INSTALLATION AND MAINTENANCE INSTRUCTIONS
TC809EA1035 Monitor Module
SPECIFICATIONS
Communications Loop
Nominal Operating Voltage:
15-32 VDC
Average Operating Current:
400 µA, 1 comm. every 5 seconds,
(Standard 47K EOL)
Maximum Alarm Current
600 µA
Monitoring Line
EOL Resistance:
47K Ohms Standard
Maximum Wiring Resistance:
1.5K Ohms
Maximum Voltage to EOL:
11 Volts
Maximum Short Circuit Current:
217 µA
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer
to the control panel installation manual for detailed system information.
If the modules will be installed in an existing operational system, inform
the operator and local authority that the system will be temporarily out
of service. Disconnect power to the control panel before installing the
modules.
NOTICE: This manual should be left with the owner/user of this
equipment.
GENERAL DESCRIPTION
The TC809EA1035 monitor module can be installed in a single gang
junction box directly behind the monitored unit. Its small size and light
weight allow it to be installed without rigid mounting (see Figure 1). The
TC809EA1035 is intended for use in intelligent, two-wire systems where
the individual address of each module is selected using rotary decade
switches. It provides a two-wire initiating circuit for normally open
contact fire alarm and security devices.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module should only be connected to a
compatible control panel.