Selecting A Termination Resistor - Allen-Bradley 1203 Series User Manual

Remote i/o communications module
Table of Contents
3–2
Installing the Module
Selecting a Termination
Resistor
Artisan Scientific - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisan-scientific.com
Remote I/O Cables
Remote I/O communications modules are connected to Remote I/O
links with twinaxial cable used for Remote I/O and Data Highway
Plus (DH+) communications. When selecting a cable, remember the
following:
Only 1770-CD Belden #9463 is tested and approved for RIO and
DH+ installations. Using other cables is at your own risk.
The total cable length depends on the baud rate that you are
using. Refer to the following table:
Baud Rate
57.6 K
115.2 K
230.4 K
All three of the following conductors must be connected at each
node.
Color
Blue
Shield
Clear
Do not use a star topology. Only two cables may be connected at
any wiring point. You can use a series topology and daisy-chain
two wires at a point.
You must terminate both ends of a Remote I/O link to ensure proper
operation. This termination is required only at the ends of the
physical cable. Each Remote I/O link should have exactly two
termination resistors.
If the device that you connect is an end device on the Remote I/O
link, it must be terminated. Refer to the following table to select a
resistor.
Important: You must use an 82 ohm external termination resistor if
the link is operating at 230.4 kbps.
Device
Description
Programmable Controller Refer to its manual.
1336-GM1
Set J2 in position 1-2 for termination and 2-3 for no termination.
Refer to Figure 3.8. The jumper enables a 150 ohm resistor
(Using Jumpers)
1203-GD1, 1203-GK1, or
Connect a resistor between terminals 1 and 2 on the Remote I/O
1336-GM1
connector. Refer to Figure 3.4.
(Using an external termi-
Use an 82 ohm termination resistor unless a device requires a
nation resistor)
150 ohm termination resistor
The following scanners require 150 ohm termination resistors on the RIO link: 1771-SN, 1772-SD,
1772-SD2, 1775-SR, 1775-S4A, 1775-S4B, 6008-SQH1, and 6008-SQH.
The following adapters require a 150 ohm termination resistors on the RIO link: 1771-AS, 1772-ASB
(Series A), 1771-DCM.
The following devices require a 150 ohm termination resistors on the RIO link: 1771-AF.
Maximum Length
3,048 m (10,000 ft)
1524 m (5,000 ft)
762 m (2,500 ft)
Description
1
SH
2
.
.