[ 9-0C ]
a
Room temperature
b
Actual room temperature
c
Desired room temperature
d
Time
#
Code
N/A
[9-0C]
Room temperature offset
ONLY applicable in case of room thermostat control. You can calibrate the room
temperature sensor. It is possible to give an offset to the room thermistor value
measured by the user interface. The settings can be used to compensate for
situations where the user interface cannot be installed on the ideal installation
location.
#
Code
Room temp. offset: Offset on the actual room temperature measured on the
user interface sensor.
[A.3.2.2]
[2-0A]
Room frost protection
Room frost protection prevents the room from getting too cold. This setting
behaves differently depending on the set unit control method ([C‑07]). Perform
actions according to the table below:
Unit control method ([C‑07])
Room thermostat control ([C‑07]=2)
External room thermostat control
([C‑07]=1)
Leaving water temperature control
([C‑07]=0)
NOTICE
Room frost protection. Even if you turn OFF the leaving water temperature (main +
additional) control via the home pages (LWT
protection –if enabled– will remain active.
INFORMATION
If a U4 error occurs, room frost protection is NOT guaranteed.
See the sections below for detailed information on room frost protection in
relation to the applicable unit control method.
d
Description
1°C~6°C
Description
–5°C~5°C, step 0.5°C
Room frost protection
Allow for the room thermostat to take
care of room frost protection:
Set [2‑06] to "1"
Set the room antifrost temperature
([2‑05]).
Allow for the external room thermostat
to take care of room frost protection:
Turn
ON
temperature home page.
Room frost protection is NOT
guaranteed.
main + LWT
9
Configuration
|
the
leaving
water
add), room frost