Electrical installation

8.3.5 To connect the electricity meters

Installer reference guide
100
Wires: 2 (per meter)×0.75 mm²
Electricity meters: 12 V DC pulse detection (voltage supplied by PCB)
[A.2.2.8] External kWh meter (meter 1)
[A.2.2.9] External kWh meter (meter 2)
INFORMATION
In case of an electricity meter with transistor output, check the polarity. The positive
polarity MUST be connected to X5M/6 and X5M/4; the negative polarity to X5M/5
and X5M/3.
1 Open the following (see
1 Top panel
2 Upper front panel
3 Upper switch box cover
2 Connect the electricity meters cable to the appropriate terminals as shown in
the illustration below.
A
B
A
B
3 Fix the cable with cable ties to the cable tie mountings.
"6.2.4 To open the indoor
S3S
S2S
3
4
5
6
3 4 5 6
4
unit" [
 54]):
X5M
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
4P596806-1 – 2019.10
1
3
2