8.3.6 To connect the domestic hot water pump

8.3.7 To connect the alarm output

ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
4P596806-1 – 2019.10
Wires: (2+GND)×0.75 mm²
DHW pump output. Maximum load: 2 A (inrush), 230 V AC, 1 A
(continuous)
[A.2.2] Options > [A.2.2.A] DHW pump
[7.3] Set schedules > [7.3.7] DHW pump
1 Open the following (see
1 Top panel
2 Upper front panel
3 Upper switch box cover
2 Connect the domestic hot water pump cable to the appropriate terminals as
shown in the illustration below.
A
B
A
B
3 Fix the cable with cable ties to the cable tie mountings.
Wires: (2+1)×0.75 mm²
Maximum load: 0.3 A, 250 V AC
[A.2.2.6.3] Alarm output
1 Open the following (see
"6.2.4 To open the indoor
M M2P
1~
1 2
X2M
"6.2.4 To open the indoor
8
Electrical installation
|
4
unit" [
 54]):
1
4
unit" [
 54]):
Installer reference guide
3
2
101