ACS-2plus
Item no. 026547, 026548
P31903-02-0G0-09
Software-Version
Subject to change
ZAC2P.00.0V0.10xx
without notice
2017-07-26
Table of Contents
loading

Summary of Contents for Honeywell ACS-2plus

  • Page 1 Installation Instructions ACS-2plus Item no. 026547, 026548 P31903-02-0G0-09 Software-Version Subject to change ZAC2P.00.0V0.10xx without notice 2017-07-26...
  • Page 3: Table Of Contents

    Installation instructions / ACS-2 plus Table of contents Safety instructions ............. . 6 Installation and subsequent extensions .
  • Page 4 Technical data 026548, ACS-2plus, 12 V version ....... . 89...
  • Page 5 Installation instructions / ACS-2 plus Appendix Master sheet for terminal assignment empty ........91 Master sheet for memory requirement calculation .
  • Page 6: Safety Instructions

    Installation instructions / ACS-2 plus Safety instructions Danger for device or user if ignoring the following safety instructions! Please read this manual carefully and completely before installing and starting to work with the ACS-2 plus. Only use the ACS-2 plus: - according to the designated use and - in technically perfect condition - in correctly installed condition...
  • Page 7: Symbols

    Installation instructions / ACS-2 plus Symbols The following symbols are used in this manual: Indicates danger. Non observance can create a risk for people or the machine. Gives important information on a subject, procedural information and warnings about steps you make that could have far-reaching consequences. Describes useful and practical mounting tips.
  • Page 8: Overview

    Installation instructions / ACS-2 plus Overview Functon (in alphabetical order) to set up via page S1 or º Setup Address Battery S1 or º Setup Baud rate Clock/Data Flashbank Interface card BU 4 / BU 5 Memory expansion BU 2 Power supply unit S1 or º...
  • Page 9: General Information

    Installation instructions / ACS-2 plus General information Access control systems are required if, for safety reasons, access to rooms or buildings is reserved to a certain group of persons only. Software Novar GmbH offers a powerful and practice-oriented access control system. MultiAccess for Windows or IQ MultiAccess is the parent user software for the connected access control devices.
  • Page 10: Protective Measures

    Installation instructions / ACS-2 plus Protective measures Protective measures against electrostatic discharge Modern semiconductor devices are increasingly endangered by electrostatic charges. The higher the integration density the finer the structures on the chip. This leads to increased stress susceptibility. With certain semiconductor devices, damage may already be caused at a voltage of less than 20V. This is a very low value if you consider that, when walking over a carpet, more than 1000V may be generated.
  • Page 11: Important Installation Instructions

    Installation instructions / ACS-2 plus Important installation instructions (See also chapter 2 = Safety instructions) Grounding / shielding Use shielded lines and a suitable shielding connection for protection against electromagnetic interference couplings occurring, for example, when switching electric appliances on and off. Make sure that the line shields in the distribution boxes are connected so that there are no links to other potentials.
  • Page 12: Shielded Lines

    Installation instructions / ACS-2 plus Shielded lines Die ACS-2 plus devices are daisy chained via a shielded line. Use cables of category Cat 5 or higher! The shielding of the incoming line is to be connected to the shield soldering bar of the ACS-2 plus. The shielding of the outgoing line is not connected.
  • Page 13: Supply Voltage And Cables

    Installation instructions / ACS-2 plus Supply voltage and cables Please observe the informations about grounding and shielding in chapter 5.2. 5.3.1 ACS-2 plus 230 V version Parameter Value operating voltage range 230 V AC –15% +10% mains frequency 40 – 60 Hz power supply cable type NYM 3 x 1,5 mm²...
  • Page 14 Installation instructions / ACS-2 plus The voltage diagrams 1 and 2 compare the effects of two cable cross-sections. The required line cross-section must be calculated using the graphs shown above. Note! Pay attention to legal rulings! The local requirements must be observed for the line cross-section. VDE 0100 applies to Germany.
  • Page 15: Interface And Bus Topology

    Installation instructions / ACS-2 plus Interface and bus topology Interface technology, RS485 bus systems There are two types of data transmission, point-to-point connection and multipoint connection. Point-to-point connection means that two controllers are communicating with each other. A point-to-point connection can be realized by means of an RS232 and a current loop interface. Multipoint connection means that several controllers are communicating with each other.
  • Page 16: Potential Separation And Terminating Resistor

    Installation instructions / ACS-2 plus 6.1.3 Potential separation and terminating resistor Potential separation Each RS485 line must be provided with one non-floating interface. The other interfaces must be floating. The best position of the non-floating interface is in the middle of the RS485 line. The ACS-2 plus, fitted with the interface which is not floating, must have a good grounding.
  • Page 17: Ethernet Connection (Rj45)

    Installation instructions / ACS-2 plus 6.1.4 Ethernet connection (RJ45) When installing an Ethernet interface card (Item no. 026840.29) instead of an RS 485 interface card, the ACS-2 plus can be linked to an existing network via Ethernet. For more information about the interface installation, please refer to the mounting and installation instructions for the interface.
  • Page 18 Installation instructions / ACS-2 plus Example 3: Remote data transmission (RDT) and network Remote data transmission (RDT): Remote stations can be managed via Remote data transmission. It is possible to link one ACS-8 controller to one modem. Network: MultiAccess for Windows or IQ MultiAccess makes it possible to use existing networks. MultiAccess for Windows can be accessed from up to 64 workstations.
  • Page 19: Interface Connections

    Installation instructions / ACS-2 plus Interface connections These interface- connections and the following two tables help you to find the required pin assignment. The data lines must be switched between the interface converter and the first RS485 device. All following devices are to be connected 1 : 1...
  • Page 20: Pin Assignment Tables

    Installation instructions / ACS-2 plus Pin assignment tables Table 1: Pin assignment of interface converter and PC. Device RS232 RS485 (3-wire) RS485 (5-wire) Current Loop COM1/COM2 9-pole COM1/COM2 25-pole Interface converter Table 2: Pin assignment of the controllers/terminals Device RS232 RS485 (3-wire) RS485 (5-wire) Current...
  • Page 21: Connection Examples

    Installation instructions / ACS-2 plus Connection examples Example 1: Connection via interface converter RS485 5-wire technique. Example 2: Connection via Ethernet.
  • Page 22: Configuration

    Installation instructions / ACS-2 plus Configuration The ACS-2 plus controls the access to a room. The use of an additional interior reader makes it possible to control also the exit of a room. The readers must function according to the same reading principle (magnetic card reader, contactless reader or chip card reader).
  • Page 23: Mounting

    Installation instructions / ACS-2 plus Mounting Installation site The installation site of the central unit must meet the following conditions: * within the indoor area of a building * within the secured area * easily accessible * no extraordinary environmental conditions, e.g., aggresive vapors, high humidity, etc.
  • Page 24: Installing The Interface

    Installation instructions / ACS-2 plus The commissioning of the device is described in chapter 10. The individual steps to be carried out while the cover housing is open must be checked. Then mount the housing cover, close it with the housing screws and seal it. To assure safe and easy working, we recommend removing the battery holder during the installation of the peripheral devices.
  • Page 25: Inserting / Changing Lithium Battery

    Since the status of the battery cannot be clearly determined it is recommended that the battery be changed every two years. Lithium battery (type CR 2477N, 3 V 950 mAh) for data preservation in ACS-2plus = item no. 018050. “Battery empty” Message The ACS-2plus continuously checks the status of the lithium battery.
  • Page 26 Installation instructions / ACS-2 plus Example in IQ MultiAccess: In IQ NetEdit: a) Logical view b) Select controller c) Reset alarms/notifications d) Select alarm to reset. or in IQ MultiAccess (as of V7) a) Controllers b) Select controller c) “Common” tab d) Reset alarms/notifications e) Select alarm to reset.
  • Page 27 Installation instructions / ACS-2 plus Notes on environment / disposal Batteries and recharchable batteries - even free from heavy metal - must not be disposed of in domestic waste. According to EU guidline 2006/66/EG users are obligated to return batteries for recycling. In Germany they will be accepted for free at each selling point;...
  • Page 28: Dip Switches On The Cpu Board

    Installation instructions / ACS-2 plus DIP switches on the CPU board (See also chapter 1 = Overview and chapter 14 = CPU component mounting diagram) 8.5.1 DIP switch S1 Table 1: Addresses Function Address 1 = factory setting Address 2 Address 3 Address 4 Address 5...
  • Page 29 Installation instructions / ACS-2 plus Table 2: Protocol and Baud rate Function Connected to Comment Setup via terminal e. g. Event protocol (for The switch positions 1-7 are program ethernet) ignored (see chapter 11). 9-Bit-Protocol = factory With these protocols, the setting baud rate is set at 19200.
  • Page 30: Dip Switch S2

    Installation instructions / ACS-2 plus Table 5: Special function for ACS-2 plus Setup (see Chapter 10). Function Setup via hyperterminal An unintentional activation of the switch 8 can be ignored by resetting it to OFF (while the LED 1 flashes). After the reset, the device does not switch to the service mode and the switches keep their original meaning.
  • Page 31: Memory Extension

    Installation instructions / ACS-2 plus Memory extention The ACS-2 plus is equipped with a 1MByte memory which is firmly mounted on the CPU board. The following additional memory extensions are possible: - 026596 1 MB RAM memory card - 026597 2 MB RAM memory card - 026598 3 MB RAM memory card...
  • Page 32 Installation instructions / ACS-2 plus The gray highlighted fields must be filled in 1. Calculation of the memory requirements for the cards Header: This is a preset value using 13 bytes for each card. ID no.: Enter the number of digits of the identification code to be used in the column no. of digits ...
  • Page 33 Installation instructions / ACS-2 plus Indexing: If indexing is employed, each werden je Ausweis 6 BYTES belegt. Without indexing, the  value of this field is 0. Macros An ACS-2 plus can manage up to 64 macros. Enter in the column no. of digits required ...
  • Page 34 Installation instructions / ACS-2 plus 3. Calculation of the memory required for bookings Booking: Each booking occupies 9 bytes. Multiply this value by the number of bookings to be stored and enter the result in the column total. A unique fixed value of 45 bytes is required for the bookings. Add this value to the value of the field total and enter the result in the field memory requirements.
  • Page 35 Installation instructions / ACS-2 plus Example: The memory requirements for an ACS-2 plus controller is to be calculated based on the following conditions: 10,000 ESSER coded contactless cards  6-digit PIN code  20 room/time zones  Antipassback control  Control of 7 macros ...
  • Page 36: Inserting / Changing Memory Card

    Caution! Data loss possible! Never insert or remove the memory card while the ACS 2plus is powered up! If the memory card is removed, all of the ACS-2plus data is irrevocably lost. Danger of data loss / disruption in operation! All data will be lost if the device is set to dead-voltage and the battery is removed.
  • Page 37: Dimensioning Of The Power Supply Unit And The Battery

    Installation instructions / ACS-2 plus Dimensioning of the power supply unit and the battery Dimensioning of the power supply unit The ACS-2 plus (Item no.026547) is delivered with a power supply/charging unit. The ACS-2 plus (Item no.026548) is delivered without a power supply unit. The power supply is to be mounted seperately or you can use an already existing power supply, e.
  • Page 38 Installation instructions / ACS-2 plus The end-of-charging voltage of the battery charging unit is correctly set in the factory for Sonnenschein batterys of the A500 series. If it is necessary to change the setting, proceed as described in the chapter "Adjusting the end-of-charging voltage".
  • Page 39: Integrated Power Supply Unit

    Installation instructions / ACS-2 plus Integrated power supply unit Fully electronic power supply/ charging unit Voltage stabilized Current limitation Redundancy standby operation with battery monitoring Total discharge protection Charge monitoring Battery fault detection Up to 2Ah battery capacity Directives for the power supply The power supply must be connected to the mains via a separate fuse.
  • Page 40 Installation instructions / ACS-2 plus Functional description Two independent control loops are mounted on the mother board. First control loop: It supplies the central unit and the connected readers. - protected with 2.0 AF (including external consumers) Second control loop: It is used to charge the batterys.
  • Page 41 Installation instructions / ACS-2 plus Adjusting the end-of-charging voltage The power supply must have reached the operating temperature. This requires the power supply to be switched on for at least two hours with rated load and closed housing. Connect the charged battery. An incompletely charged battery leads to an incorrect adjustment! Adjust the voltage at the battery terminals by means of the RV2 potentiometer under consideration of the ambient temperature according to the table below.
  • Page 42 Installation instructions / ACS-2 plus Connection/component mounting diagram...
  • Page 43: Commissioning

    Installation instructions / ACS-2 plus 10. Commissioning During commissioning of the ACS-2 plus, the following steps must be carried out: Insertion of the back-up battery (see chapter 8.4). Connection to the mains. Bootstrap via the DIP switch S1 (see chapter 8.5.1, table 4). The ACS-2 plus is brought to the defined initial state.
  • Page 44 Installation instructions / ACS-2 plus Requirements: Laptop / notebook Terminal program (e.g., Hyperterminal, Telemate, etc. 9-pole serial cable (socket - socket) Cable assignment: Procedure: Set DIP switch S1 1-8 to OFF / 0:  Function Setup via hyperterminal Turn the controller off briefly or press the Reset button. ...
  • Page 45 Installation instructions / ACS-2 plus In the following window under Connect using, select the  interface of the notebook to which the cable is connected (COM1 in our example). The entries in the other fields are irrelevant. In the next window, select the following settings and confirm ...
  • Page 46 Installation instructions / ACS-2 plus This will open the ACS-2 plus setup: ****************************************************************************** SETUP - ACS-2 plus ****************************************************************************** Setup from: APPL. Login. Label: [] 1. Communication 2. System 3. Save 4. Exit No.:_ Meanings: Setup from: Shows the mode via which the setup was called. APPL.-Login = Application login ...
  • Page 47 Installation instructions / ACS-2 plus press the Reset button. Normally, the APPL.-Login is sufficient. Advantages: The normal course of operations is not disturbed. Login must not be carried out within the above mentioned 3 seconds during the booting process. Certain DIP switch settings have priority and do not permit any modifications in the Communication - To Host area (see section Dependencies in this chapter).
  • Page 48 Installation instructions / ACS-2 plus Example: 9-bit AC/CU Prot. 2.=>DIN prot. RDT prot. Event prot. Status: Addr: 32; GAddr: 30; 19200 Baud Change? Y/N:_ The current value is marked with "=>". To modify the values enter "y" and confirm with Enter. Then you can select one of the consecutive numbers. Settings and their use: 9-bit AC/CU prot.: ------...
  • Page 49 Installation instructions / ACS-2 plus necessary: MVA: My Virtual Address. When using the event protocol, the communication between the controller and the host is controlled by events, i.e., as soon as a booking is carried out on the controller, the booking is sent to the host by the controller.
  • Page 50 Installation instructions / ACS-2 plus Network device: In this field the network card used must be entered. Example: 1=>W&T Com-Server 2 = Novar TR/AC Ethernet (Item no. 026840.20) Change? Y/N:_ 2. System: This menu items offers the following possibilities: 1. Software version 2.
  • Page 51: Defining The Controller In Netedit

    Installation instructions / ACS-2 plus Settings for netwerk connection with Ethernet card: As described previously, the following settings must be carried out: Event protocol  Baud rate 19200  MVA (virtual address of the current controller from NetEdit).  DVA (virtual target address of the computer communicated with that of the controller = MVA ...
  • Page 52: Leds, Buzzer And Buzzer Stop Push-Button

    The LEDS, the buzzer and the buzzer stop push-button are located on the LED board in the housing cover. For differentiation of the controller types ACS-2plus and ACS-2 plus, the ACS-2 plus from firmware 7.00 on activates all LEDs and the buzzer while booting.
  • Page 53 Installation instructions / ACS-2 plus Functions of the LEDs and the buzzer of the ACS-2 plus LED/buzzer State Meaning No operating voltage Slow flashing Not parameterized Normal (green) Fast flashing Parameterization running Ready No fault Battery/battery fault Without storing Fault (yellow) Line failure (except for central reset) Central reset...
  • Page 54: Outputs

    Installation instructions / ACS-2 plus 12. Outputs 12.1 Semiconductor outputs The ACS-2 plus board is provided with 3 semiconductor outputs: output 5 (terminal 24) and the output 6 (ST 5-3) are freely programmable via NetEdit. watchdog output (ST 5-2) signals (12V) that at least one watchdog reset occurred since the last hardware reset.
  • Page 55: Inputs

    Installation instructions / ACS-2 plus ST 16 Description 1 - 3 Relay 3 (alarm) is activated during system failure 2 - 4 Relay 4 (tamper) is activated during system failure 3 - 5 Relay 3 (alarm) is deactivated during system failure 4 - 6 Relay 4 (tamper) is deactivated during system failure 13.
  • Page 56: Structure/Diagram

    Installation instructions / ACS-2 plus 14. Structure/diagrams 14.1 CPU component mounting diagram S1, S2, S3, S4: See also chapter 8.5 = DIP switches.
  • Page 57 Installation instructions / ACS-2 plus Description of the CPU board shown on the opposite page Number Explanation Extention plug for external modem certified byNovar GmbH w.o. function Power supply unit connector PIN 1+ 2 = OPEN PIN 3 >1V-> battery fault PIN 4 = 10-15V PIN 5 = 0V PIN 6 >1V->...
  • Page 58: Acs-2 Plus-Structure

    Installation instructions / ACS-2 plus 14.2 ACS-2 plus structure...
  • Page 59: Connections

    Installation instructions / ACS-2 plus 15. Connections 15.1 Terminal assignment The standard factory settings of the inputs and outputs are described in this overview. However, individual assignments are also possible if required. In this case, we recommend noting the changed assignment for each ACS-2 plus controller.
  • Page 60: General Connection Diagram

    Installation instructions / ACS-2 plus 15.2 General connection diagram 15.3 Pin assignment of the host interface connections RS232 RS485 (3-wire) RS485 (5-wire) Current loop T GND R GND Inputs 11 and 12 as well as watchdog and danger signal output see chapters 13.2 and 14.1...
  • Page 61: Connecting A Door Strike

    Installation instructions / ACS-2 plus 15.4 Connecting a door strike 15.4.1 Connecting a fail secure door strike Fail secure door strike = strike with load current function: The door is released if the coil is energized Tamper monitoring for the strike with load current function is possible. For this, a DC door strike must be connected as shown above.
  • Page 62: Connecting A Fail Safe Door Strike (With No Load Current Function)

    Installation instructions / ACS-2 plus 15.4.2 Connecting a fail safe door strike Fail safe door strike = no-load current door strike: The door is blocked if the coil is energized Tamper monitoring for the fauil safe door strike is not possible. ACS-2 plus terminal assignment: for relay 1: jumper ST6 = 2 -4...
  • Page 63: Electric Safety Lock

    Installation instructions / ACS-2 plus 15.5 Electric safety lock The electric safety lock is available in a conventionally connectable variant (809) as well as in a BUS version (809N). 16.5.1 Electric safety lock conventional connection The differential alarm lines (inputs 5 - 10) must be terminated with 12K1. Door monitoring The interior door handle contact activates a door release on the ACS-2 plus.
  • Page 64 Installation instructions / ACS-2 plus 15.5.1 Electric safety lock conventional connection The differential monitored inputs (inputs 5 - 10) must be terminated with 12KΩ resistor. The electrical safety lock is connected via the I / O module N5950. This module provides the BUS connection to the electric safety lock.
  • Page 65: Turnstile

    Installation instructions / ACS-2 plus 15.6 Turnstile The ACS-2 plus can manage, besides a standard door, 3 types of turnstiles. They differ from each other by the number or the evaluation of the monitoring contacts. Flow chart of a door monitoring with monitoring contacts to a “normal” door: With the door closed, the monitoring contact is likewise closed.
  • Page 66: Turnstile With Two Separate Monitoring Contacts

    Installation instructions / ACS-2 plus 15.6.2 Turnstile with two monitoring contacts in common In this variation, depending on the rotary direction, first the one monitoring contact is activated and then the other. The rotational direction is detected by means of the sequence. Left rotational direction: = Exterior reader enabled.
  • Page 67 Installation instructions / ACS-2 plus 15.6.3 Turnstile with 2 two separate monitoring contacts This variation corresponds basically to point 16.4.3, but the way in which the contact makers of the monitoring contacts are organized results in a modified pulse sequence: Left rotational direction: = Exterior reader activated.
  • Page 68: Connection Diagrams

    Installation instructions / ACS-2 plus 16. Connection diagrams Connection diagram for: 026010.00 Magnetic card mortise reader, sm 026016.00 Motorized magnetic card reader, sm 026342.00 Chip card reader, sm 026345.00 Chip card reader module for Siedle “Vario” System, item no. 027545 - 027548 026053.00 Magnetic card swipe reader, sm...
  • Page 69 Installation instructions / ACS-2 plus Connection diagram for: 026011.00 Magnetic card mortise reader, fm 026017.00 Motorized magnetic card reader, fm The terminals 14 and 15 of the reader must only be connected with motorized readers. If only one reader is used, this reader is always connected as reader 1. ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus (see chapter 8.5):...
  • Page 70 Installation instructions / ACS-2 plus Connection diagram for: 027710 Magnetic card mortise reader, sm, with keypad 027711 Motorized magnetic card reader, sm 027712 Magnetic card reader, sm 027740 Chip card reader, sm, without keypad 027741 Chip card reader, sm, with keypad If only one reader is used, this reader is always connected as reader 1.
  • Page 71 Installation instructions / ACS-2 plus Connection diagram for 026046.00 Magnetic card mortise reader, sm, with keypad 026047.00 Motorized magnetic card reader, sm, with keypad 026343.00 Chip card reader, sm, with keypad 026054.00 Magnetic card swipe reader, sm, with keypad If only one reader is used, this reader is always connected as reader 1. ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus (see chapter 8.5):...
  • Page 72 Installation instructions / ACS-2 plus Connection diagram for: 026340.00 Chip card reader, fm 027470.10 Magnetic card reader module for Siedle “Vario” System, item no. 027545 - 027548 027580 "Plug in" magnetic card reader If only one reader is used, this reader is always connected as reader 1. ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus (see chapter 8.5):...
  • Page 73 Installation instructions / ACS-2 plus Connection diagram for: 026366.00 Contactless reader, increased reading range 026366.10 Contactless reader, increased reading range If only one reader is used, this reader is always connected as reader 1. ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus (see chapter 8.5): Switch Position...
  • Page 74 Installation instructions / ACS-2 plus Connection diagram for: 026383.00 Contactless reader, sm, with keypad If only one reader is used, this reader is always connected as reader 1. ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus (see chapter 8.5): Switch Position...
  • Page 75 Installation instructions / ACS-2 plus Connection diagram for: 026387.00 Contactless reader, fm If only one reader is used, this reader is always connected as reader 1. ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus (see chapter 8.5): Switch Position...
  • Page 76 Installation instructions / ACS-2 plus Connection diagram for: 026492 Legic reader without keypad, sm 026494 Mifare reader without keypad, sm 026481 Contactless reader with keypad, sm 026390.00 Contactless reader, sm 026390.10 Contactless reader, sm 026491 Legic reader with keypad, sm 026493 Mifare reader with keypad, sm If only one reader is used, this reader is always connected as reader 1.
  • Page 77 Installation instructions / ACS-2 plus Connection diagram for: 026420 Accentic reader proX2 without keypad 026421 Accentic reader proX2 with keypad 026422 Accentic reader mifare without keypad 026423 Accentic reader mifare with keypad 026424 Accentic reader Legic without keypad 026425 Accentic reader Legic with keypad If only one reader is used, it is always connected as reader 1.
  • Page 78 Installation instructions / ACS-2 plus Connection diagram for: 029340 Accentic Fingerkey IK3 029341 Accentic Fingerkey mifare If only one reader is used, it is always connected as reader 1. Terminal assignment ACS-2 plus: Settings of the DIP switches located on the CPU board of the ACS-2 plus (see chapter 8.5): Switch Setting...
  • Page 79 Installation instructions / ACS-2 plus Connection diagram for: 027660 Insertic 50 reader proX1/2 027662 Insertic 50 reader mifare 027664 Insertic 50 reader Legic 027666 Insertic reader proX1/2 without keypad 027667 Insertic reader proX1/2 with keypad 027670 Insertic reader mifare without keypad 027671 Insertic reader mifare with keypad 027676...
  • Page 80 Installation instructions / ACS-2 plus Connection diagram for: 026480 Contactless reader, sm 026480.10 Contactless reader, sm If only one reader is used, this reader is always connected as reader 1. ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus (see chapter 8.5): Switch Position...
  • Page 81 Installation instructions / ACS-2 plus Connection diagram for: 026484 Legic reader (Oris) 026485 Mifare reader (Oris) If only one reader is used, this reader is always connected as reader 1. ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus (see chapter 8.5): Switch Position...
  • Page 82 Installation instructions / ACS-2 plus Connection diagram for: 027540 - 027543 proximity / contactless reader, Siedle If only one reader is used, it is always connected as reader 1. Terminal assignment ACS-2 plus: Settings of the DIP switches located on the CPU board of the ACS-2 plus (see chapter 9.6): Switch Setting...
  • Page 83 Installation instructions / ACS-2 plus Connection diagram for: 023330 - 023343 contactless proX2 reader Siedle If only one reader is used, it is always connected as reader 1. Terminal assignment ACS-2 plus : Settings of the DIP switches located on the CPU board of the ACS-2 plus (see chapter 9.6): Switch Setting...
  • Page 84 Installation instructions / ACS-2 plus Connection diagram for: 027575 Contactless reader “Plug in” 027575.20 Contactless reader “Plug in” 027577 Mifare reader “Plug in” 027579 Legic reader “Plug in” If only one reader is used, this reader is always connected as reader 1. ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus (see chapter 8.5):...
  • Page 85 Installation instructions / ACS-2 plus Connection diagram for: 027570.20 Keypad with analogue interface, “Plug in”...
  • Page 86 Installation instructions / ACS-2 plus Connection diagram for: 026070.02 Keypad, sm housing 026072.02 Keypad, fm housing 026071.02 Keypad, sm housing, splashproof 026073.02 Keypad, fm housing, splashproof...
  • Page 87 Installation instructions / ACS-2 plus Connection diagram for: 026064 Keypad, sm plastic housing...
  • Page 88 Installation instructions / ACS-2 plus...
  • Page 89 Installation instructions / ACS-2 plus...
  • Page 90: Connections / Technical Data

    Installation instructions / ACS-2 plus 17. Connections / technical data 17.1 Connections Interface to the host system: 1 x interface slot inserted with: - RS232 interface (026840.03) - RS485 interface (026692, 026693) - Ethernet interface (026840.29) - Current-Loop interface (026840.16) Keypad: 2 x external keypads with 2-wire technique connectable.
  • Page 91 Installation instructions / ACS-2 plus Appendix Master sheet for terminal assignment, empty (For the documentation of individual in- and output assignments deviating from the standard assignment) Master sheet for the calculation of the memory requirements, empty (For the calculation of the memory requirements for the ACS-2 plus controllers) Factory settings Index...
  • Page 92 Installation instructions / ACS-2 plus Terminal assignments deviating from the standard Company:........................... Device No...........Site:.................
  • Page 93 Installation instructions / ACS-2 plus...
  • Page 94 Installation instructions / ACS-2 plus Factory settings List in alphabetic order: Function Factory setting Switch block Chapter Table Address Address 1 1 = OFF 2 = OFF 3 = OFF 4 = OFF 5 = OFF Baud rate 19200 6 = OFF 7 = ON Clock/Data Modus Clock 1 (Pull down)
  • Page 95 Installation instructions / ACS-2 plus Index Access control system ..................9 Access rights .
  • Page 96 Installation instructions / ACS-2 plus IQ NetEdit ..................31, 41, 43, 59 Jumpers .
  • Page 97 Installation instructions / ACS-2 plus...
  • Page 98 Honeywell Security and Fire Solutions Novar GmbH Johannes-Mauthe-Straße 14 D-72458 Albstadt P31903-02-0G0-09 2017-07-26 www.honeywell.com/security/de © 2017 Novar GmbH...