Alarm A, B, And C Menus - Honeywell 301C User Manual

Hide thumbs Also See for 301C:
Table of Contents
Available languages

Available languages

 
Alarm A, B, and C Menus 
The screens for viewing alarm thresholds are combined in this manu‐
al. There will be either two or three levels, depending on transmitter 
type. 
 
If present, separate "MIN" and "MAX"levels permit manual control of 
the hysteresis of each alarm. Normally, the "MAX" level is set greater 
than "MIN." However, alarms can be made to trigger on falling con‐
centration (as with oxygen) by setting the "MAX" threshold smaller 
than the "MIN" threshold. 
 
With certain transmitters, only one threshold will be displayed. 
 
Additionally, with certain transmitters, the alarm thresholds are read‐
only at the controller. These thresholds can be set only at the trans‐
mitter. 
 
These are typical screens: 
 
 
 
Typical screen for viewing alarms A or B on XCD and XNX transmitters 
 
 
 
Typical screen for viewing or changing alarm A, B, or C thresholds on 
other transmitters. 
32 
 

Chapters

Table of Contents
loading

Table of Contents