Daikin Altherma 3 R F Installer's Reference Manual page 49

Hide thumbs Also See for Altherma 3 R F:
Table of Contents
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
4P596806-1 – 2019.10
Mind the following spacing guidelines:
b
a
>250
b
a
>250
(mm)
a
Air outlet
b
Air inlet
NOTICE
The height of the wall on the outlet side of the outdoor unit MUST be ≤1200 mm.
NOTICE
Do NOT stack the units on each other.
Do NOT hang the unit on a ceiling.
Strong winds (≥18 km/h) blowing against the outdoor unit's air outlet causes short
circuit (suction of discharge air). This may result in:
deterioration of the operational capacity;
frequent frost acceleration in heating operation;
disruption of operation due to decrease of low pressure or increase of high
pressure;
a broken fan (if a strong wind blows continuously on the fan, it may start rotating
very fast, until it breaks).
It is recommended to install a baffle plate when the air outlet is exposed to wind.
It is recommended to install the outdoor unit with the air inlet facing the wall and
NOT directly exposed to the wind.
b
a
Baffle plate
b
Prevailing wind direction
c
Air outlet
>250
>350
b
>250
a
b
a
6
Unit installation
|
a
>250
b
>250
a
>350
b
Installer reference guide
49
Table of Contents
loading

Table of Contents