; Output B corresponds to pins 4, 5 and 6; etc.
DigitalFlow™ XGS868i Programming Manual
Slot 1
. See Chapter 1, Installation, of the Startup Guide for a complete description of the
Chapter 1. Programming Site Data
Slot 0
. Also, a variety of input/output option
25