How To Build A Title 24 Compliant System - Honeywell 301C User Manual

Hide thumbs Also See for 301C:
Table of Contents
Available languages

Available languages

 
How to Build a Title 24 Compliant System 
 
California Title 24 Part 6 specifies mandatory requirements for en‐
closed parking garages.  A compliant gas detection system can be con‐
structed from the Honeywell Analytics 301C24 and E³Point Network 
gas sensor.  This section describes how to configure the 301C control‐
ler to accomplish this. 
 
Glossary 
The terminology for a couple of technical concepts differs between 
Honeywell and California. 
 
California's 
Honeywell's 
Term 
proximity 
zone 
alarm 
 
 
Requirement:  Section 120.6(c)4 "CO concentration at all sensors is 
maintained at 25 ppm or less at all times." 
 
Solution: Create an event for each group such that if one or more 
sensors report a concentration greater than 25 ppm the event is acti‐
vated.   
 
 
Term 
A region of a garage containing several 
sensors.  Gas readings in the region are 
group 
presumed to be similar because of free 
air circulation. 
A notification from the gas detection 
fault 
system that the system is not working 
correctly. 
 
96 
Description 
 
  

Chapters

Table of Contents
loading